New Mexico Administrative Code
Title 20 - ENVIRONMENTAL PROTECTION
Chapter 5 - PETROLEUM STORAGE TANKS
Part 114 - AIRPORT HYDRANT FUEL DISTRIBUTION SYSTEMS, UST SYSTEMS WITH FIELD- CONSTRUCTED TANKS, AND HYBRID STORAGE TANK SYSTEMS
Section 20.5.114.1402 - ADDITIONAL REQUIREMENTS FOR HYBRID STORAGE TANK SYSTEMS

Universal Citation: 20 NM Admin Code 20.5.114.1402

Current through Register Vol. 35, No. 6, March 26, 2024

A. Owners and operators of hybrid storage tank systems shall, no later than one year after the effective date of these regulations, install redundant automatic shut off and manual override equipment on the piping transferring a regulated substance from the AST to the UST in order to prevent overfills.

B. Owners and operators of existing hybrid storage tank systems who replace the underground piping on or after the effective date of these regulations shall install double walled piping including but not limited to the underground remote fill piping. Containment sumps shall be installed at both ends of the underground piping. The new underground piping shall be interstitially monitored monthly in accordance with 20.5.108.811 NMAC or 20.5.8.813 NMAC as applicable upon installation.

Disclaimer: These regulations may not be the most recent version. New Mexico may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.