New Mexico Administrative Code
Title 14 - HOUSING AND CONSTRUCTION
Chapter 9 - MECHANICAL CODES
Part 4 - BOILERS
Section 14.9.4.33 - EMERGENCY EXITS

Universal Citation: 14 NM Admin Code 14.9.4.33

Current through Register Vol. 35, No. 18, September 24, 2024

A. Boilers shall be so located and so equipped that egress is provided to permit safe and quick escape of any person in case of emergency; this shall include suitable and sufficient permanent stairs or ladders from boiler tops and elevated appurtenances and appliances which are located more than eight (8) feet above the floor, walkway or platform nearest thereto, except water columns and gauge glasses.

B. Water columns or gauge glasses which are located over ten (10) feet above the floor or a walkway shall be provided with a suitable platform beneath them, which need not be provided with a permanent means of egress.

Disclaimer: These regulations may not be the most recent version. New Mexico may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.