A. If owners and operators construct or operate piping of fiberglass-reinforced plastic or flexible piping, the piping shall:

(1) be completely underground;

(2) be within secondary containment that includes a release detection system that meets the requirements of 20.5.108 NMAC;

(3) have a suitable cover approved by the piping manufacturer; or

(4) have equivalent protection approved by the piping manufacturer and approved by the department prior to installation.

B. Owners and operators shall ensure that the piping meets the requirements of the current edition of an industry standard or code of practice developed by a nationally recognized association or independent testing laboratory approved in advance by the department, and that the piping is approved by the manufacturer for the application for which it is to be used. Owners and operators shall use one or more of the following to comply with the requirements of this section:

(1) Underwriters Laboratories Standard 971, "Standard for Nonmetallic Underground Piping for Flammable Liquids"; or

(2) Underwriters Laboratories of Canada Standard S660, "Standard for Nonmetallic Underground Piping for Flammable and Combustible Liquids".

Disclaimer: These regulations may not be the most recent version. New Mexico may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.