New York Codes, Rules and Regulations
Title 12 - DEPARTMENT OF LABOR
Chapter I - Industrial Board Of Appeals
Subchapter A - The Industrial Code
Part 23 - Protection In Construction, Demolition And Excavation Operations
Subpart 23-2 - Construction Operations
Section 23-2.6 - Catch platforms required
Universal Citation: 12 NY Comp Codes Rules and Regs § 23-2.6
Current through Register Vol. 47, No. 12, March 26, 2025
(a) During the construction of exterior masonry walls of any building or other structure, except chimneys, from a floor or scaffold inside the building or other structure and such floor or scaffold is more than 35 feet above the adjoining ground or equivalent surface, there shall be provided along the exterior face of such wall a catch platform, installed in compliance with this Part (rule) with the following exceptions:
(1) In lieu of the required barricade or
fence on all open sides of the catch platform, such sides shall be provided
with planks whose minimum cross-sectional dimensions shall be two inches by
nine inches or material of equivalent strength having one dimension at least
nine inches. Such planks or material of equivalent strength shall be so placed
that the greater dimensions are vertical.
(2) A two-inch space may be left between the
inner edge of the catch platform and the face of the wall of the building or
other structure.
(b) Such catch platform shall be located not more than 20 feet below the floor or scaffold platform from which the work is being performed.
Disclaimer: These regulations may not be the most recent version. New York may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.