New York Codes, Rules and Regulations
Title 12 - DEPARTMENT OF LABOR
Chapter I - Industrial Board Of Appeals
Subchapter A - The Industrial Code
Part 36 - State Standard Building Code For Places Of Public Assembly
Subpart 36-3 - Special Requirements For Particular Occupancies
Section 36-3.2 - Theatres with stages-new
Universal Citation: 12 NY Comp Codes Rules and Regs ยง 36-3.2
Current through Register Vol. 46, No. 12, March 20, 2024
This section applies to theatres built on or after July 1, 1957.
(a) Exits.
(1) Main floor entrance and exits.
(i) The principal entrance shall constitute
one required means of exit but, regardless of its width, shall not be credited
as providing more than one half the required exit capacity of the main
floor.
(ii) The total required
capacity of exit doorways other than the principal entrance, shall be divided
between them approximately equally.
(iii) Where two means of exit are required,
one shall be located not more than 25 feet back of the front row of seats.
Where three means of exit are required, two shall be similarly located on
opposite sides. Where five or more means of exit are required, two shall be
similarly located on opposite sides and the remaining pair or pairs shall be
located on opposite sides so as to divide the distance between the exit nearest
the front row and the rear wall of the auditorium approximately
equally.
(iv) Where any main floor
exit doorway other than the doorway to the lobby does not open directly on a
lobby, court, street or public way, the passageway connecting with the street
shall be without openings other than those for entrance and exit.
(2) Exit stairways serving
balconies and galleries.
(i) Every tier above
the main floor shall have its required interior stairways located on opposite
sides of the tier. Entrance to such stairways shall be direct from a crossaisle
or from a corridor leading from a crossaisle.
(ii) Such stairways, when serving only the
balcony and terminating within the auditorium, lobby or foyer, may be
unenclosed. If not terminating within the auditorium, lobby or foyer, such
stairways shall be enclosed below the balcony level served.
(iii) Such stairways serving only the
balcony, may discharge to the main floor within the auditorium only if
subsequent exit facilities are of the aggregate width required, and the
discharge from such stairways is not at a greater angle than 90 degrees with
exit travel from the main floor within the auditorium.
(iv) Such stairways serving one or more
galleries, shall be enclosed except at the uppermost level served, and shall
lead directly to a ground floor lobby or foyer, a street, or an open area
leading to a street.
(v) When any
stairway from a higher tier or level discharges to a lobby, foyer, mezzanine or
other similar area, such area shall be separated from the auditorium by
self-closing doors.
(iv) There shall be at
least one exit serving each end of each crossaisle and each such exit shall be
not farther from the nearest end of the crossaisle than one fourth of the
length of the crossaisle. There shall also be an exit not more than 75 feet
from any seat, and every such exit provided along the course of the crossaisle
shall lead by means of tunnels or otherwise directly to a corridor or hallway
communicating with a stairway.
(3) Supplementary (emergency) exits from
balconies and galleries.
(i) In addition to
the stairways required by the previous paragraph each balcony or gallery having
a capacity, exceeding 750 persons shall be provided with at least two
supplementary exit stairways not less than 42 inches wide. When the capacity
exceeds 1,500, four such supplementary exit stairways shall be provided.
Supplementary interior exit stairways shall be provided with self- closing fire
doors, and shall lead directly to the street, or to a passageway independent of
other exits, or to an open court leading to a street. There shall be no
communication from any portion of the building to any supplementary exit
stairway enclosure except from the tier for which the stairway is exclusively
intended.
(ii) Such supplementary
exit stairways, when serving only the balcony and not exceeding 35 feet in
height, may be exterior stairways.
(4) Waiting space. Where persons are admitted
to the building at times when seats are not available to them and are allowed
to wait in a lobby, foyer or similar space until seats are available, the
capacity of such space shall be included when determining the aggregate exit
width needed.
(5) Stage exits. At
least two exits shall be provided at the stage level. These exits shall be at
opposite sides of the stage. Openings in the proscenium wall do not constitute
required stage exits.
(b) Seats and aisles.
(1) Seats.
(i) Seats, except those in boxes
accommodating not more than 16 persons, shall be at least 32 inches from back
to back and firmly secured to the floor.
(ii) There shall be at least five and
one-half inches between the back of a seat and the front of the seat
immediately behind it as measured between plumb lines with the seat in the down
or extended position. The minimum clearance between a seat back and the front
of the seat immediately behind it with the seat in the down, or extended
position, shall be 10 inches for any orchestra seat and seven inches for any
balcony or gallery seat.
(iii)
Seats designed to be turned to the up position shall be constructed and
maintained so as to remain up when turned up. "Push-back" type sliding seats
shall be constructed and maintained so as to retract automatically when
unoccupied.
