Current through Register Vol. 56, No. 18, September 16, 2024
(a) The following
requirements shall be met for materials and installation methods for all items
that are part of the applicant's proposed project for all categories of work
other than repair as defined in
N.J.A.C.
5:23-6.3.
1. Where sections listed below reference
other sections not listed below, those sections shall apply within that limited
context.
(b) Building and
Fire Protection Materials and Methods: The following sections of the building
subcode (N.J.A.C. 5:23-3.14) shall
constitute the building and fire protection materials and methods requirements
for this subchapter:
1. The following
sections of Chapter 5 entitled "General Building Height and Areas":
i. Section 505 shall apply to newly
constructed "Mezzanines and Equipment Platforms";
2. The following sections of Chapter 7
entitled "Fire and Smoke Protection Features":
i. Sections 703.2, 703.3, 703.4, 703.6,
703.7;
ii. Sections 705.2.1,
705.2.2, 705.4;
iii. Sections
706.2, 706.3;
iv. Sections 707.2,
707.9;
v. Section 708.2;
vi. Section 709.2;
vii. Sections 710.2, 710.5, 710.6, 710.7,
710.8;
viii. Sections 711.2.1,
711.3.1;
ix. Section
712.1.13;
x. Section
713.3;
xi. Section 714;
xii. Section 715;
xiii. Section 716;
xiv. Section 717;
xv. Sections 718.2.1, 718.3.1;
xvi. Section 719;
xvii. Section 720;
xviii. Section 721; and
xix. Section 722;
3. All of Chapter 8 entitled "Interior
Finishes";
4. All of Chapter 9
entitled "Fire Protection Systems," except Sections 902, 903.2, 903.3.2, 904.2,
905.3, 906.1, 907.2, 908.1, 908.2, 910.2, 911, 917, and 918;
5. The following sections of Chapter 10
entitled "Means of Egress":
i. Sections 1010.2
and 1010.3;
(1) Sections 1010.2.9.3 and
1010.2.9.4 shall be the only sections that apply within Section
1010.2.9.
ii. Sections
1013.3, 1013.4, 1013.5, and 1013.6;
iii. Section 1015.8.1; and
iv. Sections 1025.4, 1025.5;
6. The following sections of
Chapter 12 entitled "Interior Environment":
i. Section 1202.5.2 shall apply to new
sources of contaminants; and
ii.
Section 1209;
7. All of
Chapter 14 entitled "Exterior Walls" except Sections 1401, 1402.2, 1402.3,
1402.4;
8. All of Chapter 15
entitled "Roof Assemblies and Rooftop Structures" except Sections 1501, 1502,
1503.4, and 1511.8;
9. All of
Chapter 16 entitled "Structural Design," except Sections 1601, 1604, 1608,
1609, 1610, 1611, 1612, 1613, 1614, 1615, and 1616 shall apply to new or
replaced structural members. The referenced sections of Chapter 16 shall not be
used to analyze any existing structural members, except as otherwise provided
by this subcode;
10. All of Chapter
18 entitled "Soil and Foundations" except Sections 1801, 1802, 1803, 1804,
1805, 1806;
i. Additionally, the following
requirements of Section 1805 shall be included as part of Materials and
Methods: 1805.2.1, 1805.2.2, 1805.3.1, 1805.3.2, 1805.3.3, 1805.4.1, 1805.4.2,
1805.4.3;
11. All of
Chapter 19 entitled "Concrete" except Sections 1901, 1902;
12. All of Chapter 20 entitled
"Aluminum";
13. All of Chapter 21
entitled "Masonry" except Sections 2101, 2102;
14. All of Chapter 22 entitled "Steel" except
Section 2201;
15. All of Chapter 23
entitled "Wood" except Section 2301.1;
16. All of Chapter 24 entitled "Glass and
Glazing" except Sections 2401, 2402;
17. All of Chapter 25 entitled "Gypsum Board
and Plaster" except Sections 2501.1, 2502;
18. All of Chapter 26 entitled "Plastic"
except Sections 2601, 2602;
19. For
the applicability of Chapter 30 entitled "Elevators and Conveying Systems,"
refer to (i) and (j) below; and
20.
