Section 7.13.2.42 - DOORS

Universal Citation: 7 NM Admin Code 7.13.2.42

Current through Register Vol. 35, No. 6, March 26, 2024

A. Required exit doors must be openable from the inside at all times the facility is in operation.

B. All required exit doors must have a minimum width of thirty six (36") inches. Exception: Adult day care homes.

C. Required exit doors in facilities having a capacity of fifty (50) or more must open outward.

D. Locks and latches on closets and bathrooms must be of the type that the lock can be released from the outside.

Disclaimer: These regulations may not be the most recent version. New Mexico may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.