New Jersey Administrative Code
Title 7 - ENVIRONMENTAL PROTECTION
Chapter 14A - NEW JERSEY POLLUTANT DISCHARGE ELIMINATION SYSTEM
Subchapter 23 - TECHNICAL REQUIREMENTS FOR TREATMENT WORKS APPROVAL APPLICATIONS
Section 7:14A-23.25 - Ultraviolet disinfection
Universal Citation: NJ Admin Code 7:14A-23.25
Current through Register Vol. 56, No. 18, September 16, 2024
(a) The following provisions apply to the design of ultraviolet disinfection (UV) systems:
1. The turbidity and color of the wastewater shall
be addressed in the design. Treatment of the influent wastewater prior to the UV
units by intermittent sand filtration, or other filtration, as approved by the
Department, is recommended. Removable screens, located upstream of the UV unit, are
recommended to prevent debris from entering the system.
2. Wastewater shall pass over the UV source in a
thin film, so that the maximum depth of penetration is no greater than two inches.
The UV contact time shall be dictated by water absorbance and film
thickness.
3. A UV intensity sensor
shall be installed at the maximum depth from the source with an alarm to alert
operators when the UV level falls below acceptable levels. The UV intensity reading
shall be displayed by a meter on the control panel. UV sensors shall be properly
maintained to insure reliable, accurate readings.
4. The UV unit shall be protected from dust,
excessive heat, and freezing temperatures. Adequate ventilation of heat-generating
electrical components shall be provided.
i. An
alarm system shall be provided to alert the operator of excessive temperatures in
the ballast power panel.
5.
When utilizing a closed channel UV system two separate units, or one UV unit and
another approved form of disinfection, each capable of treating peak flow, shall be
provided.
6. Open channel UV systems
shall be equipped with a sufficient number of bulbs such that a safety factor of at
least 125 percent will be provided. Separate electrical racks shall also be provided
to permit maintenance of the system without removing the entire unit from
service.
7. Electrical wiring shall be
properly sized and the wire covering shall be resistant to UV radiation
effects.
(b) UV lamps/sleeves shall be chemically cleaned semi-annually if automatic wipers are present, or three to four times per year if automatic wipers are not present. A clean water supply equipped with a back flow prevention device shall be available at all times.
(c) UV bulbs shall be replaced when dead life occurs (60 percent of initial emission).
Disclaimer: These regulations may not be the most recent version. New Jersey may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google
Privacy Policy and
Terms of Service apply.