Section 8.321.11.66 - ELECTRICAL STANDARDS
Universal Citation: 8 NM Admin Code 8.321.11.66
Current through Register Vol. 35, No. 18, September 24, 2024
A. All electrical installation and equipment must comply with all current state and local codes.
B. Circuit breakers or fused switches that provide electrical disconnection and over current protection shall be:
(1) enclosed or guarded
to provide a dead front assembly;
(2) readily accessible for use and
maintenance;
(3) set apart from
traffic lanes;
(4) located in a
dry, ventilated space, free of corrosive fumes or gases;
(5) able to operate properly in all
temperature conditions;
(6) panel
boards servicing lighting and appliance circuits shall be on the same floor and
in the same facility area as the circuits they serve; and
(7) each panel board will be marked showing
the services.
C. The use of jumpers or devices to bypass circuit breakers or fused switches is prohibited.
D. Light switches and electrical devices in the residential unit shall be secured with tamper resistant screws.
Disclaimer: These regulations may not be the most recent version. New Mexico may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.