New Mexico Administrative Code
Title 20 - ENVIRONMENTAL PROTECTION
Chapter 5 - PETROLEUM STORAGE TANKS
Part 114 - AIRPORT HYDRANT FUEL DISTRIBUTION SYSTEMS, UST SYSTEMS WITH FIELD- CONSTRUCTED TANKS, AND HYBRID STORAGE TANK SYSTEMS
Section 20.5.114.1404 - OPERATION AND MAINTENANCE OF AIRPORT HYDRANT SYSTEMS, USTS WITH FIELD-CONSTRUCTED TANKS, AND HYBRID STORAGE TANK SYSTEMS

Universal Citation: 20 NM Admin Code 20.5.114.1404

Current through Register Vol. 35, No. 6, March 26, 2024

Owners and operators shall comply with the requirements in 20.5.107 NMAC and 20.5.110 NMAC no later than three years after the effective date of these regulations for existing systems and upon installation for new systems. In addition to the monthly inspection requirements in 20.5.107.707 NMAC, owners and operators must inspect the following additional areas for airport hydrant systems at least once every 30 days if confined space entry per the occupational safety and health administration (see 29 CFR part 1910) is not required or at least annually if confined space entry is required and keep documentation of the inspection per 20.5.107.714 NMAC

A. Hydrant pits--visually check for any damage; remove any liquid or debris; and check for any leaks, and

B. Hydrant piping vaults--check for any hydrant piping leaks.

Disclaimer: These regulations may not be the most recent version. New Mexico may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.