North Carolina Administrative Code
Title 15A - Environmental Quality
Chapter 02 - ENVIRONMENTAL MANAGEMENT
Subchapter U - RECLAIMED WATER
Section .0400 - DESIGN STANDARDS
Section 02U .0403 - DESIGN CRITERIA FOR DISTRIBUTION LINES
Current through Register Vol. 39, No. 6, September 16, 2024
(a) The requirements in this Rule shall apply to all new distribution lines.
(b) All reclaimed water valves, storage facilities, and outlets shall be tagged or labeled to warn the public or employees that the water is not intended for drinking.
(c) All reclaimed water piping, valves, outlets, and other appurtenances shall be color-coded, taped, or otherwise marked to identify the source of the water as being reclaimed water as follows:
(d) All reclaimed water valves and outlets shall be of a type, or secured in a manner, that permits operation by personnel authorized by the entity that operates the reclaimed water system.
(e) Hose bibs shall be located in locked, below grade vaults that shall be labeled as being of nonpotable quality. As an alternative to the use of locked vaults with standard hose bib services, other locking mechanisms such as hose bibs that can only be operated by a tool may be placed above ground and labeled as nonpotable water.
(f) There shall be no direct cross-connections between the reclaimed water and potable waters systems, unless such connection has been approved by the Department pursuant to 15A NCAC 18C .0406.
(g) Irrigation system piping shall be considered part of the distribution system for the purposes of this Rule.
(h) Reclaimed water distribution lines shall be located at least 5 feet horizontally from and 18 inches below any water line if practicable. If these separation distances cannot be met, the piping and integrity testing procedures shall meet water main standards in accordance with 15A NCAC 18C.
(i) Reclaimed water distribution lines shall not be less than 50 feet from a well unless the piping and integrity testing procedures meet water main standards in accordance with 15A NCAC 18C, but in no case shall they be less than 25 feet from a private well.
(j) Reclaimed water distribution lines shall meet the separation distances to sewer lines in accordance with 15A NCAC 02T .0305.
Authority
G.S.
143-215.1;
143-215.3(a);
Eff. June 18, 2011 (S.L. 2011-218);
Readopted Eff. March 21,
2019.