The following sections of Chapter 31 entitled "Special Construction":
i. Section 3105;
ii. Sections 3106.3;
iii. Section 3107;
iv. Section 3109 shall apply to newly
installed and completely replaced enclosures for swimming pools, spas, and hot
tubs. This shall also apply to partial enclosure replacement if the portion
being replaced exceeds 25 percent of the total perimeter of the
enclosure;
v. Section
3110;
vi. Section 3111 shall apply
to newly installed and completely replaced solar energy systems; and
vii. Section 3115 shall apply to newly
repurposed intermodal shipping containers.
(c) Plumbing Materials and Methods: The
following sections of the plumbing subcode (N.J.A.C.
5:23-3.15) shall constitute the plumbing
materials and methods requirements for this subchapter:
1. All of Chapter 2 entitled "General
Regulations" except Section 2.19:
i. Sections
2.16a.1 and 2 shall not apply to the replacement of water service or building
sewers in the same location.
ii.
Section 2.19 for availability of public water supply and sewer shall apply when
existing septic or water supply facilities are no longer suitable for use as
determined by the local health inspector, and public facilities are available
within the meaning of Section 2.19.
2. All of Chapter 3 entitled
"Materials."
3. All of Chapter 4
entitled "Joints and Connections."
4. All of Chapter 5, entitled "Traps,
cleanouts and backwater valves."
5.
Chapter 6, entitled "Liquid Waste Treatment Equipment" except Sections 6.1.1,
6.3.1, and 6.4.1:
i. Section 6.1.1, 6.3.1,
6.4.1 for when interceptors are required shall not apply. However, when new
fixtures, or devices are installed that will produce wastes that need to be
separated, an interceptor shall be required.
6. Chapter 7, entitled "Plumbing Fixtures,
Fixture Fittings and Plumbing Appliances" except section 7.21 and table
7.21.1.
7. Chapter 8 entitled
"Hangers and Supports."
8. Chapter
9 entitled "Indirect Wastes Piping and Special Waste."
9. Chapter 10 entitled "Water Supply and
Distribution" except for sections 10.3, 10.6.5, 10.8.1, 10.14 and 10.15.9:
i. Water shall be supplied so that fixtures
within a building are provided with an adequate supply of water so that they
are functional.
ii. In Section
10.6.4, the minimum of five feet for the wall sleeve shall not be required for
"trenchless pipe replacement systems" for water service replacement using
plastic pipe.
iii. Section 10.6.5
shall apply to all newly-installed or completely replaced water
services.
iv. Section 10.8.1 shall
apply, where there is not sufficient pressure for proper functioning of
fixtures, a water pressure booster system shall be required.
v. Section 10.14 for sizing water
distribution systems shall apply when the proposed work will impose additional
loads on the system. Where the proposed work does not increase or decreases the
load on the existing system, no increase in size shall be required. All new
piping associated with the installation of additional fixtures shall comply
with the sizing requirements of Chapter 10.
10. All of Chapter 11, entitled "Sanitary
Drainage Systems" except 11.2.2, 11.2.3, 11.5, and 11.6:
i. Section 11.2.3 for sizing building sewers shall apply when the
proposed work will impose additional loads on the sewer. Where the proposed
work does not increase or decreases the load on the existing system, no
increase in size shall be required.
ii. Section 11.5 for sizing drainage systems shall apply when the
proposed work will impose additional loads on the system. Where the proposed
work does not increase or decreases the load on the existing system, no
increase in size shall be required. All new piping associated with the
installation of additional fixtures shall comply with the sizing requirements
of 11.5.
iii. Section 11.6 for
sizing offsets in drainage systems shall apply when the proposed work will
impose additional loads on the system. Where the proposed work does not
increase or decreases the load on the existing system, no increase in size
shall be required.
11. All
of Chapter 12, entitled "Vents and Venting" except 12.3.1, 12.3.2 and 12.16:
i. Section 12.3.1 for locations where vent
stacks are required shall apply where new stacks are being installed;
ii. Section 12.3.2 "Relief Vents for Stacks
having Ten or More Branch Intervals" shall apply only when new stacks of ten or
more branch intervals are being installed; and
iii. Section 12.16 for size and length of
vents shall apply when new vents are being installed.
