New Jersey Administrative Code
Title 5 - COMMUNITY AFFAIRS
Chapter 70 - UNIFORM FIRE CODE
Subchapter 4 - FIRE SAFETY CODE
Section 5:70-4.12 - Interior finish
Current through Register Vol. 56, No. 18, September 16, 2024
(a) The interior finish of walls and ceilings shall have a flame spread rating not greater than the class prescribed by Table 5:70-4.12(a).
Click here to view image.
(b) The classification of interior finishes referred to herein corresponds to flame spread ratings determined by ASTM E84 as follows: Class I flame spread, 0-25; Class II flame spread, 26-75; Class III flame spread, 76-200. In all cases, the smoke developed rating determined by ASTM E84 shall not exceed 450.
(c) All existing interior finish materials which do not comply with the requirements of this section shall be removed or shall be treated with an approved fire retardant coating in accordance with the manufacturer's instructions to secure compliance with the requirements of this section.
(d) In buildings of Use Group I-3, interior furnishings, drapes, curtains, carpeting, decorations, bedding, etc. shall be flame retardant.