(iv) The maximum number
of seats in any row with egress at both ends shall be 15, and the maximum
number of seats in any row with egress at one end only shall be
eight.
(v) Platforms formed to
receive seats in balconies or galleries shall be not less than 32 inches wide,
nor more than 21 inches high, except immediately above or below a crossaisle,
at which level steps may be recessed into the platform. No such platform shall
be nearer than eight feet to the ceiling. Such platform shall be continuous
across the aisle except when the rise between seat platforms is four inches or
less and except at the first platform above a crossaisle.
(2) Longitudinal aisles.
(i) Aisles with seats on one side only shall
be at least 30 inches wide. Aisles with seats on both sides shall be at least
36 inches wide.
(ii) Every
longitudinal aisle with exits at only one end shall have at least the minimum
prescribed width where the aisle begins and shall increase in width toward the
exits at the rate of one and one-half inches for each five feet of such aisle.
If exits or crossaisles are provided at both ends, such aisle may be of uniform
width throughout. This uniform width shall be not less than the average of the
minimum width prescribed and the increased width as calculated for the length
of aisle between crossaisles or exits.
(iii) Whenever an aisle borders on a means of
exit, the aisle shall have a width of at least four feet along the width of the
means of exit.
(iv) There shall be
no steps in any main floor aisle, except at the rear of the main floor in a
stadium type theatre.
(v) The
maximum slope in aisles on the main floor shall be one in six for the first,
second and third rows of seats from the rear; one in seven for the fourth,
fifth and sixth rows; one in eight for the seventh, eighth and ninth; one in
ten for the remaining rows.
(vi) In
balcony and gallery aisles, when the rise between the seat platforms is four
inches or less, the aisle shall be in the form of ramps with slopes not
exceeding one in eight.
(vii) In
balcony and gallery aisles, the steps if any shall be the full width of the
aisles with treads not less than 10 inches wide and risers not more than seven
and one-half inches high.
(3) Crossaisles on the main floor.
(i) Crossaisles at least 44 inches wide shall
connect either two longitudinal aisles or one such aisle and an exit door. They
need not extend through a side block of seats where neither a side aisle nor an
exit door is required or provided.
(ii) Where there are less than 27 rows and
less than four blocks of seats, a crossaisle shall extend to each sidewall exit
not served by a side aisle, but such crossaisle is not required to extend
through the central block of seats when a crossaisle is provided in front of
the central block of seats.
(iii)
Where there are 27 or more rows or four or more blocks of seats, crossaisles
shall be provided dividing the number of rows approximately equally and so that
no block of seats shall have more than 22 rows.
(4) Crossaisles in balconies and galleries.
(i) One or more crossaisles at least 44
inches wide shall be provided in every balcony or gallery having more than 10
rows of seats. Such crossaisles shall be so arranged that no more than seven
rows of seats intervene between any row and the nearer crossaisle above or
below.
(ii) Crossaisles shall be
separated from the seating spaces by railings at least 26 inches high except
where the adjoining seat platform is on the same level as the
crossaisle.
(iii) No step is
permitted in any crossaisle.
(5) Crossaisles in stadium-type theatres.
(i) In a stadium-type theatre, the rearmost
crossaisle of the main floor may serve not more than 10 rows of seats behind
it. The width of such crossaisle shall be 44 inches minimum and shall be
increased by eight inches for each 100 persons or major fraction thereof in the
first 10 rows of seats behind such crossaisle. Intermediate exits from such
crossaisle shall be provided so that the distance between such exits shall not
exceed 75 feet.
(ii) If a secondary
crossaisle is provided at the rear of the stadium section, such section shall
have not to exceed 20 rows of seats. One or more stairways complying with the
pertinent requirements for balcony stairs shall be provided at each end of the
secondary crossaisle. Each such stairway shall have an aggregate capacity
adequate for all persons seated behind the 10th row and need not be
enclosed.
(iii) The requirements
for railings along crossaisles in balconies apply to stadium
sections.
(6)
Obstructions and standing room in aisles.
(i)
All longitudinal aisles, and the paths of egress leading from them to the outer
doors, shall be kept unobstructed. No persons except employees shall be allowed
to remain in them during a public assemblage.
(ii) Part of the rear crossaisle on the main
floor only may be used for standing room provided a space at least seven feet
wide inside the rear auditorium wall is kept clear and unobstructed. No seats
shall be provided in the standing room space.
(iii) The aggregate width of the main floor
exits shall be increased to include the occupants of standing room
areas.
(c) Railings.
(1) Fascia railings. The fascias of
boxes and balconies shall have substantial walls or railings at least 26 inches
in height above the floor. The railings at the ends of aisles extending to the
fascia shall be at least 36 inches high if at the foot of steps, unless the
aisle is level for a distance of two feet from the lowest step to the fascia,
in which case the railing must be at least 32 inches high. Such walls and
railings in galleries shall be at least six inches higher than those required
above. No opening in any such railing shall exceed six inches in its lesser
dimension.
(2) Longitudinal aisle
railings. In aisles along the walls in balconies, galleries and stadium
sections, there shall be handrails affixed to the walls.
(d) Proscenium wall and curtain for stages as herein defined.
(1) Proscenium wall.
(i) The stage shall be separated from the
auditorium by a wall having a fire-resistance rating of at least two hours and
extending from the foundation to at least four feet above the stage roof, or
the auditorium roof if the latter be the higher.
(ii) Any windows in the structure above the
auditorium which face over the roof of the stage section must, when within 100
feet of the stage roof, be provided with stationary or automatic fire
windows.
(2) Openings in
proscenium wall.
(i) Openings between the
stage and auditorium, other than the stage opening, shall not be larger than 21
square feet each and shall be limited to two at the approximate stage level,
and two below the stage level. Openings below the stage level, including doors
from under the stage to pipetunnels, plenum chambers and other spaces to which
access must be provided, shall be provided with fire doors having a rating of
at least one hour, except that no door shall lead directly through the
proscenium wall to a plenum chamber.
(ii) In openings whose greatest dimension
does not exceed 18 inches three-eighths inch automatic incombustible damper
plates may be used in lieu of fire doors.
(3) Fire curtain--operation.
(i) The proscenium opening shall be provided
with a fire curtain so designed and constructed as to close the opening
completely and prevent the passage of hot gases, flame and smoke.
(ii) Such curtain shall be so arranged and
maintained that in case of fire it will be released automatically by an
approved heat actuated device and will then descend at a rate of at least one
foot per second and settle on the stage floor without shock. It shall also be
equipped with effective devices on each side of the stage which will permit
prompt release by manual means.
(4) Fire curtain--construction.
(i) The fire curtain shall consist of a rigid
incombustible framework covered on both sides with incombustible material and
having all its parts including the means of support made of incombustible
material.
(ii) It shall extend past
the sides and top of the proscenium opening by at least 12 inches on the stage
side when closed.
(iii) The bottom
shall have a yielding roll of asbestos or other fire-resistive material
attached thereto to form a smoke seal when in contact with the surface of the
floor.
(5) Smoke seals
and guides. The curtain shall be guided throughout its travel by a rigid steel
track upon which the curtain guides shall travel. The track shall be built into
a smoke seal made of rolled steel shapes and plates. The mounting and details
of guides, track and smoke seal shall be such as to insure ready and positive
closure of the curtains when subjected to a lateral pressure of five pounds per
square foot. The smoke seal shall be at least 12 inches deep and six inches
wide, be set back from the stage opening at least six inches and extend from
the stage floor to a point at least three feet above the top of the raised
curtain.
(6) Fire-resistive
requirements. The materials and design of curtains, curtain guides and smoke
seals shall be designed and constructed to prevent the passage of flame during
a fire test for a period of one-half hour in accordance with the standard
time-temperature curve, while subject to an air pressure of not less than five
pounds per square foot normal to its surface during such period.
(e) Stage section.
(1) Construction. From the inside line of the
fire curtain to the back wall, the stage floor for a width of six feet more
than the curtain opening may be entirely of wood construction. All the
remainder of the stage floor behind the proscenium wall and extending in front
of it to the edge of the apron shall have a fire-resistance rating of at least
two hours, except that a wood floor finish with no air space between it and the
fire-resistive construction underneath may be used from the inside line of the
curtain to the edge of the apron.
(2) Openings in exterior walls. All door or
window openings in exterior walls of the stage section shall be provided with
self-closing fire doors having a rating of at least one hour or with fire
windows.
(3) Galleries and lofts.
Fly and tie galleries and the gridiron shall be constructed of incombustible
materials and be easily accessible by stairs or ladders of incombustible
materials. A means of exit shall also be provided from the gridiron to a roof
or other adjacent structure having available and unobstructed access to
grade.
(4) Scenery, workshops and
storage rooms. All stage scenery, curtains and decorations of combustible
material and all woodwork on or about the stage shall be treated so as not to
ignite readily nor support combustion. Scene docks, workshops and storage rooms
shall be separated by construction having a fire-resistance rating of at least
two hours from the other portions of the theatre. The only openings connecting
such spaces with the stage shall be doorways provided with self-closing fire
doors having a fire-resistance rating of at least one and one-half
hours.
(5) Dressing rooms and
dressing room exits.
