(a) The walls and roof shall be made of:
(b) The interior walls in security areas shall be made of:
(c) Interior floors shall be made of concrete that is finished smooth, terrazzo, quarry tile, or other approved material.
(d) Interior ceilings shall be made of:
(e) Grating fronts and grating doors for single and multiple rooms shall be made of tool-resisting steel, as specified in Rule.1513(1)(a) of this Section, unless enclosed in a tool resisting perimeter.
(f) Safety vestibule grating and interior grating doors shall be made of tool-resisting steel, as specified in Rule.1513(1)(a) of this Section.
(g) Materials shall be non-combustible and shall have fire-resistive ratings if required by the North Carolina State Building Code.
(h) A local confinement facility shall not be located in or attached to buildings with less than fire-resistive construction, unless the confinement area is separated by an approved masonry firewall.