New Jersey Administrative Code
Title 5 - COMMUNITY AFFAIRS
Chapter 70 - UNIFORM FIRE CODE
Subchapter 4 - FIRE SAFETY CODE
Section 5:70-4.19 - Smoke alarms for one- and two-family dwellings; carbon monoxide alarms; and portable fire extinguishers
Current through Register Vol. 56, No. 18, September 16, 2024
(a) In one- and two-family or attached single family dwellings subject to the requirements of 5:70-2.3, smoke alarms shall be installed as follows:
(b) The smoke alarms required in (a) above shall be located and maintained in accordance with NFPA 72.
(c) Ten-year sealed battery-powered single station smoke alarms shall be installed and shall be listed in accordance with ANSI/UL 217, incorporated herein by reference. However, A/C-powered single or multiple-station smoke alarms installed as part of the original construction or rehabilitation project shall not be replaced with battery-powered smoke alarms. The effective date of this subsection shall be January 1, 2019.
(d) Carbon monoxide alarms shall be installed in all dwelling units in buildings in one- and two-family or attached single-family dwellings, except for units in buildings that do not contain a fuel-burning device or have an attached garage, as follows:
(e) A portable fire extinguisher shall be installed in accordance with the following: