New Jersey Administrative Code
Title 5 - COMMUNITY AFFAIRS
Chapter 27 - REGULATIONS GOVERNING ROOMING AND BOARDING HOUSES
Subchapter 4 - GENERAL BUILDING REQUIREMENTS
Section 5:27-4.5 - Ventilation
Current through Register Vol. 56, No. 6, March 18, 2024
(a) Means of ventilation shall be provided for every habitable room. Such ventilation may be provided either by an easily operable window or skylight having an openable area of at least 50 percent of the minimum window area or minimum skylight area as required in 5:27-4.4(a), or by other means acceptable to the Bureau which will provide at least two air changes per hour.
(b) Means of ventilation shall be provided for every bathroom or water closet compartment. Such ventilation may be provided either by an easily operable window or skylight having an openable area of at least 50 percent of the minimum window area or minimum skylight area as required in 5:27-4.4(a), or by other means acceptable to the Bureau which will provide at least six air changes per hour.