Current through Register Vol. 56, No. 18, September 16, 2024
(a) Renovations, as defined in
N.J.A.C. 5:23-6.3,
shall comply with the requirements of this section.
(b) All work shall be done in a workmanlike
manner.
(c) The work shall not
cause any diminution of existing structural strength, system capacity or
mechanical ventilation below that which exists at the time of application for a
permit or that which is required by the applicable subcodes of the Uniform
Construction Code, whichever is lower. The replacement of fixtures, equipment
or appliances shall not increase loads on these systems unless the system is
upgraded in accordance with the applicable subcode of the UCC to accommodate
the increased load.
1. Newly introduced fixed
loads shall not exceed the uniformly distributed live loads or concentrated
live load criteria of Table 1607.1 of the building subcode or Table R301.5 of
the one- and two-family dwelling subcode, as applicable, and shall not create
deflection that exceeds the standards set forth below. As used in this section,
fixed loads shall mean uniform or concentrated loads and shall include, but not
be limited to, equipment, files, library stacks, or similar loading conditions.
(Building)
i. For wood frame construction,
deflection shall not exceed L/180 for roofs with a slope of 3 in 12 or less or
L/120 for roofs with a slope of greater than 3 in 12 and for floors.
ii. For steel frame construction, deflection
shall not exceed L/240 for roofs with a slope of 3 in 12 or less or L/180 for
roofs with a slope of greater than 3 in 12 and for floors.
iii. For concrete construction, deflection
shall not exceed L/180 for roofs or L/240 for floors.
2. Fire protection systems may be removed if
the requirements of
N.J.A.C. 5:23-6.6(c)2
or 6.7(c)2 are met, as applicable.
(Fire)
3. No work shall be
undertaken that diminishes accessibility below that which is required by
Chapter 11 of the building subcode. (Building)
(d) The following products and practices
shall not be used:
1. Wood paneling being
used as an interior finish not in conformance with Table 2 of
N.J.A.C.
5:23-6.11 of this subcode;
(Building)
2. Carpet used for floor
covering that fails to meet the DOC FF-1 "Pill Test" (Consumer Product Safety
Commission 16 CFR 1630); (Building)
3. Electrical materials/supplies: Unlisted or
unapproved electrical products. As stated in the National Electrical Code
(sections 90.7, 110.2, 110.3, and article 100), only electrical products
listed, labeled, approved, and identified are acceptable. Approval is to be
based on tests and listings of testing laboratories such as Underwriters
Laboratories, Inc. (UL), Factory Mutual (FM) or Canadian Standards
Association/Nationally Recognized Testing Laboratory (CSA/NRTL), etc.; and
(Electrical)
4. Plumbing materials
and supplies:
i. All purpose solvent
cement;
ii. Clear PB (polybutylene)
piping;
iii. Flexible traps and
tailpieces;
iv. Sheet and tubular
copper and brass trap and tailpiece fittings less than B&S (Brown &
Sharpe) 17 gauge (.045 inch); and
v. Solder having more than 0.2 percent lead
shall not be used in the repair of potable water systems. (Plumbing)
5. Bars, grilles and screens shall
not be placed over emergency escape windows or doors in Groups R or I-1 unless
they are releasable or removable from the inside without the use of a key, tool
or force greater than that which is required for the normal operation of the
window or door. (Building)
6. The
following practices shall not be used on painted surfaces in all buildings of
Group R that were constructed before 1978, Group E and Group I-4 buildings used
as child-care facilities unless the painted surface has been tested and found
to be free of lead-based paint:
i. Open flame
burning or the use of high temperature (in excess of 1100 degrees Fahrenheit)
heat guns;
ii. Power sanding or
sandblasting, unless a special HEPA (high efficiency particulate air) filter
equipped vacuum attachment is used to contain dust;
iii. Uncontained water blasting or power
washing; or
iv. Dry scraping or
sanding more than two square feet per room (interior) or 10 square feet or more
per building (exterior). (Building)
7. A mirror shall not be placed in or
adjacent to any means of egress so as to confuse the direction of egress or
give the appearance of a doorway exit, or passageway. Draperies or similar
hangings shall not obscure an exit.
i.
