North Carolina Administrative Code
Title 15A - Environmental Quality
Chapter 02 - ENVIRONMENTAL MANAGEMENT
Subchapter D - AIR POLLUTION CONTROL REQUIREMENTS
Section .2600 - SOURCE TESTING
Section 02D .2611 - SULFUR DIOXIDE TESTING METHODS
Current through Register Vol. 39, No. 6, September 16, 2024
(a) If compliance with a sulfur dioxide emission standard is to be demonstrated for a combustion source through stack sampling, the procedures described in Method 6 or Method 6C to Appendix A of 40 CFR Part 60 shall be used as follows:
(b) Method 8 of Appendix A to 40 CFR Part 60 shall be used to determine compliance with emission standards for sulfuric acid manufacturing plants governed by 15A NCAC 02D .0517 and spodumene ore roasting plants governed by 15A NCAC 02D .0527. Compliance shall be determined by averaging emissions measured from three one-hour test runs, unless otherwise specified in the applicable rule or federal subpart.
(c) For stationary gas turbines, Method 20 of Appendix A to 40 CFR Part 60 shall be used to demonstrate compliance with applicable sulfur dioxide emissions standards.
(d) Fuel burning sources not required to use continuous emissions monitoring to demonstrate compliance with sulfur dioxide emission standards may determine compliance with sulfur dioxide emission standards by stack sampling or by analyzing sulfur content of the fuel.
(e) For a combustion source demonstrating compliance with the sulfur dioxide emission standards by analysis of sulfur in fuel, the sampling, preparation, and analysis of fuels shall be according to the following American Society of Testing and Materials (ASTM) methods. The Director shall approve ASTM methods different from those described in this Paragraph if they will provide equivalent results. The Director shall prescribe alternate ASTM methods on an individual basis if that action is necessary to secure reliable test data.
(f) If the test methods described in Subparagraph (e)(1) or (e)(2) of this Rule are used to demonstrate that the ambient air quality standards for sulfur dioxide set forth in 15A NCAC 02D .0402 are not exceeded, the sulfur content shall be determined at least once per year from a composite of:
This Paragraph shall not apply to sources that are only using fuel analysis in place of continuous monitoring to meet the requirements of 15A NCAC 02D .0600.
Authority
G.S.
143-215.3(a)(1);
143-215.65;
143-215.66;
143-215.107(a)(5);
Eff. June 1, 2008;
Readopted Eff. November 1,
2019.