New York Codes, Rules and Regulations
Title 14 - DEPARTMENT OF MENTAL HYGIENE
Chapter IV - Regulation And Quality Control
Subchapter C - Construction Of Facilities
Part 77 - Standards For Physical Facilities Of Hospitals For The Mentally Ill, Schools For The Retarded, And Alcohol Facilities
Section 77.4 - Safety and sanitation

Current through Register Vol. 46, No. 39, September 25, 2024

(a) There shall be adequate insect screens on all windows to be used for ventilation.

(b) Domestic hot water shall be generated and circulated at 110 degrees Fahrenheit without the use of thermostatically controlled mixing valves and be equipped with a high temperature alarm providing both auditory and visual signals having a set point of 120 degrees Fahrenheit located in an office or other location normally occupied by supervising personnel. Shower mixing valves shall be of the pressure balance type. A separate source of hot water or booster heater shall be provided for kitchens and other appliances and fixtures requiring temperatures in excess of 110 degrees Fahrenheit.

Disclaimer: These regulations may not be the most recent version. New York may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.