Exception: Within dwelling units of Groups R-2, R-3, R-4, and R-5. (Plan review
- Building, Fire. Inspection - Building)
(e) The following products and practices
shall be required, when applicable:
1. When
any water closet is replaced, the replacement water closet shall require not
more than 1.6 gallons of water per flush as required by the plumbing subcode.
(Plumbing)
2. In buildings required
by Chapter 11 of the building subcode to be accessible, when bathrooms or
toilet rooms are renovated, the following requirements for providing
accessibility shall apply unless the requirements of Chapter 11 of the building
subcode have been met:
i. When toilet
partitions are moved or installed, but existing fixtures are not being moved,
an accessible stall complying with ICC A117.1, Section 604.9 shall be created
provided that this can be accomplished without moving fixtures.
(Building)
ii. When bathroom
fixtures or hardware are replaced, the replacement fixtures or hardware shall
comply with ICC A117.1, Sections 603 through 608, as applicable, for
nonresidential buildings or ICC A117.1, Chapter 10, for residential buildings
required by Chapter 11 of the building subcode to be accessible.
(Plumbing)
iii. Where full
compliance is technically infeasible, compliance shall be achieved to the
maximum extent feasible. (Building)
3. Replacement doors shall comply with the
following: (Building)
i. When replacement
doors are installed in buildings required by Chapter 11 of the building subcode
to be accessible, replacement hardware shall comply with ICC A117.1, Section
404.2.6.
ii. Replacement dwelling
unit, guest room or rooming unit corridor doors in Groups I-1, R-1 or R-2 shall
be 13/4 inch solid core wood or approved equal with approved door closers and
shall not have any glass panels, other than approved wire glass in metal
frames.
(1) 13/8 inch solid core replacement
doors shall be accepted if the existing frame is not being replaced and will
accommodate only a 13/8 inch door.
4. Replacement glass shall comply with the
"Safety Glazing" requirements of the building subcode and shall be installed in
the "Hazardous Locations" as specified by Sections 2406.4 and 2406.5 of the
building subcode or by Section R308.4 of the one- and two-family dwelling
subcode, as applicable. (Building)
5. Where a fireproofing material is removed
that is integral to the rating of an existing fire-rated assembly, the material
shall be replaced so that the rating is preserved. (Building)
6. Plug fuses of the Edison-base type shall
be used only for replacements where there is no evidence of over fusing or
tampering per Section 240.51(B) of the electrical subcode.
(Electrical)
7. Any replacement to
the electrical service equipment shall require that the grounding electrode
system be updated to the requirements of Article 250 Part III of the electrical
subcode. (Electrical)
8.
Non-"hospital grade" receptacles in patient bed locations of health care
facilities, Group I-2, shall be replaced with "hospital grade" receptacles.
(Electrical)
9. When a new
refrigerant is introduced, the requirements of the mechanical subcode
applicable to that refrigerant, if any, shall be met. This shall apply to the
replacement of existing equipment with equipment using a different refrigerant
or the replacement of the refrigerant in existing equipment with a different
refrigerant. (Plumbing)
10. When
the work being performed exposes wood framing of any wall, floor, ceiling, or
roof, fireblocking shall be provided as required by section 718.2 of the
building subcode or section R302.11 of the one- and two-family dwelling
subcode, as applicable. The fireblocking material shall comply with section
718.2.1 of the building subcode or section R302.11.1 of the one- and two-family
dwelling subcode, as applicable.
11. When the work being performed creates or
exposes the roof decking/sheathing or the framing of any wall, floor, ceiling,
or roof assembly that is part of the building thermal envelope (encloses
conditioned space), any accessible voids in insulation shall be filled using
insulation meeting the R-values of Table R402.1.3 (N1102.1.3) of the
residential energy code for wood framing and of Table R402.2.6 (N1102.2.6) of
the residential energy code for metal framing equivalents or of Table 5.5-4 or
5.5-5 of the commercial energy code, as applicable.
i. In the event that insulation meeting the
R-values above cannot be installed due to space constraints, and the
equivalency exceptions of Sections R402.2.1 and R402.2.2 (N1102.2.1 and
N1102.2.2) cannot be applied for residential buildings, insulation that fills
the cavities of the framed assembly shall be installed.