12. All of Chapter 13 entitled "Storm Water
Drainage" except Sections 13.1.1, 13.1.2, 13.1.6, 13.1.7, 13.1.10.1, 13.4.3,
13.6.1, and 13.6.2:
i. Section 13.1.1 for
where storm water drains are required shall apply only when new roofs, paved
areas, yards, courts and courtyards are created.
ii. Section 13.1.2 "Storm Water Drainage to
Sewer Prohibited" shall not be applied to existing connections to the sewer.
This section shall only prohibit the connection of new storm water drains to a
sanitary sewer that is prohibited from accepting such discharge.
iii. Section 13.1.6 "Areaway Drains" shall
apply only to newly created, open, below grade areaways where storm water can
accumulate.
iv. Section 13.1.7
"Window Well Drains" shall apply only to newly created window wells.
v. Section 13.1.10.1 for sizing roof drains,
as amended in
N.J.A.C.
5:23-3.15, shall apply only where additional
roof area is to be drained or where other circumstances increase the load on
existing roof drains.
vi. Section
13.4.3 "Combining Storm Water with Sanitary Drainage" shall not be applied to
existing connections to the sewer. This section shall only require that newly
installed sanitary and storm sewers be separate.
vii. Section 13.6.1 "Size of Vertical Storm
Drain Piping" shall only apply when the proposed work will impose additional
loads on the system. Where the proposed work does not increase or decreases the
load on the existing system, no increase in size shall be required.
viii. Section 13.6.2 "Size of Horizontal
Storm Drain Piping" shall only apply when the proposed work will impose
additional loads on the system. Where the proposed work does not increase or
decreases the load on the system, no increase in size shall be
required.
13. All of
Chapter 14 entitled "Special Requirements For Health Care
Facilities."
14. All of Chapter 15
entitled "Tests and Maintenance."
15. Section 16.1.7 of Chapter 16 entitled
"Regulations Governing Individual Sewage Disposal Systems for Homes and Other
Establishments Where Public Sewage Systems Are Not
Available."
(d)
Electrical Materials and Methods. The following sections of the electrical
subcode (N.J.A.C. 5:23-3.16) shall
constitute the electrical materials and methods requirements for this
subchapter:
1. Section 90.7, entitled
"Examination of Equipment for Safety" of the Introduction, Article
90;
2. All of Chapter 1 entitled
"General" except Sections 110.8 Wiring Methods, 110.26 Spaces About Electrical
Equipment (1,000 Volts, Nominal, or less), 110.32 Work Space About Equipment
(over 1,000 Volts, Nominal) and 110.33 Entrance to Enclosures and Access to
Working Space;
i. Section 110.32 shall be
required for upgrading the complete system or where the voltage is
increased;
3. All of
Chapter 2 entitled "Wiring and Protection" except Sections 210.11 Branch
Circuits Required, 210.12 Arc-Fault Circuit-Interrupter Protection, 210.52
Dwelling Unit Receptacle Outlets, 210.60 Guest Rooms or Guest Suites
Dormitories and Similar Occupancies, 210.62 Show Windows, 210.63 Equipment
Requiring Servicing, and 210.70 Lighting Outlets Required;
i. In applying item #3 of the exception of
Section 250.140, the branch circuit may originate at a location other than the
service equipment.
4. All
of Chapter 3 entitled "Wiring Methods and Materials";
5. All of Chapter 4, entitled "Equipment for
General Use" except Section 404.8 Accessibility and Grouping (switches) and
Section 408.18 Clearances (switchboards and switchgear);
6. All of Chapter 5, entitled "Special
Occupancies;"
7. All of Chapter 6,
entitled "Special Equipment;"
8.
All of Chapter 7, entitled "Special Conditions;" and
9. All of Chapter 8 entitled "Communications
Systems."
10. Existing working
clearances, clear space, access and entrance dimensions to working spaces,
illumination, headroom clearances, and location of overcurrent protection
devices shall be allowed to remain without modification.
(e) Mechanical Materials and Methods: The
following sections of the mechanical subcode (N.J.A.C.
5:23-3.20) shall constitute the mechanical
materials and methods requirements for this subchapter:
1. All of Chapter 3, entitled "General
Regulations" except Sections 301.2, 301.10, 301.11, 301.16, 301.18, 303.5,
303.6, 303.7, 306, 307.2.3, 309, and 312;
i.
