Section 5203.3 - Building

Current through Register Vol. 46, No. 12, March 20, 2024

(a) Fire protection. All PSAPs shall comply with the New York State Uniform Fire Prevention and Building Code.

(b) Facility power.

(1) All PSAPs shall have an engine driven generator as an emergency source of power.

(2) All PSAPs shall have an uninterruptible power system (UPS) which shall maintain the power connection during the transition from commercial power to the standby generator power for critical systems and applications.

(3) The authority shall have a written procedure for the testing of standby power sources.

(4) The authority shall conduct documented inspections and testing of standby power sources at least monthly.

(c) Facility hours of operation. All PSAPs shall be fully operational 24 hours a day, 7 days a week, and 365 days a year (366 days during leap year).

Disclaimer: These regulations may not be the most recent version. New York may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.