Current through Register Vol. 57, No. 6,
March 17, 2025
(a)
Owners and operators of underground storage tank systems which are installed on
or after September 4, 1990, shall obtain a permit in accordance with N.J.A.C.
7:14B-10 before installation and ensure that the systems meet the following
performance standards:
1. Each tank shall be
properly designed and constructed, and any portion underground that routinely
contains product shall be protected from corrosion, in accordance with a code
of practice developed by a nationally recognized association or independent
testing laboratory as specified below:
i. The
tank shall be constructed of fiberglass-reinforced plastic;
ii. The tank shall be constructed of steel
and cathodically protected in the following manner:
(1) The tank shall be coated with a suitable
dielectric material;
(2)
Field-installed cathodic protection systems shall be designed by a Cathodic
Protection Specialist certified in accordance with N.J.A.C. 7:14B-13. The
design shall be based upon data collected onsite by a Cathodic Protection
Specialist or Cathodic Protection Tester certified in accordance with N.J.A.C.
7:14B-13;
(3) Impressed current
systems shall be designed to allow determination of current operating status as
required in
N.J.A.C.
7:14B-5.2(a)3; and
(4) Cathodic protection systems shall be
operated and maintained in accordance with
N.J.A.C.
7:14B-5.2;
iii. The tank shall be constructed of a
steel-fiberglass-reinforced-plastic composite;
iv. The tank shall be constructed of metal
without additional corrosion protection measures provided that:
(1) The tank is installed at a site that is
determined by a Department certified Cathodic Protection Specialist not to be
corrosive enough to cause it to have a release due to corrosion during its
operating life; and
(2) Owners and
operators maintain records that demonstrate compliance with the requirements of
(a)1iv(1) above for the remaining life of the tank;
v. Except as set forth in (a)1v(1) below,
each tank for which installation begins on or after April 11, 2016, shall be
designed and constructed with secondary containment and interstitial monitoring
in accordance with
N.J.A.C.
7:14B-6.5(a) 7, such that in
the event of a primary containment breach the secondary containment shall
contain regulated substances until they are detected and removed. Secondary
containment shall prevent the release of regulated substances to the
environment at all times during the operational life of the tank.
(1) The provisions of (a)1v above shall apply
to a regulated heating oil tank system for which installation begins on or
after July 15, 2018.
vi.
For each tank installed prior to January 16, 2018, that has secondary
containment and is performing interstitial monitoring as of January 16, 2018,
shall maintain interstitial monitoring at all times during the operational life
of the tank.
2. The
piping, including metallic swing joints and metallic flex connectors, that
routinely contains regulated substances and is in contact with the ground shall
be properly designed, constructed, and protected from corrosion in accordance
with a code of practice developed by a nationally recognized association or
independent testing laboratory as specified below:
i. The piping shall be constructed of
fiberglass-reinforced plastic;
ii.
The piping shall be constructed of metal and cathodically protected in the
following manner:
(1) The piping shall be
coated with a suitable dielectric material;
(2) Field-installed cathodic protection
systems shall be designed by a person certified as a Cathodic Protection
Specialist pursuant to N.J.A.C. 7:14B-13;
(3) Impressed current systems shall be
designed to allow determination of current operating status as required in
N.J.A.C.
7:14B-5.2(a)3; and
(4) Cathodic protection systems shall be
operated and maintained in accordance with
N.J.A.C.
7:14B-5.2;
iii. The piping shall be constructed of metal
without additional corrosion protection measures provided that:
(1) The piping is installed at a site that is
determined by a Department certified Cathodic Protection Specialist to not be
corrosive enough to cause it to have a release due to corrosion during its
operating life; and
(2) Owners and
operators maintain records that demonstrate compliance with the requirements of
(a)2iii(1) above for the remaining life of the piping; and
iv. Except as set forth in (a)2iv(1) below,
all new or replaced piping for which installation begins on or after April 11,
2016, except suction piping that meets the requirements of
N.J.A.C.
7:14B-6.2(a) 2ii(1) through
(5) and piping associated with field-constructed tanks greater than 50,000
gallons or airport hydrant systems, shall be designed, constructed, and
installed with secondary containment and interstitial monitoring in accordance
with N.J.A.C.
7:14B-6.5(a)7, such that in
the event of a primary containment breach, the secondary containment shall
contain the regulated substances until they are detected and removed. Secondary
containment shall prevent the release of regulated substances to the
environment at all times during the operational life of the UST system.
(1) For a regulated heating oil tank system,
the provisions of (a)2iv above shall apply to new or replaced piping for which
installation begins on or after July 15, 2018.
v. For piping installed prior to January 16,
2018, that has secondary containment and performing interstitial monitoring as
of January 16, 2018, shall maintain interstitial monitoring at all times during
the operational life of the piping.