(i) Dressing rooms shall
be separated from the other portions of the theatre by construction having a
fire-resistance rating of at least one hour. Door openings in same shall be
provided with self-closing fire doors having a rating of at least one
hour.
(ii) Dressing rooms, when
used as such, shall be ventilated by fire windows or metal frame and wired
glass skylights opening directly to the open air, or shall be mechanically
ventilated with at least six air changes per hour.
(iii) Dressing rooms located at or above the
stage level shall have a means of exit independent of the stage and leading to
a street or court.
(iv) When
dressing rooms are located below the stage level at least two exits therefrom
shall be provided, one of which shall lead directly to a street or
court.
(v) The maximum distance of
travel from any dressing room to the nearest grade exit, exit stairway or
passageway, shall be 75 feet.
(6) Sanitary facilities. Appropriate and
sufficient washing and toilet facilities for both men and women shall be
located within the stage section of the theatre for the use of performers and
employees.
(7) Ventilators in stage
section.
(i) One or more ventilators
constructed of metal or other incombustible material shall be placed near the
center and above the highest part of the stage roof. The aggregate ventilating
area shall not be less than 10 per cent of the floor area within the stage
walls. Sills of doors or shutters shall be located at least three feet above
the roof. Doors or shutters shall be constructed and maintained to open outward
by force of gravity, when released, and shall be weighted sufficiently to
overcome the effects of rust, dirt, frost, snow, expansion by heat or warping
of the framework. Hinges shall be of wrought or malleable iron with bronze pins
at least three-eighths inch in diameter. Glass, used in ventilators, must be
protected against falling on the stage. If wire screens are used, they must be
at least one-eighth inch galvanized iron with a one-inch mesh and so placed
that, if clogged, neither the required vent area will be reduced nor the
operating mechanism obstructed.
(ii) The shutters or doors shall be arranged
to open instantly by the use of approved heat-actuated devices which shall be
located in the ventilator above the roof line. Manual operation shall be
provided by a multiple controlling hemp rope accessible from the stage level
and a sharp knife shall be chained where it may be used for cutting this rope.
While the theatre stage is in use, each ventilator shutter shall be maintained
in operating condition.
(8) Sprinklers.
(i) An automatic wet pipe sprinkler system
conforming to the provisions of Industrial Code Part 20 shall be provided for
the stage section.
(ii) Sprinkler
heads shall be placed under the roof of the stage and under all superstructures
above the stage so as to protect every square foot of the stage floor. An
additional line of sprinkler heads shall be placed not over six feet apart and
not more than two feet from the stage side of the fire curtain.
(iii) Sprinkler heads shall be placed under
the stage, and in dressing rooms, scenes docks, workshops, storage rooms and
all other enclosed spaces in the stage section.
(iv) Sprinkler heads are not permitted in
such positions as to affect the heat-actuated devices controlling the stage
ventilators. Switchboards, generators and other important electrical equipment
shall be protected against water from the sprinkler system. Wherever there is a
liability of damage from moving objects, scenery or other stage settings,
sprinkler heads shall be provided with metal shields.
(9) Standpipes.
(i) A standpipe system having adequate water
supply and installed in accordance with the standards of the National Board of
Fire Underwriters shall be located in the stage section.
(ii) Every portion of the stage, every
dressing room section, basement, workshop, property room and every other room
or space which is appurtenant to the stage and in which combustible material is
stored or handled, shall be accessible to a standpipe hoseline so located that
it will not require more than 100 feet of hose plus 20 feet to cover any such
room or space.
(iii) The standpipes
shall have internal diameters sufficient to deliver 50 gallons of water per
minute under a pressure of 30 pounds per square inch at the highest outlet.
Hose having a diameter of one and one-half inches shall be used.
(10) Extinguishers and fire tools.
(i) There shall be provided at each side of
the stage and the space under the stage two approved two and one-half gallon
soda and acid or loaded stream fire extinguishers. On the stage one six-pound
fire axe and one 10-foot fire hook shall be provided on each side. One approved
two and one-half gallon soda and acid or loaded stream fire extinguisher shall
be placed on each fly gallery, in each tier of dressing rooms, and in every
scenery loft, workroom, storeroom or furnace room having an area of more than
1,000 square feet.
(ii)
Extinguishers shall be charged annually, as well as immediately after use, and
shall be tagged to indicate when this was done and by whom. Fire extinguishers
and fire tools shall be securely mounted on walls, in plain sight and readily
accessible.
(f) Smoking. Smoking shall at no time be permitted in the stage section except as incidental to the action of a performance. It shall be permitted elsewhere only in the parts of the theatre designated by the enforcing authority.
Disclaimer: These regulations may not be the most recent version. New York may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google
Privacy Policy and
Terms of Service apply.