12. When fenestration (windows, skylights or
doors) is newly installed or replaced, the U-factor (thermal transmittance)
shall not exceed the U-factor of Table R402.1.2 (N1102.1.2) of the residential
energy code or of Table 5.5-4 or 5.5-5 of the commercial energy code, as
applicable.
i. Exception: In residential
buildings, fenestration that meets Sections R402.3.3 (N1102.3.3) and R402.3.4
(N1102.3.4), as applicable.
13. Ducts that are newly installed or
replaced shall be installed with insulation meeting the R-values of Section
R403.3.1 (N1103.3.1) of the residential energy code or of Section 6.4.4.1.2 of
the commercial energy code, as applicable.
14. The total replacement of a building
lighting system or a newly installed building lighting system shall meet
Section R404 (N1104) of the residential energy code or Section 9.1.2 of the
commercial energy code, as applicable. (A "lighting system" is defined by the
commercial energy code as "a group of luminaires circuited or controlled to
perform a specific function.")
i. Exception:
The total replacement of a lighting system within a room, space or tenancy
shall be required to meet Section 9.1.2 for the room, space, or tenancy
only.
15. Where work,
other than ordinary maintenance or minor work, is being performed on an
elevator, the elevator shall be equipped to operate with a standardized fire
service key. (Fire)
(f)
In buildings of Groups R-3, R-4, and R-5 and in dwelling units of Group R- 2,
smoke alarms shall be installed and maintained on each level of the structure,
outside each separate sleeping area in the immediate vicinity of the bedrooms,
and located on or near the ceiling. Battery-operated units shall be permitted,
but shall not replace any AC-powered smoke alarms or a household fire alarm
system. (Fire)
(g) In buildings
containing a fuel burning appliance or having an attached garage, carbon
monoxide detection equipment shall be installed in accordance with Section 915
of the building subcode or Section R315 of the one- and two-family dwelling
subcode, as applicable. (Fire)
1. Exception:
Battery-powered or plug-in devices shall be accepted for purposes of meeting
the requirements of this section.
(h) All materials and methods used shall
comply with the requirements specified in
N.J.A.C.
5:23-6.8, Materials and methods.
1. Exception: Windows may be replaced with
windows like those existing without meeting the size requirements of the
building subcode.
i. In sleeping rooms below
the fourth story in occupancies of Groups R or I-1, where the size of window
openings is being changed, at least one window shall:
(1) Be operable;
(2) Have a sill height of not more than 44
inches;
(3) Have a width of at
least 20 inches, a height of at least 24 inches and a minimum of total area of
5.7 square feet measured from head to sill and from side to side.
(4) New window openings in sleeping rooms
shall not be required to meet these requirements in buildings where the
sleeping room is provided with a door to a corridor having access to two remote
exits or in buildings equipped throughout with an automatic sprinkler
system.
ii. Basement
windows in buildings of Group R-2 shall comply with the requirements of
N.J.A.C.
5:23-6.26(b)3 where the
window serves as the second means of egress from the dwelling unit. (Plan
review - Building, Fire. Inspection - Building)
2. Newly installed and replacement handrails
and guardrails shall comply with Sections 1011.11, 1012.8, 1014, and 1015 of
the building subcode, respectively, or Sections R311.7.8, R311.8.3, and R312.1
of the one- and two-family dwelling subcode, respectively, as applicable. Where
50 percent or more of a handrail or guardrail on a flight or on a level is
replaced, then this shall be considered a complete replacement and shall comply
with the above referenced sections. The repair or replacement of less than 50
percent of a handrail or guardrail shall be permitted to match the existing
handrail or guardrail.