North Carolina Administrative Code
Title 10A - HEALTH AND HUMAN SERVICES
Chapter 13 - NC MEDICAL CARE COMMISSION
Subchapter S - LICENSURE OF SUITABLE FACILITIES FOR THE PERFORMANCE OF SURGICAL ABORTIONS
Section .0200 - MINIMUM STANDARDS FOR CONSTRUCTION AND EQUIPMENT
Section 13S .0212 - ELEMENTS AND EQUIPMENT
Current through Register Vol. 39, No. 6, September 16, 2024
The physical plant shall provide equipment to carry out the functions of the clinic with the following minimum requirements:
(1) Mechanical requirements.
Area |
Temperature |
Relative Humidity |
Procedure |
70-76 degrees F. |
50-60% |
Recovery |
75-80 degrees F. |
30-60% |
Area |
Pressure Relationship |
Minimum Air Changes/Hour |
Procedure |
P |
6 |
Recovery Soiled work, Janitor's closet, Toilets, |
P |
6 |
Soiled holding |
N |
10 |
Clean work or Clean holding |
P |
4 |
(P = positive pressure N = negative pressure) |
(2) Plumbing And Other Piping Systems.
(3) Electrical Requirements.
(4) Buildings systems and medical equipment shall have preventative maintenance conducted as recommended by the equipment manufacturers' or installers' literature to assure operation in compliance with manufacturer's instructions.