New York Codes, Rules and Regulations
Title 12 - DEPARTMENT OF LABOR
Chapter I - Industrial Board Of Appeals
Subchapter A - The Industrial Code
Part 4 - Low Pressure Boilers
Subpart 4-5 - Specific Requirements For Low Pressure Heating System Boilers
Section 4-5.12 - Combustion regulators
Universal Citation: 12 NY Comp Codes Rules and Regs § 4-5.12
Current through Register Vol. 47, No. 12, March 26, 2025
Each automatically fired hot water heating boiler shall be provided with a temperature actuated control which win control the rate of combustion to prevent the temperature of the water from rising above 250° F at or near the boiler outlet and each automatically fired steam boiler shall be provided with a pressure-actuated combustion control which shall operate to prevent the steam pressure from rising above 15 psi. Such control for a hot water boiler shall be incapable of being set so as to permit operation of the heat generating apparatus if the temperature of the water is higher than 250° F.
Disclaimer: These regulations may not be the most recent version. New York may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.