New York Codes, Rules and Regulations
Title 12 - DEPARTMENT OF LABOR
Chapter I - Industrial Board Of Appeals
Subchapter A - The Industrial Code
Part 4 - Low Pressure Boilers
Subpart 4-5 - Specific Requirements For Low Pressure Heating System Boilers
Section 4-5.9 - Feedwater connections
Universal Citation: 12 NY Comp Codes Rules and Regs § 4-5.9
Current through Register Vol. 47, No. 12, March 26, 2025
Feedwater connections shall be independent of any water gage connections. Feedwater connections for cast iron steam boilers, when introduced from a pressure line, shall be made to the condensate return line or the reservoir of the condensate return pump, not directly to the boiler. There shall be a check valve in the feedwater line at the boiler for all boilers.
Disclaimer: These regulations may not be the most recent version. New York may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google
Privacy Policy and
Terms of Service apply.