New Mexico Administrative Code
Title 19 - NATURAL RESOURCES AND WILDLIFE
Chapter 15 - OIL AND GAS
Part 40 - NEW MEXICO LIQUEFIED PETROLEUM GAS STANDARD
Section 19.15.40.20 - CONTAINERS AND INSTALLATIONS
Current through Register Vol. 35, No. 24, December 23, 2024
A. Safe installation. No LP gas container shall be filled or LP gas system used that does not meet the requirements of NFPA 58, NFPA 54 or this document.
B. Filling of Containers. Transfer of LP Gas to or from any LP Gas container shall be only by the owner or upon the owners authorization.
C. Chart 1 (all services except cargo tanks). ASME 1949 and earlier and U-68 and U-69 Codes are approved for all LP gas service, except cargo tank, regardless of installation date, with the following working pressures and relief valve settings, when using propane grade 5 or higher.
Working Pressure |
100 |
125 |
150 |
175 |
200 |
225 |
250 |
251+ |
Approved |
No |
No |
No |
No |
Yes |
Yes |
Yes |
Yes |
Relief Valve Setting (%) |
100 to 125 |
137 to 156 |
165 to 187 |
192 to 218 |
220 to 250 |
247 to 281 |
275 to 317 |
110% to 125% |
D. Chart 2 (bulk service). API-ASME Code, ASME U-201, 1950 and 1952 or later ASME Codes are approved for bulk plant use*, and for all other container use if manufactured after June 30, 1959, in accordance with ASME Code, at the time of manufacture with the following working pressures and relief settings, when using propane of grade 5 or higher. *Cargo containers shall have a minimum working pressure of 250 PSI.
Working Pressure |
100 |
125 |
150 |
175 |
200 |
225 |
250 |
251+ |
Approved |
No |
No |
No |
No |
No |
No |
Yes |
Yes |
Relief Valve Setting (%) |
100 to 125 |
220 to 250 |
88% to 100% |
E. Chart 3 (domestic tank service). API-ASME Code, ASME U-200, U-201, 1950 and 1952 or later ASME Codes, if installed in New Mexico before June 30, 1959, may be moved from one place to another within the state, but not brought into the state, are approved for domestic tank service with the following working pressures and relief settings, when using propane of grade 5 or higher.
Working Pressure |
100 |
125 |
150 |
175 |
200 |
225 |
250 |
251+ |
Approved |
No |
No |
No |
No |
No |
No |
Yes |
Yes |
Relief Valve Setting (%) |
110 to 125 |
132 to 150 |
154 to 175 |
176 to 200 |
198 to 225 |
220 to 250 |
88% to 100% |
F. Container protection. Where physical damage to LP gas containers, or systems of which they are a part, from vehicles is a possibility, precautions shall be taken against such damage.
G. Container markings. All LP gas tanks owned by LP gas dealers must be marked with the name and phone number of the LP gas dealer. This regulation does not apply to customer owned tanks.
H. Container screening. Screens for all LP gas above ground containers shall be installed in the following manner.