Section 20.7.3.504 - DESIGN; BUILDING SEWER
Current through Register Vol. 35, No. 18, September 24, 2024
A. The building sewer connects the building drain to the septic tank or liquid waste treatment unit. Horizontal building sewer piping shall be run in practical alignment and a uniform slope of not less than 1/4 of an inch per foot or 2% toward the point of disposal provided that where it is impractical due to the structural features or arrangement of any building or structure to obtain a slope of 1/4 of an inch or 2%, any such pipe or piping four inches in diameter or larger may have a slope of not less than 1/8 of an inch per foot or 1%, when first approved by the department.
B. Each horizontal sewer pipe shall be provided with a cleanout at its upper terminal and each run of pipe that is more than 100 feet in length shall be provided with a cleanout for each 100 feet or fraction thereof. Cleanouts shall be installed pursuant to the New Mexico plumbing code.
C. Sewer piping shall be approved material having a smooth uniform bore. Vitrified clay pipe or fittings shall not be used above ground or where pressurized by a pump or ejector. Vitrified clay pipe or fittings shall be a minimum of 12 inches below ground.