North Carolina Administrative Code
Title 10A - HEALTH AND HUMAN SERVICES
Chapter 13 - NC MEDICAL CARE COMMISSION
Subchapter K - HOSPICE LICENSING RULES
Section .1200 - HOSPICE INPATIENT CARE
Section 13K .1211 - ADDITIONAL PLUMBING REQUIREMENTS/HOSPICE INPATIENT UNITS

Universal Citation: 10A NC Admin Code 13K .1211

Current through Register Vol. 39, No. 6, September 16, 2024

Hospice inpatient facilities or units shall provide a flow of hot water within safety ranges specified as follows:

(1) Patient Areas - 6 1/2 gallons per hour per bed and at a temperature of 100 to 116 degrees F;

(2) Dietary Services - 4 gallons per hour per bed and at a minimum temperature of 140 degrees F; and

(3) Laundry Area - 4 1/2 gallons per hour per bed and at a minimum temperature of 140 degrees F.

Authority G.S. 131E-202;
Eff. June 1, 1991;
Readopted Eff. October 1, 2021.

Disclaimer: These regulations may not be the most recent version. North Carolina may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.