North Carolina Administrative Code
Title 10A - HEALTH AND HUMAN SERVICES
Chapter 14 - Director, Division of Health Service Regulation
Subchapter J - JAILS, LOCAL CONFINEMENT FACILITIES
Section .1200 - STANDARDS FOR NEW JAIL DESIGN AND CONSTRUCTION
Section 14J .1217 - MECHANICAL SYSTEMS

Universal Citation: 10A NC Admin Code 14J .1217

Current through Register Vol. 39, No. 6, September 16, 2024

(a) Each jail shall have heating, ventilation, and air conditioning systems that are capable of maintaining temperatures in confinement units at not less than 68 degrees Fahrenheit during the heating season and not more than 85 degrees Fahrenheit during the cooling season.

(b) The master controls for the system shall be located outside the confinement units and shall be accessible to officers during an emergency.

(c) The ducts for the systems shall be designed to prevent the escape of inmates and the passage of contraband, and they shall be designed to inhibit their use for attempted suicide.

(d) The ventilation system shall provide a minimum of ten cubic feet per minute of fresh or purified air for each inmate.

Authority G.S. 153A-221;
Eff. June 1, 1990;
Pursuant to G.S. 150B-21.3A, rule is necessary without substantive public interest Eff. January 5, 2016.

Disclaimer: These regulations may not be the most recent version. North Carolina may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.