Subpart 4-4 - Inspection Of Boilers
Section 4-4.0 - Biennial inspections

Current through Register Vol. 47, No. 12, March 26, 2025

The inspection of boilers required by section 204 of the Labor Law shall be governed by the following schedule:

Exceptions:

Cast iron boilers shall be inspected externally at least biennially. Steel boilers shall be inspected at least biennially. When the type of construction of the boiler permits, such inspection shall be an internal inspection at least every three years for steam boilers and an internal inspection at least once every five years for hot water boilers, in addition to the biennial external inspection. A grace period beyond the period specified above may be permitted between inspections at the discretion of the commissioner.

Disclaimer: These regulations may not be the most recent version. New York may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.