North Carolina Administrative Code
Title 15A - Environmental Quality
Chapter 02 - ENVIRONMENTAL MANAGEMENT
Subchapter U - RECLAIMED WATER
Section .0300 - EFFLUENT STANDARDS
Section 02U .0301 - RECLAIMED WATER EFFLUENT STANDARDS

Universal Citation: 15A NC Admin Code 02U .0301

Current through Register Vol. 39, No. 6, September 16, 2024

(a) Reclaimed water treatment processes producing an effluent quality prior to storage, distribution, or utilization that meets the parameter limits listed below shall be classified as Type 2:

(1) monthly average five-day biochemical oxygen demand (BOD5) of less than or equal to 5 mg/L and a daily maximum BOD5 of less than or equal to 10 mg/L;

(2) monthly average total suspended solids (TSS) of less than or equal to 5 mg/L and a daily maximum TSS of less than or equal to 10 mg/L;

(3) monthly average ammonia (NH3-N) of less than or equal to 1 mg/L and a daily maximum NH3-N of less than or equal to 2 mg/L;

(4) monthly geometric mean Escherichia coli (E. coli) or fecal coliform level of less than or equal to 3/100 mL and a daily maximum E. coli or fecal coliform level of less than or equal to 25/100 mL;

(5) monthly geometric mean Coliphage level of less than or equal to 5/100 mL and a daily maximum Coliphage level of less than or equal to 25/100 mL;

(6) monthly geometric mean Clostridium perfringens level of less than or equal to 5/100 mL and a daily maximum Clostridium perfringens level of less than or equal to 25/100 mL; and

(7) maximum turbidity of 5 Nephelometric Turbidity Units (NTUs).

(b) Reclaimed water treatment processes producing an effluent quality prior to storage, distribution, or utilization that meets the parameter limits listed below shall be classified as Type 1:

(1) monthly average five-day biochemical oxygen demand (BOD5) of less than or equal to 10 mg/L and a daily maximum BOD5 of less than or equal to 15 mg/L;

(2) monthly average total suspended solids (TSS) of less than or equal to 5 mg/L and a daily maximum TSS of less than or equal to 10 mg/L;

(3) monthly average ammonia (NH3-N) of less than or equal to 4 mg/L and a daily maximum NH3-N of less than or equal to 6 mg/L;

(4) monthly geometric mean Escherichia coli (E. coli) or fecal coliform level of less than or equal to 14/100 mL and a daily maximum E. coli or fecal coliform level of less than or equal to 25/100 mL; and

(5) maximum turbidity of 10 NTUs.

(c) Reclaimed water produced by industrial facilities shall not be required to meet the criteria in this Rule if the reclaimed water is used at the facility in an industrial process and the area of use has no public access and does not result in employee exposure.

Authority G.S. 143-215.1; 143-215.3(a);
Eff. June 18, 2011;
Readopted Eff. September 1, 2018.

Disclaimer: These regulations may not be the most recent version. North Carolina may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.