North Carolina Administrative Code
Title 15A - Environmental Quality
Chapter 18 - ENVIRONMENTAL HEALTH
Subchapter A - ENVIRONMENTAL HEALTH
Section .1700 - PROTECTION OF WATER SUPPLIES
Section 18A .1725 - WATER QUALITY
Current through Register Vol. 39, No. 6, September 16, 2024
(a) Prior to the initial use of a water supply, or after construction, maintenance, repairs, pump installation, or a report of a positive coliform sample, two consecutive bacteriological water samples taken at least 48 hours apart shall be collected by the Department and submitted to the Division of Laboratory Services of the Department of Environment, Health, and Natural Resources or another laboratory certified pursuant to 15A NCAC 20D for analysis. Prior to collecting the sample, the water shall be tested and shall be negative for chlorine residual. For the purposes of this Rule, confirmation means another positive sample result following the initial positive sample unless the last positive sample was preceded by two consecutive negative samples.
(b) The water supply shall be deemed an imminent hazard under the following circumstances:
(c) The water supply shall be deemed unsafe for use under the following conditions:
(d) After a positive sample has been followed by two consecutive negative samples collected at least 48 hours apart, follow-up samples shall be collected by the Department at least once each quarter, while the supply is in use, for one year. There shall be no treatment procedures between the two consecutive negative samples.
Authority
G.S.
95-225;
130A-5(3);
130A-230;
130A-235;
130A-236;
130A-248;
130A-257;
Eff. July
1, 1993;
Amended Eff. May 1, 1996;
Pursuant to
G.S.
150B-21.3A, rule is necessary without
substantive public interest Eff. July 20,
2019.