Current through Register Vol. 56, No. 18, September 16, 2024
(a) Reconstruction, as defined in
N.J.A.C. 5:23-6.3,
shall comply with the requirements of this section.
1. If a project is less than the entire use,
primary function space or tenancy by a de minimis amount, the construction
official may designate the project a reconstruction project and require that
the requirements of this section be met.
2. If work performed or to be performed in
phases is so extensive that the project would require a new certificate of
occupancy if the work were performed at one time, the construction official may
designate the project a reconstruction project and require that the
requirements of this section be met.
(c) The work shall not
cause any diminution of existing structural strength, system capacity or
mechanical ventilation below that which exists at the time of application for a
permit or that which is required by the applicable subcodes of the Uniform
Construction Code, whichever is lower. The replacement or addition of fixtures,
equipment or appliances shall not increase loads on these systems unless the
system is upgraded in accordance with the applicable subcode of the UCC to
accommodate the increased load.
1. Newly
introduced fixed loads shall not exceed the uniformly distributed live loads or
concentrated live load criteria of Table 1607.1 of the building subcode or
Table R301.5 of the one- and two-family dwelling subcode, as applicable, and
shall not create deflection that exceeds the standards set forth below. As used
in this section, fixed loads shall mean uniform or concentrated loads and shall
include, but not be limited to, equipment, files, library stacks, or similar
loading conditions. (Building)
i. For wood
frame construction, deflection shall not exceed L/180 for roofs with a slope of
3 in 12 or less or L/120 for roofs with a slope of greater than 3 in 12 and for
floors.
ii. For steel frame
construction, deflection shall not exceed L/240 for roofs with a slope of 3 in
12 or less or L/180 for roofs with a slope of greater than 3 in 12 and for
floors.
iii. For concrete
construction, deflection shall not exceed L/180 for roofs or L/240 for
floors.
2. Fire
protection system removal: Any fire protection system providing partial or
redundant protection originally installed to protect a special hazard that no
longer exists and that is not required in accordance with the current Uniform
Construction Code, is allowed to be removed with the written approval of the
fire subcode official and fire official. All disconnected equipment and
devices, such as pull stations, nozzles, detectors, sprinklers, sensors, panels
and hose connections, shall be removed so as not to give a false indication
that the structure, area or space is protected. (Fire)
3. No work shall be undertaken that
diminishes accessibility below that which is required by Chapter 11 of the
building subcode. (Building)
4.
Construction materials used as part of a reconstruction project shall be
consistent with the existing construction type or the allowable construction
type, whichever is less restrictive. (Plan review - Building, Fire. Inspection
-Building)
(d) The
following products and practices shall not be used:
1. Carpet used for floor covering that fails
to meet the DOC FF-1 "Pill Test" (Consumer Product Safety Commission 16 CFR
1630); (Plan review - Building, Fire. Inspection - Building)
2. Electrical materials/supplies: Unlisted or
unapproved electrical products. As stated in the National Electric Code
(sections 90.7, 110.2, 110.3, and article 100), only electrical products
listed, labeled, approved, and identified are acceptable. Approval is to be
based on tests and listings of testing laboratories such as Underwriters
Laboratories Inc. (UL), Factory Mutual (FM) or Canadian Standards
Association/Nationally Recognized Testing Laboratory (CSA/NRTL), etc.;
(Electrical)
3. Plumbing materials
and supplies:
i. All purpose solvent
cement;
ii. Clear PB (polybutylene)
piping;
iii. Flexible traps and
tailpieces;
iv. Sheet and tubular
copper and brass trap and tailpiece fittings less than B&S (Brown &
Sharpe) 17 gauge (.045 inch); and
v. Solder having more than 0.2 percent lead
shall not be used in the repair of potable water systems (Plumbing);
and
4. Bars, grilles and
screens shall not be placed over emergency escape windows or doors in Groups R
or I-1 unless they are releasable or removable from the inside without the use
of a key, tool or force greater than that which is required for the normal
operation of the window or door. (Building)
5. The following practices shall not be used
on painted surfaces in all buildings of Group R that were constructed before
1978, Group E and Group I-4 buildings used as child-care facilities unless the
painted surface has been tested and found to be free of lead-based paint:
i. Open flame burning or the use of high
temperature (in excess of 1100 degrees Fahrenheit) heat guns;
ii. Power sanding or sandblasting, unless a
special HEPA (high efficiency particulate air) filter equipped vacuum
attachment is used to contain dust;
iii. Uncontained water blasting or power
washing; or
iv. Dry scraping or
sanding more than two square feet per room (interior) or 10 square feet or more
per building (exterior). (Building)
6. A mirror shall not be placed in or
adjacent to any means of egress so as to confuse the direction of egress or
give the appearance of a doorway, exit, or passageway. Draperies or similar
hangings shall not obscure an exit. (Plan review - Building, Fire. Inspection -
Building)
i. Exception: Within dwelling units
of Groups R-2, R-3, R-4 and R-5.