Section 312 shall apply when appliance/equipment input ratings are
increased.
2. All of
Chapter 4, entitled "Ventilation" except Sections 402, 403, and 407;
3. All of Chapter 5, entitled "Exhaust
Systems" except Sections 502, 509, 510, and 513;
i. Section 509 shall apply to newly installed
or replaced commercial food heat-processing appliances and Type I
hoods;
ii. Section 510 shall apply
to newly introduced sources of hazardous exhaust;
4. All of Chapter 6, entitled "Duct Systems"
except Sections 602, 604.1, and 608;
i.
Section 602 shall apply to newly constructed plenums. Modifications to existing
plenums, such as installation of new building, electrical, or plumbing
materials inside the plenum, increasing air flow rate within the plenum, etc.
shall not require the plenum to comply with the construction requirements for
new plenums. However, newly installed materials within the plenum shall be
consistent with material requirements of Section 602; and
ii. Section 608 shall apply to newly
installed systems.
5. All
of Chapter 7, entitled "Combustion Air";
i.
Chapter 7 shall not apply if the work being performed does not increase the
input rating of the equipment.
6. All of Chapter 8, entitled "Chimneys and
Vents";
7. All of Chapter 9,
entitled "Specific Appliances, Fireplaces and Solid Fuel-Burning
Equipment";
8. All of Chapter 10,
entitled "Boiler, Water Heaters and Pressure Vessels";
9. All of Chapter 11, entitled
"Refrigeration," except Section 1105.9;
10. All of Chapter 12, entitled "Hydronic
Piping" except Section 1204;
11.
All of Chapter 13, entitled "Fuel Oil Piping and Storage" except Section
1305.1;
i. Section 1305.1 shall apply when the
work being performed increases the load on the system such that the existing
pipe does not meet the size required by code. Existing systems that are
modified shall not require resizing as long as the load on the system is not
increased and the system length is not increased even if the altered system
does not meet code minimums; and
12. All of Chapter 14, entitled "Solar
Thermal Systems."
(f)
Fuel Gas Materials and Methods: The following sections of the fuel gas subcode
(N.J.A.C.
5:23-3.22) shall constitute the fuel gas
materials and methods requirements of this subchapter:
1. All of Chapter 3, entitled "General
Regulations" except Sections 301.2, 301.6, 301.11, 301.12, 303.7, and 306
(excluding Section 306.6);
i. Section 304
shall not apply if the work being performed does not increase the input rating
of the equipment.
2. All
of Chapter 4, entitled "Gas Piping Installations" except Sections 401.8 and
402.3;
i. Sections 401.8 and 402.3 shall
apply when the work being performed increases the load on the system such that
the existing pipe does not meet the size required by code. Existing systems
that are modified shall not require resizing as long as the load on the system
is not increased and the system length is not increased even if the altered
system does not meet code minimums;
3. All of Chapter 5, entitled "Chimneys and
Vents";
i. Section 503.6.10 shall apply only
when the equipment being installed results in a greater output to the common
venting system;
4. All of
Chapter 6, entitled "Specific Appliances"; and
5. All of Chapter 7, entitled "Gaseous
Hydrogen Systems."
(g)
Barrier Free Materials and Methods: The requirements of ICC A117.1 shall
constitute the barrier free materials and methods requirements for this
subchapter and shall apply to work projects in all buildings other than
buildings of Group R-2, R-3, R-4, or R-5 containing fewer than four dwelling
units or buildings of Use Group U.
1.
Exception: Where full compliance is technically infeasible, compliance shall be
achieved to the maximum extent feasible.
2. For toilet or bathing facilities, at least
one of each type of fixture shall comply with the barrier free materials and
methods. Where six or more toilet stalls are provided, in addition to a
wheelchair accessible stall, at least one ambulatory accessible stall shall be
provided.
3. Limited exceptions to
the accessibility requirements for theatres and auditoriums are permitted as
follows:
i. Where fixed seating is provided
and it is technically infeasible to provide integrated accessible seating,
accessible seating may be clustered.
ii. When a facility contains more than one
performing area and it is technically infeasible to make all performing areas
accessible, the provision of one accessible performing area shall be accepted
as meeting the requirement for providing access to performing areas.
