Part 4 - Low Pressure Boilers
Subpart 4-14 - Special Requirements For Cast-iron Boilers
Section 4-14.3 - Boiler openings

Current through Register Vol. 47, No. 12, March 26, 2025

(a) Washout openings.

All cast-iron steam and hot water boilers shall be provided with suitable washout openings to permit the removal of any sediment that may accumulate therein. Washout openings may be used for return pipe connections and the washout plug placed in a tee so that the plug is directly opposite and as close as possible to the opening in the boiler.

(b) Threaded openings.

Pipe connections, if threaded, shall be tapped into material having a minimum thickness as specified in the following table:

MINIMUM THICKNESS OF MATERIAL FOR THREADED CONNECTIONS TO BOILERS

Size of pipe connection (inches) Minimum thickness material required (inches)
3/4 and under 5/16
1 to 21/2, inclusive 7/16
3 to 31/2, inclusive 5/8
4 to 5, inclusive 7/8
6 to 8, inclusive 1
9 to 12, inclusive 11/4

Disclaimer: These regulations may not be the most recent version. New York may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.