(e) The following products and practices
shall be required, when applicable:
1. When
any water closet is replaced, the replacement water closet shall require not
more than 1.6 gallons of water per flush as required by the plumbing subcode.
(Plumbing)
2. In buildings required
by Chapter 11 of the building subcode to be accessible, when bathrooms or
toilet rooms are altered, the following requirements for providing
accessibility shall apply unless the requirements of Chapter 11 of the building
subcode have been met:
i. When toilet
partitions are moved or installed, but existing fixtures are not being moved,
an accessible stall complying with ICC A117.1, Section 604.9, shall be created
provided that this can be accomplished without moving fixtures.
(Building)
ii. When bathroom
fixtures or hardware are replaced, the replacement fixtures or hardware shall
comply with ICC A117.1, Sections 603 through 608, as applicable, for
nonresidential buildings or ICC A117.1, Chapter 11, for residential buildings
required by Chapter 11 of the building subcode to be accessible.
(Plumbing)
iii. Where full
compliance is technically infeasible, a single fixture unisex accessible
bathroom shall be permitted. This may be accomplished by providing two unisex
bathrooms, one of which is accessible. (Building)
iv. Where it is technically infeasible to
gain compliance with the altered bathroom, signage to the closest accessible
bathroom (if any) shall be provided at the altered bathroom.
(Building)
3. In
buildings required by Chapter 11 of the building subcode to be accessible, when
space is reconfigured, the reconstructed space shall comply with Chapter 11 of
the building subcode.
i. Where full compliance
is technically infeasible, compliance shall be achieved to the maximum extent
feasible. (Building)
4.
Replacement or new doors shall comply with the following: (Building)
i. In buildings required by Chapter 11 of the
building subcode to be accessible, when new door openings are created, existing
door openings are enlarged or door assemblies are replaced and the required
door width can be achieved within the existing opening, the new door shall
comply with ICC A117.1, Section 404.
(1) If
the door being added, enlarged, or replaced is a building entrance and at least
60 percent of the entrance doors are accessible, then the door being added,
enlarged, or replaced is not required to comply with ICC A117.1, Section
404.
ii. When bathroom
fixtures or hardware are replaced, the replacement fixtures or hardware shall
comply with ICC/ANSI A117.1, Sections 603 through 608, as applicable, for
nonresidential buildings or ICC/ANSI A117.1, Chapter 10 for residential
buildings required by Chapter 11 of the building subcode to be accessible.
(Plumbing)
5. In
buildings required by Chapter 11 of the building subcode to be accessible, when
entrance steps are being replaced, a ramp shall be installed, provided that the
installation of a ramp does not add more than 20 percent to the cost of
replacing the steps. (Building)
i. If at
least 60 percent of the other building entrances are accessible, then the
installation of a ramp shall not be required.
6. When providing vertical access is part of
the scope of work, a limited use limited application elevator or platform lift
may be installed as permitted Chapter 11 of the building subcode.
(Building)
7. Replacement glass
shall comply with the "Safety Glazing" requirements of the building subcode and
shall be installed in the "Hazardous Locations" as specified by Sections 2406.4
and 2406.5 of the building subcode or by Section R308.4 of the one- and
two-family dwelling subcode, as applicable. (Building)
8. Where a fireproofing material is removed
that is integral to the rating of an existing fire-rated assembly, the material
shall be replaced so that the rating is preserved. (Building)
9. Plug fuses of the Edison-base type shall
be used only for replacements where there is no evidence of over fusing or
tampering per Section 240.51 (B) of the electrical subcode.
(Electrical)
10. Any replacement to
the electrical service equipment shall require that the grounding electrode
system be updated to the requirements of Article 250 Part III of the electrical
subcode. (Electrical)
11.
Non-"hospital grade" receptacles in patient bed locations of health care
facilities, Group I-2, shall be replaced with "hospital grade" receptacles.
