Section 19.15.40.18 - PIPING AND APPLIANCES WITHIN BUILDINGS

Universal Citation: 19 NM Admin Code 19.15.40.18

Current through Register Vol. 35, No. 24, December 23, 2024

A. All piping and LPappliances must meet current NFPA 54 and NFPA 58 requirements, with the exception that anodeless flexible risers may be used at the tank and at the house.

B. LP Gas piping or appliances in attics, under floor area, or below grade must be adequately ventilated. Ventilation openings shall be a minimum of 36 square inches.

C. Gas utilization equipment located in confined spaces shall be provided with two permanent openings, one commencing within 12 inches of the top, and one commencing within 12 inches of the bottom of the enclosure.

Disclaimer: These regulations may not be the most recent version. New Mexico may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.