North Carolina Administrative Code
Title 04 - COMMERCE
Chapter 11 - UTILITIES COMMISSION
Chapter 8
Article 4 - OPERATION
Section 11 R08-17 - STANDARD VOLTAGE
Current through Register Vol. 39, No. 6, September 16, 2024
(a) Each electric supplier shall adopt and file with the Commission standard average service voltages available from its distribution class facilities. The filing shall contain the nominal voltage, base voltage, lower limit, and upper limit. The voltage maintained at the point of delivery shall be reasonably constant and variations therein should not normally exceed the limits set forth in this rule.
NOMINAL SYSTEM VOLTAGE**** |
||
Two-wire |
Three-wire |
Four-wire |
Single-Phase Systems |
||
120* |
120/240* |
|
Three-Phase Systems |
||
208Y/120*** |
||
240/120 |
||
240 |
||
480Y/277 |
||
480 |
||
600** |
||
2400 |
||
4160 |
4160Y/2400 |
|
4800 |
||
6900 |
||
8320Y/4800 |
||
12000Y/6930 |
||
12470Y/7200 |
||
13200Y/7620 |
||
13800 |
13800Y/7970 |
|
20780Y/12000 |
||
23000 |
22860Y/13200 |
|
24940Y/14400 |
||
34500 |
34500Y/19920 |
*see (a)(2) below
**This classification covers the range of nominal voltages from 550 to 600 volts.
***A modification of this three-phase, four-wire system is available as a 120/208YV service for single-phase, three-wire, open-wye applications.
****Preferred system voltages are in bold-face type.
(b) In order to promote harmony between the service of electric suppliers and the utilization of voltage requirements of presently manufactured equipment, the following service voltage variations are permitted:
(c) An electric supplier may elect to deliver service at a nominal voltage that is not standard on its system. The variation in the nonstandard voltage shall not exceed the limits set forth above for the type of service being rendered.
(d) Upon approval of the Commission and proper notification to its customers a utility may cease to deliver a particular voltage.
(e) Variations in voltage in excess of those specified that are caused by the following shall not be construed a violation of this rule:
(f) Customers shall select, install, maintain and operate their electrical equipment so as to cause the least interference with the regulation of the electric supply system. Three phase motors in excess of 20 horsepower, single phase motors in excess of five horsepower and other apparatus with high starting or fluctuating currents must be installed in accordance with the supplier's filed tariffs and rules and regulations.
(g) Greater variations in voltage for service to installations that permit greater variations than those required above may be allowed upon specific authorization by the Commission.
NCUC Docket No. E-100, Sub 9, 4/25/72; NCUC Docket No. E-100, Sub 153, 11/27/2019.