New Jersey Administrative Code
Title 7 - ENVIRONMENTAL PROTECTION
Chapter 9D - WELL CONSTRUCTION AND MAINTENANCE; SEALING OF ABANDONED WELLS
Subchapter 2 - REQUIREMENTS AND PROCEDURES FOR THE CONSTRUCTION, INSTALLATION, OPERATION AND MAINTENANCE OF WELLS
Section 7:9D-2.7 - Minimum distance requirements
Current through Register Vol. 56, No. 18, September 16, 2024
(a) All new Category 1 and Category 2 wells shall be located at least five feet horizontally from a building or any portion thereof, except for a pump house.
(b) All Category 1 wells and components shall be located no less than the minimum distances prescribed as follows (all distances are in feet):
Component | Building sewer | Septic tank | Distribution box | Disposal field | Seepage pit* | Dry well | Cesspool | Fuel Storage tank |
Well | 25 | 50 | 50 | 100 | 150 | 50 | 150 | 25 |
Suction line | 25 | 50 | 50 | 100 | 100 | 50 | 150 | - |
Water service line | 5 | 10 | 10 | 10 | 10 | - | 25 | - |
*Note: The Department may reduce the 150-foot minimum distance between a new well and seepage pit system as a condition of well permit approval where the well casing is sealed into a confining layer separating the aquifer from the stratum of soil used for sewage disposal or where the well is constructed with additional casing.
(c) All Category 2 wells shall be located no less than 25 feet from a fuel storage tank.
(d) Additional minimum distance requirements for any well may be required by the Department as necessary to protect groundwater supplies in areas of known contamination.
(e) The Department may modify the minimum distances in this section for individual well installations where it has determined that additional controls are necessary to protect water supplies.