New Jersey Administrative Code
Title 8 - HEALTH
Chapter 43G - HOSPITAL LICENSING STANDARDS
Subchapter 24 - PLANT MAINTENANCE AND FIRE AND EMERGENCY PREPAREDNESS
Section 8:43G-24.4 - Plant maintenance services

Universal Citation: NJ Admin Code 8:43G-24.4

Current through Register Vol. 56, No. 6, March 18, 2024

(a) Records of preventive maintenance inspections and repairs of electrical and mechanical systems shall be maintained for at least one year.

(b) The building maintenance service shall be provided with copies of the written instructions for operating and maintaining departmental and unit equipment. These instructions shall be systematically retained in the departments or units in which the equipment is used.

(c) All life-sustaining equipment shall be plugged into outlets connected to the emergency power supply.

(d) Routine maintenance inspections of elevators shall be conducted in accordance with local ordinances.

(e) The standby emergency generator shall be checked weekly, tested under load monthly, and serviced in accordance with accepted engineering practices.

(f) Floors, ceilings, and walls shall be free of cracks and holes, discoloration, residue build-up, water stains, and other signs of disrepair.

Disclaimer: These regulations may not be the most recent version. New Jersey may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.