4. In buildings of Group M, where
fitting room partitions are installed or moved, five percent of the fitting
rooms, but not less than one, shall comply.
5. Section 309 of the ICC A117.1 shall not
apply to electrical panelboard replacement (s).
(h) Residential Materials and Methods: The
following sections of the one- and two-family dwelling subcode (N.J.A.C.
5:23-3.21) shall constitute the residential
materials and methods requirements for this subchapter:
1. The following sections of Chapter 3,
entitled "Building Planning":
i. Section
R301.8;
ii. Sections R302.10,
R302.14;
iii. Section
R307.2;
iv. Section R308;
v. Section R309.4;
vi. Sections R313.1.1, R313.2.1;
vii. Sections R314.1.1, R314.5, R314.7.1,
R314.7.4;
viii. Sections R315.1.1,
R315.4, R315.7.1, R315.7.4;
ix.
Section R316;
x. Section R317;
and
xi. Section R318;
xii. Section R324 shall apply to newly
installed and completely replaced solar energy systems;
xiii. Section R327 shall apply to newly
installed and completely replaced enclosures for swimming pools, spas, and hot
tubs. This shall also apply to partial enclosure replacement if the portion
being replaced exceeds 25 percent of the total perimeter of the
enclosure;
xiv. Section R328 shall
apply to newly installed and completely replaced stationary storage battery
systems;
xv. Section R329 shall
apply to newly installed and completely replaced stationary engine generators;
and
xvi. Section R330 shall apply
to newly installed and completely replaced stationary fuel cell power
systems;
2. The following
sections of Chapter 4 entitled "Foundations":
i. Section R402; and
ii. Section R407;
3. The following sections of Chapter 5
entitled "Floors":
i. Sections R502.1, R502.8,
R502.11;
ii. Sections R503.2.1,
R503.2.3, R503.3.1, R503.3.3;
iii.
Sections R504.1.2, R504.1.3, R504.3;
iv. Sections R505.2.1, R505.2.2, R505.2.3,
R505.2.4, R505.2.5, R505.2.6 for web hole patching only, and R505.3.5;
and
v. Section R507 shall apply to
newly installed and completely replaced decks;
4. The following sections of Chapter 6
entitled "Wall Construction":
i. Sections
R602.1, R602.2, R602.6;
ii.
Sections R603.2.1, R603.2.2, R603.2.3, R603.2.4, R603.2.5, R603.2.6 for web
hole patching only, and R603.3.4;
iii. Sections R604.1, R604.3;
iv. Section R605;
v. Sections R606.1, R606.2;
vi. Section R607.2;
vii. Sections R608.5.1.1, R608.5.1.2,
R608.5.2, R608.5.3;
viii. Sections
R609.3, R609.4, R609.5; and
ix.
Sections R610.3, R610.7;
5. All of Chapter 7 entitled "Wall
Covering";
6. The following
sections of Chapter 8, entitled "Roof-Ceiling Construction":
i. Sections R802.1, R802.7,
R802.10.4;
ii. Section R803.2.1;
and
iii. Sections R804.2.1,
R804.2.2, R804.2.3, R804.2.4, R804.2.5, R804.2.6 for web hole patching only,
and R804.3.3;
7. All of
Chapter 9 entitled "Roof Assemblies", except Section R907.
i. Section R907 shall apply to newly
installed and completely replaced panel systems;
8. All of Chapter 10 entitled "Chimneys and
Fireplaces";
9. All of Chapter 13,
entitled "General Mechanical System Requirements", except Section M1301.1.1 and
M1305;
10. All of Chapter 14,
entitled "Heating and Cooling Equipment and Appliances," except Sections
M1401.2, M1401.3, and M1401.5;
11.
All of Chapter 15, entitled "Exhaust Systems";
12. All of Chapter 16, entitled "Duct
Systems";
13. All of Chapter 17,
entitled "Combustion Air," except M1701.2;
i.
Chapter 17 shall not apply if the work being performed does not increase the
input rating of the equipment.
14. All of Chapter 18, entitled "Chimneys and
Vents";
15. All of Chapter 19,
entitled "Special Appliances, Equipment and Systems";
16. All of Chapter 20, entitled "Boilers and
Water Heaters";
17. All of Chapter
21, entitled "Hydronic Piping";
18.
