New York Codes, Rules and Regulations
Title 16 - DEPARTMENT OF PUBLIC SERVICE
Chapter III - GAS UTILITIES
Subchapter C - Safety
Part 256 - Inspection And Maintenance Of Gas Holders
Section 256.17 - Exterior inspections-all holders

Current through Register Vol. 47, No. 12, March 26, 2025

An inspection of the exterior of all holders shall be made at least once a month to ascertain the condition of paint, shell, framing and holder top. Guide rollers on water seal holders shall be inspected for lubricating, alignment, and clearance at least once a month. During winter months a crew shall be available to insure prompt removal of any unsafe accumulation of snow and ice on the top and other parts of the holder.

Disclaimer: These regulations may not be the most recent version. New York may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.