Section 14.7.4.18 - LINTELS OVER OPENINGS
Current through Register Vol. 35, No. 18, September 24, 2024
A. General. All openings require a lintel or semi-circular arch over the opening. All lintels, whether of wood or concrete shall bear a minimum of two inches into the length of the wall. Exception: nichos and other shaped voids as defined in 14.7.4.15 NMAC.
B. Bearing limitations. Lintels shall bear a minimum of two inches beyond coved, splayed or rounded bearing portions of openings that are less than the full width of the wall. (Refer to Figure 15 of the earthen building figures supplement).
C. Lintels over openings in stabilized rammed earth walls. Openings less than 2four inches in width shall not require a lintel or semi-circular arched opening. Openings greater than 2four inches in width require lintels as defined in Table 4.
Table 4 Concrete Lintels Over Openings in Rammed Earth Walls (1) |
|||||
Wall width |
Lintel span |
Lintel depth |
Reinforcement (2) |
Reinforcement Concrete Cover (3) |
Uniform Load |
18" |
24" |
6" |
3- #4 @ 4"o.c. |
3" minimum concrete cover on all sides |
1000 PLF |
36" |
6" |
3- #4 @ 4"o.c. |
|||
48" |
6" |
3- #4 @ 4"o.c. |
|||
60" |
6" |
3- #4 @ 4"o.c. |
|||
72" |
8" |
3- #5 @ 4"o.c. |
|||
84" |
8" |
3- #5 @ 4"o.c. |
|||
96" |
8" |
3- #5 @ 4"o.c. |
|||
20" |
24" |
6" |
3- #4 @ 4"o.c. |
4" minimum concrete cover on all sides |
1350 PLF |
36" |
6" |
3- #4 @ 4"o.c. |
|||
48" |
6" |
3- #4 @ 4"o.c. |
|||
60" |
6" |
3- #4 @ 4"o.c. |
|||
72" |
8" |
3- #5 @ 4"o.c. |
|||
84" |
8" |
3- #5 @ 4"o.c. |
|||
96" |
10" |
3- #5 @ 4"o.c. |
|||
22" |
24" |
6" |
3- #4 @ 5"o.c. |
3 1/2" minimum concrete cover on all sides |
1700 PLF |
36" |
6" |
3- #4 @ 5"o.c. |
|||
48" |
6" |
3- #4 @ 5"o.c. |
|||
60" |
6" |
3- #4 @ 5"o.c. |
|||
72" |
8" |
3- #5 @ 5"o.c. |
|||
84" |
10" |
3- #5 @ 5"o.c. |
|||
96" |
10" |
3- #5 @ 5"o.c. |
|||
24" |
24" |
6" |
3- #4 @ 6"o.c. |
3" minimum concrete cover on all sides |
2000 PLF |
36" |
6" |
3- #4 @ 6"o.c. |
|||
48" |
6" |
3- #4 @ 6"o.c. |
|||
60" |
6" |
3- #4 @ 6"o.c. |
|||
72" |
8" |
3- #5 @ 6"o.c. |
|||
84" |
10" |
3- #5 @ 6"o.c. |
|||
96" |
12" |
3- #5 @ 6"o.c. |
|||
1. 3000 psi minimum concrete at approximately 28 days. 2. Grade 40 steel reinforcement minimum. 3. Steel reinforcement at mid-depth of lintel. |