New Jersey Administrative Code
Title 7 - ENVIRONMENTAL PROTECTION
Chapter 14B - UNDERGROUND STORAGE TANKS
Subchapter 4 - UNDERGROUND STORAGE TANK SYSTEMS: DESIGN, CONSTRUCTION AND INSTALLATION
Section 7:14B-4.1A - Performance standards for dispenser systems
Universal Citation: NJ Admin Code 7:14B-4.1A
Current through Register Vol. 56, No. 18, September 16, 2024
(a) Each UST system shall be equipped with under-dispenser containment (UDC) for any new dispenser system installed on or after April 11, 2016.
1. A dispenser system is
considered new when both the dispenser and the equipment needed to connect the
dispenser to the underground storage tank system are installed at an UST facility.
The equipment necessary to connect the dispenser to the underground storage tank
system includes check valves, shear valves, unburied risers or flexible connectors,
or other transitional components that are beneath the dispenser and connect the
dispenser to the underground piping.
2.
Under-dispenser containment shall:
i. Be
liquid-tight on its sides, bottom, and at any penetrations;
ii. Be compatible with the substance conveyed by
the piping; and
iii. Allow for visual
inspection and access to the components in the containment system, or be monitored
for leaks from the dispenser system, in accordance with N.J.A.C. 7:14B-5.12(a)1
ii.
Disclaimer: These regulations may not be the most recent version. New Jersey may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.