North Carolina Administrative Code
Title 15A - Environmental Quality
Chapter 02 - ENVIRONMENTAL MANAGEMENT
Subchapter N - CRITERIA AND STANDARDS APPLICABLE TO UNDERGROUND STORAGE TANKS
Section .0300 - UST SYSTEMS: DESIGN, CONSTRUCTION, INSTALLATION, AND NOTIFICATION
Section 02N .0301 - PERFORMANCE STANDARDS FOR UST SYSTEM INSTALLATIONS OR REPLACEMENTS COMPLETED AFTER DECEMBER 22, 1988 AND BEFORE NOVEMBER 1, 2007
Current through Register Vol. 39, No. 6, September 16, 2024
(a) The regulations governing "Performance standards for new UST systems" set forth in 40 CFR 280.20 are hereby incorporated by reference, excluding any subsequent amendments and editions, except that:
(b) No UST system shall be installed within 100 feet of a well serving a public water system, as defined in G.S. 130A-313(10), or within 50 feet of any other well supplying water for human consumption.
(c) An UST system existing on January 1, 1991, and located within the area described in Paragraph (b) of this Rule may be replaced with a new tank meeting the performance standards of 40 CFR 280.20 and the secondary containment provisions of 40 CFR 280.42(a) through (d). The replacement UST system shall not be located nearer to the water supply source than the UST system being replaced.
(d) Except as prohibited in Paragraph (b) of this Rule, an UST system shall meet the requirements for secondary containment described at 40 CFR 280.42(a) through (d):
(e) An UST system or UST system component installation completed on or after November 1, 2007, to replace an UST system or UST system component located within the areas described in Paragraphs (b), (c), or (d) of this Rule shall meet the requirements of Section .0900 of this Subchapter.
Authority
G.S.
143-215.3(a)(15);
143B-282(a)(2)(h);
Eff. January 1, 1991;
Amended Eff. June 1, 2017; November 1,
2007;
Readopted Eff. January 1,
2021.