New Mexico Administrative Code
Title 20 - ENVIRONMENTAL PROTECTION
Chapter 5 - PETROLEUM STORAGE TANKS
Part 109 - NEW AND UPGRADED ABOVE GROUND STORAGE TANK SYSTEMS: DESIGN, CONSTRUCTION, AND INSTALLATION
Section 20.5.109.917 - SECONDARY CONTAINMENT FOR AST DISPENSERS

Universal Citation: 20 NM Admin Code 20.5.109.917

Current through Register Vol. 35, No. 6, March 26, 2024

Owners and operators shall install a containment sump underneath each dispenser system associated with an AST, unless the dispenser is located within secondary containment.

A. Owners and operators shall hydrostatically test the sump upon installation, in accordance with manufacturer's recommendations.

B. The following may be used to comply with this containment sump requirement: dispenser liners, under-dispenser containment, dispenser pans, and dispenser sump liners.

C. Under-dispenser containment sumps shall be either listed in accordance with an industry standard or code of practice developed by a nationally recognized association or independent testing laboratory for use with flammable and combustible liquids or approved prior to installation by the department in accordance with the alternate methods requirements in 20.5.109.920 NMAC.

Disclaimer: These regulations may not be the most recent version. New Mexico may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.