North Carolina Administrative Code
Title 10A - HEALTH AND HUMAN SERVICES
Chapter 14 - Director, Division of Health Service Regulation
Subchapter J - JAILS, LOCAL CONFINEMENT FACILITIES
Section .1500 - CONSTRUCTION STANDARDS FOR EXISTING FACILITIES
Section 14J .1512 - LIGHTING AND VENTILATION

Universal Citation: 10A NC Admin Code 14J .1512

Current through Register Vol. 39, No. 6, September 16, 2024

(a) Lighting fixtures in sleeping rooms and dayrooms shall provide at least 30 footcandles of artificial light, and they shall have diffusers designed to illuminate a horizontal area from a ceiling or wall position.

(b) Artificial lighting in the inspection and control corridors shall be at least 20 footcandles.

(c) The artificial lighting at night in the sleeping rooms shall not exceed two footcandles.

(d) The lighting levels in the non-domiciliary portions of the jail shall be within ranges recommended by the I.E.S. (Illumination Engineering Society) for the particular activity.

(e) Lighting fixtures in the inmate-occupied areas shall be of the security type, and the wiring controls and fixtures shall be inaccessible to inmates (see Rule.1527 of this Section).

(f) Confinement areas shall be heated within a range of not less than 70 degrees nor more than 75 degrees. Confinement areas shall not have a heater or furnace that burns liquid or solid fuel.

(g) Wiring, temperature controls, and heat distribution equipment shall be inaccessible to inmates.

(h) Each facility shall provide adequate air circulation and ventilation of confinement areas in compliance with the North Carolina State Building Code.

(i) Confinement areas shall be cooled within a range of not less than 75 degrees nor more than 85 degrees.

Authority G.S. 153A-220; 153A-221;
Eff. June 1, 1990;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. January 5, 2016.

Disclaimer: These regulations may not be the most recent version. North Carolina may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.