All of Chapter 22, entitled "Special Piping and Storage Systems";
19. All of Chapter 23, entitled "Solar
Thermal Energy Systems"; and
20.
All of Chapter 24, entitled "Fuel Gas," except Sections G2404.7, G2404.8,
G2412.8, and G2413.3.
i. Section G2407 shall
not apply if the work being performed does not increase the input rating of the
equipment.
ii. Sections G2412.8 and
G2413.3 shall apply when the work being performed increases the load on the
system such that the existing pipe does not meet the size required by code.
Existing systems that are modified shall not require resizing as long as the
load on the system is not increased and the system length is not increased even
if the altered system does not meet code minimums;
(i) Elevator Devices Materials and
Methods: The following sections of the elevator subcode (N.J.A.C. 5:23-12)
shall constitute the elevator device materials and methods requirements for
this subchapter:
1. The following sections of
the elevator subcode and ASME A17.1 referenced by the adopted building subcode:
N.J.A.C.
5:23-12.2(c) and 12.8, ASME
A17.1, Sections 8.7 Alterations, 8.8, Welding; and 8.9, Code Data Plate, and
Appendices, except for E, J, N, T, W, X, and Y.
2. The following section of Chapter 30 of the
building subcode: Section 3002.1.2--"Hoistway Enclosures, Hardware."
3. The requirements of ASME A17.1 Section
2.8.3.3, as referenced by the adopted building subcode, when an automatic
sprinkler system is installed in an elevator hoistway, machine room and/or
machinery space.
4. When a
controller is replaced, without any change in the type of operation or control,
the newly installed controller shall conform to the requirements of ASME A17.1
Sections 2.26.4 and 2.26.9. The installation shall also conform to the
requirements of ASME A17.1 Sections 2.25; 2.26.6; 2.26.7; and 2.26.8.
5. When a controller is replaced, with any
change in the type of operation or control, the newly installed controller
shall conform to the requirements of ASME A17.1 Sections 2.26.4 and 2.26.9. The
installation shall also conform to the requirements of ASME A17.1 Sections
2.25; 2.26.6; 2.26.7; 2.26.8; and 2.27.3 through 2.27.9.
(j) Conveying Devices Materials and Methods:
The following sections of Chapter 30 of the building subcode (N.J.A.C.
5:23-3.14) shall constitute the conveying
device materials and methods requirements for this subchapter:
1. Section 3004.3--"Conveyors"; Section
3004.4--"Personnel and material hoists" and the following referenced standards
from Table 3001.3--"ALI ALCTV," "ANSI MH 29.1," "ASME B20.1."
(k) Manufactured Home Materials
and Methods: The following sections of Part 3280 of Title 24 of the Code of
Federal Regulations shall constitute the manufactured home materials and
methods requirements for this subcode:
1. All
of Part 3280 of Title 24 of the Code of Federal Regulations except 3280.1,
3280.5, 3280.6, 3280.7, and 3280.8.
(l) Energy Conservation Materials and
Methods: The following sections of the energy subcode (N.J.A.C.
5:23-3.18) shall constitute the energy
conservation materials and methods requirements for this subchapter:
1. Residential energy code provisions:
i. The following sections of Chapter 3
entitled "Climate Zones":
(1) Section R303
(N1101.10).
ii. The
following sections of Chapter 4 of the residential energy code entitled
"Residential Energy Efficiency":
(1) Sections
R402.2.3, R402.2.4, R402.2.7, R402.2.11, R402.4.1.1, R402.4.3, R402.4.5, and
R402.4.6 (N1102.2.3, N1102.2.4, N1102.2.7, N1102.2.11, N1102.4.1.1, N1102.4.3,
N1102.4.5, and N1102.4.6).
2. Commercial energy code provisions:
i. The following sections of Chapter 4 of the
commercial energy code entitled "Commercial Energy Efficiency":
(1) Section 4.2.3;
(2) Sections 5.4.3.1.2, 5.4.3.2, 5.5.4.1,
5.8.1, and 5.8.2;
(3) Sections
6.4.1, 6.4.4.1.1, and 6.4.4.2.1;
(4) Section 7.4.2; and
(5) Sections 10.4.1, 10.4.5, and
10.4.7.