3. Except as provided in (a) 3iv and v below,
to prevent spilling and overfilling associated with product transfer to the
underground storage tank system, owners and operators shall use the following:
i. Spill prevention equipment that shall
prevent release of product to the environment when the transfer hose is
detached from the fill pipe (for example, a spill catchment basin);
ii. Overfill prevention equipment, compatible
with the delivery method used to fill the tank, that shall:
(1) Automatically shut off flow into the tank
when the tank is no more than 95 percent full;
(2) Alert the transfer operator when the tank
is no more than 90 percent full by restricting the flow into the tank or
triggering a high-level alarm; or
(3) Restrict flow 30 minutes prior to
overfilling, alert the operator with a high level alarm one minute before
overfilling, or automatically shut off flow into the tank so that none of the
fittings located on top of the tank are exposed to product due to overfilling;
and
iii. Spill and
overfill prevention equipment tested or inspected in accordance with
N.J.A.C.
7:14B-5.10.
iv. Flow restrictors in vent lines shall not
be used to comply with (a)3ii above when overfill prevention equipment is
installed or replaced after October 13, 2015, or the date provided at
40 CFR
280.20, whichever is later.
v. Owners and operators are not required to
use the spill and overfill prevention equipment specified in (a)3i, ii, and iii
above if the underground storage tank system is filled by transfers of no more
than 25 gallons at one time.
i.
Spill prevention equipment that shall prevent release of product to the
environment when the transfer hose is detached from the fill pipe (for example,
a spill catchment basin); and
4. The UST system shall be properly installed
in accordance with a code of practice developed by a nationally recognized
association or independent testing laboratory and in accordance with the
manufacturer's instructions.
5. All
owners and operators shall ensure that the following methods of certification
or inspection are used to demonstrate compliance with
N.J.A.C.
7:14B-4.1(a)4 by
maintaining documents in accordance with the recordkeeping requirements of
N.J.A.C.
7:14B-5.6.
i. The installer has been certified by the
tank and piping manufacturers;
ii.
The installer has been certified by the Department in the category of Entire
System Installation in accordance with N.J.A.C. 7:14B-13;
iii. All work listed in the manufacturer's
installation checklists has been completed in accordance with
N.J.A.C. 7:14B-5.6;
and
iv. Owners and operators of an
UST system installed after January 16, 2018, shall obtain a certification by
the UST system installer on the New Jersey Underground Storage Tank Facility
Certification Questionnaire, pursuant to
N.J.A.C.
7:14B-2.2(h).
(b) All underground
storage tank systems installed on or after September 4, 1990, within wellhead
protection areas as defined in
N.J.A.C.
7:14B-1.6 shall be secondarily contained and
monitored in accordance with the requirements of
N.J.A.C.
7:14B-6.4(a)2.
(c) All new underground storage tank systems
using monitoring systems such as vapor or liquid sensors and discharge
detection observation wells which use screen and casing and which are being
placed in the excavation area during installation of the tank system shall
obtain a well permit as specified in the Subsurface and Percolating Waters Act,
N.J.S.A.
58:4A-4.1 et seq., unless the wells are
constructed in the following manner:
1.
Screen and casing materials shall be compatible with the substances stored in
the underground storage tank system so as not to preclude the use of the
monitoring system;
2. Solid casing
shall extend at least two feet below the surface. Glue shall not be used to
attach screen to casing. The casing shall be grouted with at least two feet of
neat cement to protect against surface infiltration. Screens shall be capped at
the bottom;
3. All monitoring
systems using screen and casing shall have protective coverings at the surface.
Grade level access ports shall be four inches greater in diameter than the
casing, watertight and strong enough to withstand the anticipated traffic load.
For casing that extends above grade, a protective outer casing at least four
inches greater in diameter than that of the inner casing shall be used. The
protective coverings shall be seated in neat cement;
4. The top of the screen shall be located at
least two feet above the seasonal high water table and five feet into the water
table for ground water observation wells;
5. The innermost casing or cap shall be
perforated with one hole to allow for venting; and
6. The screen shall be designed to minimize
migration of natural soils or filter pack in the well.
(d) The owner and operator of a proposed
monitoring system which uses screen and casing and is not in conformance with
(c) above shall comply with
N.J.S.A.
58:4A-4.1 et seq., the Subsurface and
Percolating Water Act.
(e) The
following codes and standards, incorporated herein by reference, as amended and
supplemented, shall be used to comply with (a)1i above:
1. Underwriters Laboratories Standard 1316,
"Glass-Fiber-Reinforced Plastic Underground Storage Tanks for Petroleum
Products, Alcohols, and Alcohol-Gasoline Mixtures" (available at
www.UL.com); or
2. Underwriters Laboratories of Canada
ULC-S615, "Standard for Fibre Reinforced Plastic Underground Tanks for
Flammable and Combustible Liquids" (available at canada.UL.com).
