New Mexico Administrative Code
Title 14 - HOUSING AND CONSTRUCTION
Chapter 7 - BUILDING CODES GENERAL
Part 4 - 2021 NEW MEXICO EARTHEN BUILDING MATERIALS CODE
Section 14.7.4.22 - ELECTRICAL

Universal Citation: 14 NM Admin Code 14.7.4.22

Current through Register Vol. 35, No. 18, September 24, 2024

A. Electrical system installation. Electrical wiring shall pass through a channel or conduit. Approved rigid or flexible electrical conduit shall withstand ramming pressures without damage or collapse. Electrical wiring within a channel shall be covered a minimum of one and one-fourth inches. Prior to ramming, a minimum five inch earth cover shall be provided over any horizontal pipe.

B. UF cable installation. UF cable may not be rammed within the rammed earth wall. Exception: UF cable installed within an approved conduit or channel. In a channel installation, UF cable must be covered a minimum of one and one-fourth inches with plaster, adobe or similar finish.

C. Electrical box installation. Plastic electrical boxes shall not be rammed within the rammed earth wall. Exception: plastic electrical boxes installed in a channel installation.

Disclaimer: These regulations may not be the most recent version. New Mexico may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.