New Mexico Administrative Code
Title 14 - HOUSING AND CONSTRUCTION
Chapter 9 - MECHANICAL CODES
Part 4 - BOILERS
Section 14.9.4.27 - PREPARATION OF BOILERS

Universal Citation: 14 NM Admin Code 14.9.4.27

Current through Register Vol. 35, No. 18, September 24, 2024

A. After timely notification, it shall be the responsibility of the owner or user to prepare the boiler for inspection. To prepare a boiler for internal inspection, all manhole plates, handhold plates, washout plugs and water column connection plugs shall be removed and the waterside thoroughly washed. Furnace, combustion chambers and tubes must be thoroughly cleaned and grates of internally-fired boilers, brickwork or other insulation material shall be removed to determine the condition of the shell furnace, mud drum, heads or any covered pressure part. The chamber of the low water fuel cutoffs shall be opened and the float or probes removed.

B. Any leakage of steam or hot water into the boiler shall be prevented by disconnecting the pipe or valve at the most convenient point or any appropriate means approved by the special inspector.

Disclaimer: These regulations may not be the most recent version. New Mexico may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.