(f) The following codes and
standards, incorporated herein by reference, as amended and supplemented, shall
be used to comply with (a)1ii:
1. Steel Tank
Institute "sti-P3(R) Specification and Manual for External Corrosion Protection
of Underground Steel Storage Tanks" (available at
www.steeltank.com);
2. Underwriters Laboratories of Canada
ULC-S603, "Standard for Steel Underground Tanks for Flammable and Combustible
Liquids"; ULC-S603.1, "External Corrosion Protection Systems for Steel
Underground Tanks for Flammable and Combustible Liquids"; and ULC-S631,
"Standard for Isolating Bushings for Steel Underground Tanks Protected with
External Corrosion Protection Systems";
3. NACE International Standard Practice SP
0285, "External Corrosion Control of Underground Storage Tank Systems by
Cathodic Protection," (available at
www.NACE.org) and Underwriters Laboratories Standard
58, "Standard for Steel Underground Tanks for Flammable and Combustible
Liquids" (available at
www.UL.com);
4. Underwriters Laboratories Standard 1746,
"Standard for External Corrosion Protection Systems for Steel Underground
Storage Tanks" (available at
www.UL.com);
or
5. Steel Tank Institute Standard
F841, "Standard for Dual Wall Underground Steel Storage Tanks" (available at
www.steeltank.com).
(g) The following codes and standards, as
applicable, incorporated herein by reference, as amended and supplemented,
shall be used to comply with (a)1iii above:
1. Underwriters Laboratories Standard 1746,
"External Corrosion Protection Systems for Steel Underground Storage Tanks"
(available at
www.UL.com);
2. Steel Tank Institute ACT-100R
Specification F894, "Specification for External Corrosion Protection of FRP
Composite Steel Underground Storage Tanks" (available at
www.steeltank.com);
3. Steel Tank Institute ACT-100-UR
Specification F961, "Specification for External Corrosion Protection of
Composite Steel Underground Storage Tanks" (available at
www.steeltank.com); or
4. Steel Tank Institute Specification F922,
"Steel Tank Institute Specification for Permatank(R)" (available at
www.steeltank.com).
(h) The following codes and standards,
incorporated herein by reference, as amended and supplemented, shall be used to
comply with (a)2i above:
1. Underwriters
Laboratories Standard 971, "Non-Metallic Underground Piping for Flammable
Liquids" (available at
www.UL.com);
2. Underwriters Laboratories Standard 567,
"Pipe Connectors for Petroleum Products and LP Gas" (available at
www.UL.com); or
3. Underwriters Laboratories of Canada
Standard S660, "Standard for Nonmetallic Underground Piping for Flammable and
Combustible Liquids" (available at canada.UL.com).
(i) The following codes and standards,
incorporated herein by reference, as amended and supplemented, shall be used to
comply with (a)2ii above:
1. National Fire
Protection Association Standard 30, "Flammable and Combustible Liquids Code"
(obtained from: P.O. Box 9101, Quincy, MA 02269-9101);
2. American Petroleum Institute Publication
1615, "Installation of Underground Storage Petroleum Systems" (obtained from
Global Engineering Documents at 15 Inverness Way East, Englewood, Colorado
80122);
3. American Petroleum
Institute Publication 1632, "Cathodic Protection of Underground Petroleum
Storage Tanks and Piping Systems" (available at
www.api.org);
4. NACE International Standard Practice SP
0169, "Control of External Corrosion on Underground or Submerged Metallic
Piping Systems" (available at
www.NACE.org);
5. Underwriters Laboratories Subject 971A,
"Outline of Investigation for Metallic Underground Fuel Pipe" (available at
www.UL.com);
6. Steel Tank Institute Recommended Practice
R892, "Recommended Practice for Corrosion Protection of Underground Piping
Networks Associated with Liquid Storage and Dispensing Systems" (available at
www.steeltank.com); or
7. NACE International Standard Practice SP
0285, "External Corrosion Control of Underground Storage Tank Systems by
Cathodic Protection" (available at
www.NACE.org).
(j) The following codes and standards,
incorporated herein by reference, as amended and supplemented, shall be used to
comply with (a)2iii above:
1. National Fire
Protection Association Standard 30, "Flammable and Combustible Liquids Code";
or
2. NACE International Standard
Practice SP 0169, "Control of External Corrosion on Underground or Submerged
Metallic Piping Systems" (available at
www.NACE.org).
(k) The UST system installation practices and
procedures described in the following codes and standards, incorporated herein
by reference, as amended and supplemented, shall be used to comply with (a)4
above:
1. American Petroleum Institute
Publication 1615, "Installation of Underground Petroleum Storage Systems"
(available at
www.api.org);
2. Petroleum Equipment Institute Publication
RP100, "Recommended Practices for Installation of Underground Liquid Storage
Systems" (available at
www.pei.org);
3. American National Standards Institute
Standard B31.3, "Process Piping," and American National Standards Institute
Standard B31.4, "Liquid Transportation Systems for Hydrocarbons, Liquid
Petroleum Gas, Anhydrous Ammonia and Alcohols" (available at global.ihs.com);
or
4. National Fire Protection
Association Standard 30, "Flammable and Combustible Liquids Code" and Standard
30A, "Code for Motor Fuel Dispensing Facilities and Repair Garages" (available
at
www.nfpa.org).
(l) No underground storage system shall be
installed:
1. Within 50 feet of a public
community supply system well, pursuant to
N.J.A.C.
7:10-11.4(b)2; and
2. Within 50 feet of a nonpublic community
supply system well.