New Mexico Administrative Code
Title 20 - ENVIRONMENTAL PROTECTION
Chapter 5 - PETROLEUM STORAGE TANKS
Part 110 - GENERAL OPERATING REQUIREMENTS FOR ABOVE GROUND STORAGE TANK SYSTEMS
Section 20.5.110.1008 - PERIODIC OPERATION AND MAINTENANCE WALK-THROUGH INSPECTIONS

Universal Citation: 20 NM Admin Code 20.5.110.1008

Current through Register Vol. 35, No. 6, March 26, 2024

A. Owners and operators shall conduct walk-through inspections that, at a minimum, check equipment as specified below:

(1) For spill and overfill prevention equipment, every 30 days (exception: spill prevention equipment at AST systems receiving deliveries at intervals greater than every 30 days may be checked prior to each delivery):
(a) visually check all spill and overfill prevention equipment for damage;

(b) remove liquid or debris;

(c) check for and remove obstructions in the fill pipe;

(d) check the fill cap to make sure it is securely on the fill pipe; and

(e) for double walled spill prevention equipment with interstitial monitoring, check for liquid or a leak in the interstitial area; and

(f) check overfill prevention equipment for proper operation and determine whether maintenance is required.

(2) For release detection equipment, every 30 days:
(a) check to make sure the release detection equipment is operating with no alarms or other unusual operating conditions present; and

(b) ensure records of release detection testing are reviewed and current.

(3) For containment sumps, every 30 days:
(a) visually check the containment sump for damage, liquid in the containment area, and releases to the environment;

(b) remove liquid and debris in containment sumps; and

(c) for double walled sumps with interstitial monitoring, check for liquid or a leak in the interstitial area.

(4) Annually: check hand held release detection equipment, such as, but not limited to, tank gauge sticks for operability and serviceability;

B. Owners and operators shall conduct these walk-through inspections in accordance with one of the following:

(1) the current edition of a national code of practice or standard developed by a nationally recognized association or independent testing laboratory that checks equipment included in Subsection A of 20.5.110.1008 NMAC; or

(2) a checklist developed by the department.

C. If monthly visual checks of containment sumps are not being conducted or records of the checks cannot be produced, a test in accordance with Subsection D of 20.5.10.1007 NMAC shall be conducted within 30 days of failing to meet the requirement for monthly monitoring of the equipment.

D. Owners and operators must maintain records of operation and maintenance walkthrough inspections in accordance with 20.5.110.1015 NMAC. Records must include a list of each area checked, whether each area checked was acceptable or needed action taken, a description of actions taken to correct an issue, and delivery records if spill prevention equipment is checked less frequently than every 30 days due to infrequent deliveries.

Disclaimer: These regulations may not be the most recent version. New Mexico may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.