(Electrical)
12. In buildings of
Groups R-1 and R-2, when habitable space is created in previously unoccupied
space, the minimum clear ceiling height shall be seven feet. For rooms with a
sloped ceiling, the minimum clear ceiling height shall be seven feet for at
least 35 square feet of the floor area of the room. Any portion of the room
measuring less than five feet from the finished floor to the finished ceiling
shall not be considered usable floor area. (Building)
13. When a new refrigerant is introduced, the
requirements of the mechanical subcode applicable to that refrigerant, if any,
shall be met. This shall apply to the installation of new equipment, the
replacement of existing equipment with equipment using a different refrigerant,
or the replacement of the refrigerant in existing equipment with a different
refrigerant. (Plumbing)
14. When
the work being performed creates or exposes wood framing of any wall, floor,
ceiling, or roof, fireblocking shall be provided as required by Section 718.2
of the building subcode or Section R302.11 of the one- and two-family dwelling
subcode, as applicable. The fireblocking material shall comply with Section
718.2.1 of the building subcode or Section R302.11.1 of the one- and two-family
dwelling subcode, as applicable.
15. When the work being performed creates or
exposes the roof decking/sheathing or the framing of any wall, floor, ceiling,
or roof assembly that is part of the building thermal envelope (encloses
conditioned space), any accessible voids in insulation shall be filled using
insulation meeting the R-values of Table R402.1.3 (N1102.1.3) of the
residential energy code for wood framing and of Table R402.2.6 (N1102.2.6) of
the residential energy code for metal framing equivalents or of Table 5.5-4 or
5.5-5 of the commercial energy code, as applicable.
i. In the event that insulation meeting the
R-values above cannot be installed due to space constraints, and the
equivalency exceptions of Sections R402.2.1 and R402.2.2 (N1102.2.1 and
N1102.2.2) cannot be applied for residential buildings, insulation that fills
the cavities of the framed assembly shall be installed.
16. When fenestration (windows, skylights, or
doors) is newly installed or replaced, the U-factor (thermal transmittance)
shall not exceed the U-factor of Table R402.1.2 (N1102.1.2) of the residential
energy code or of Table 5.5-4 or 5.5-5 of the commercial energy code, as
applicable.
i. Exception: In residential
buildings, fenestration that meets Sections R402.3.3 (N1102.3.3) and R402.3.4
(N1102.3.4), as applicable.
17. Ducts that are newly installed or
replaced shall be installed with insulation meeting the R-values of Section
R403.3.1 (N1103.3.1) of the residential energy code or of Section 6.4.4.1.2 of
the commercial energy code, as applicable.
18. The total replacement of a building
lighting system or a newly installed building lighting system shall meet
Section R404 (N1104) of the residential energy code or Section 9.1.2 of the
commercial energy code, as applicable. (A "lighting system" is defined by the
commercial energy code as "a group of luminaires circuited or controlled to
perform a specific function.")
i. Exception:
The total replacement of a lighting system within a room, space or tenancy
shall be required to meet Section 9.1.2 for the room, space or tenancy
only.
19. When the work
being performed results in an indoor or outdoor gas meter, related regulator or
piping becoming subject to vehicle impact, which work includes, but is not
limited to, new installation, relocation or other construction, the gas meter,
related regulator or piping shall be protected by barriers meeting the
requirements of Section 312 of the International Fire Code. For the purpose of
applying this provision, "subject to vehicle impact" shall mean located within
three feet of any garage door opening, driveway or designated parking area and
not separated by a building wall from the space where a vehicle may be
operated. (Plumbing) i. Exception: If verification of the installation of an
excess flow valve is provided by the gas utility, vehicle impact barriers shall
not be required.
20. Where work,
other than ordinary maintenance or minor work, is being performed on an
elevator, the elevator shall be equipped to operate with a standardized fire
service key. (Fire)
21. The work
shall not cause an exit enclosure to be used for any purpose other than means
of egress, except those penetrations permitted by Section 1023.5 of the
building subcode.
22. Existing
openings that become part of an exit or exit access and newly created openings
to be used as an exit or exit access shall meet Section 1008.3 and Section 1013
of the building subcode when more than one exit or exit access is required.
This shall apply only to the portion of the building served by the new exit or
exit access.
