Section 14-9.18 - Gage cocks

Current through Register 47, No. 25, June 25, 2025

(a) Each boiler shall have three or more gage cocks located within the visible length of the water glass, except when the boiler has two water glasses located on the same horizontal lines.

(b) Boilers not over 36 inches in diameter in which the heating surface does not exceed 100 square feet need have but two gage cocks.

(c) The gage cock connections shall not be less than one-half inch pipe size.

Disclaimer: These regulations may not be the most recent version. New York may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.