(f) In
buildings containing a fuel burning appliance or having an attached garage,
carbon monoxide detection equipment shall be installed in accordance with
Section 915 of the building subcode or Section R315 of the one- and two-family
dwelling subcode, as applicable. (Fire)
1.
Exception: Battery-powered or plug-in devices shall be accepted for purposes of
meeting the requirements of this section.
(g) All materials and methods used shall
comply with the requirements specified in
N.J.A.C.
5:23-6.8, Materials and methods.
1. For repair work undertaken as part of a
reconstruction project, materials like those existing may be used. There is no
limit to the amount of repair work which may be undertaken.
2. Exception: Windows may be replaced with
windows like those existing without meeting the size requirements of the
building subcode.
i. In sleeping rooms below
the fourth story in occupancies of Groups R or I-1, where new window openings
are being created or the size of window openings is being changed, at least one
window shall:
(1) Be operable;
(2) Have a sill height of not more than 44
inches;
(3) Have a width of at
least 20 inches, a height of at least 24 inches and a minimum total area of 5.7
square feet measured from head to sill and from side to side.
(4) New window openings in sleeping rooms
shall not be required to meet these requirements in buildings where the
sleeping room is provided with a door to a corridor having access to two remote
exits or in buildings equipped throughout with an automatic sprinkler
system.
ii. Basement
windows in buildings of Group R-2 shall comply with the requirements of
N.J.A.C.
5:23-6.26(b)3 where the
window serves as the second means of egress from the dwelling unit. (Plan
review - Building, Fire. Inspection - Building)
3. Newly installed and replacement handrails
and guardrails shall comply with Sections 1011.11, 1012.8, 1014, and 1015 of
the building subcode, respectively, or Sections R311.7.8, R311.8.3, and R312.1
of the one- and two-family dwelling subcode, respectively, as applicable. Where
50 percent or more of a handrail or guardrail on a flight or on a level is
replaced, then this shall be considered a complete replacement and shall comply
with the above referenced sections. The repair or replacement of less than 50
percent of a handrail or guardrail shall be permitted to match the existing
handrail or guardrail. (Building)
(i) The basic
requirements of this subchapter for the applicable group shall be met within
the work area(s). Attendant work outside the work area(s) shall not make the
building less conforming with the basic requirements than it was when the
reconstruction was undertaken.
1. Where the
building currently exceeds the basic requirements, the extent to which it
exceeds shall not be reduced unless the building also exceeds the requirements
of the corresponding subcode of the UCC. In this case, the extent of compliance
with the basic requirements may be reduced, but not below the requirements of
the corresponding subcode of the UCC. Existing fire alarm, automatic sprinkler
and standpipe systems shall not be removed without replacement and shall be
maintained in operating condition.
(k) In a building
required by Chapter 11 of the building subcode to be accessible, where the
space reconstructed is a primary function space, an accessible path of travel
to the space shall be provided up to the point at which the cost of providing
accessibility is disproportionate to the cost of the overall project; a cost is
disproportionate if it exceeds 20 percent of the cost of the work. (Building)
1. The accessible path of travel shall
include, but not be limited to, an accessible parking space, an accessible
exterior route, an accessible building entrance, an accessible interior route
to the reconstructed area, accessible restrooms, accessible drinking fountains,
and accessible telephones serving the reconstructed primary function space.
Priority shall be given to providing an accessible entrance or accessible
restrooms where possible.
2. In
determining disproportionate cost, the following materials may be deducted from
the overall cost of the project:
i. Windows,
hardware, operating controls, electrical outlets and signage;
ii. Mechanical systems, electrical systems,
installations or alterations of fire protection systems or abatement of
hazardous materials; or
iii. The
repair or installation of roofing, siding, or other exterior wall
facade.
3. Where the work
consists solely of the reconstruction of materials or systems listed in (k)2
above, the path of travel requirements shall not apply.
4. Where the work is for the primary purpose
of increasing the accessibility of the building or tenancy, the requirement to
further improve the path of travel shall not apply.
5. Where it is technically infeasible to
comply with the technical standards of ICC A117.1, the work must comply to the
maximum extent feasible.
(l) When work is performed in a Class 1
structure or when work is performed on a smoke control system, a list of all
materials and work requiring special inspections, and a list of agencies,
qualified licensed professionals or firms intended to be retained for
conducting those inspections in accordance with the requirements of the
building subcode shall be submitted as part of the permit application.
(Building, except smoke control systems - Fire)