Current through Register Vol. 56, No. 18, September 16, 2024
(a) General: The following are of general
applicability to changes of use:
1. When the
use of a building is changed, then the building must be brought into compliance
with the requirements of this section. Each of the lettered subsections of this
section establishes a specific type of requirement. This section establishes
requirements for compliance with the basic requirements of this subcode, for
means of egress, for enclosure of vertical openings, for height and area
limitation, for exterior wall fire resistance, for automatic sprinkler systems,
for fire alarm systems, for fire detection systems, for structural soundness,
for plumbing, electrical, and mechanical systems, and for accessibility.
i. Limit on new buildings undergoing a change
of use: Buildings that have been occupied for their originally intended use for
less than one year shall be required to comply with the requirements of the
Uniform Construction Code for new construction for the proposed use.
2. The subsections governing
compliance with the basic requirements, means of egress, height and area
limitations, exterior wall fire resistance, and automatic sprinkler systems
incorporate Relative Group Hazard Index Tables. Compliance with the
requirements of the subsection is required when the change of use will increase
the relative hazard. Each of the subsections should be applied separately to
the proposed new use.
3. This
section may require an owner to undertake work in order to be permitted to
change the use of a building or a portion of a building. Additionally, the
owner of a building may wish to undertake other work not required by the
section. That work must comply with the requirements for repair, renovation,
alteration, and/or reconstruction applicable to the new group in accordance
with the provisions of this subcode.
4. Fire protection system removal: Any fire
protection system providing partial or redundant protection originally
installed to protect a special hazard that no longer exists and that is not
required in accordance with the current Uniform Construction Code, is allowed
to be removed with the written approval of the fire subcode official and fire
official. All disconnected equipment and devices, such as pull stations,
nozzles, detectors, sprinklers, sensors, panels, and hose connections, shall be
removed so as not to give a false indication that the structure, area, or space
is protected. (Fire)
5. Where the
character of use of an existing building or portion thereof is changed to one
of the following special use or occupancy categories, the building or portion
shall comply with the referenced section of the building subcode specific to
the special use or occupancy regardless of whether a change of use group is
involved.
i. Covered Mall and Open Mall
Buildings--Section 402;
ii.
Atriums--Sections 404;
iii.
Underground Buildings--Section 405;
iv. Motor-Vehicle-Related Occupancies --
Section 406;
v. Motion Picture
Projection Rooms--Section 409;
vi.
Stages, Platforms, and Technical Production Areas --Section 410;
vii. Special Amusement Areas--Section 411:
(1) A variation shall not be granted for the
flame spread and smoke development ratings of interior finish and trim
requirements of Section 411.
(2)
For the use of a building as a special amusement building, where a variation
request has been submitted, the Construction Official shall consult with the
Fire Official as required by
5:23-6.2(i).
viii. Aircraft-Related
Occupancies--Section 412;
ix.
Hazardous Materials--Section 414;
x. Spray Application of Flammable
Finishes--Section 416;
xi. Drying
Rooms--Section 417;
xii. Organic
Coatings--Section 418;
xiii.
Hydrogen Fuel Gas Rooms--Section 421;
xiv. Ambulatory Health Care
Facilities-Section 422;
xv.
Hyperbaric Facilities - Section 425;
xvi. Combustible Dusts, Grain Processing and
Storage - Section 426;
xvii.
Medical Gas Systems--Section 427; and
xviii. Higher Education Laboratories--Section
428.
xix. Live/Work Units--Section
508.5.
6. Any automatic
sprinkler system or fire detection and/or alarm requirements applicable to the
special use or occupancy shall be applied throughout the entire building unless
the special use or occupancy is separated from the remainder of the building by
fire separation assemblies having a rating of at least two hours.
(Fire)
7. Group overnight stays: If
any non-residential occupancy, other than Group F, H or S, accommodates seven
or more non-consecutive group overnight stays within a calendar year for
persons over 2 1/2 years of age, and the activities involve planned periods of
sleep, the building is considered to have undergone a change of use. In such a
case, it shall be necessary to apply for and be issued a Certificate of
Occupancy. This shall be a dual Certificate of Occupancy to allow Group R-1 in
addition to the existing use of a building. Any facility that accommodates six
or fewer overnight stays within a calendar year shall obtain a permit under the
Uniform Fire Code, N.J.A.C. 5:70. Group overnight stays in Groups F, H and S
shall be prohibited.
8. Where an
existing single-family dwelling is converted into a two-family dwelling, the
following shall apply:
i. Smoke alarms shall
be installed and maintained within each dwelling unit as required by Section
907.2.11.2 of the building subcode or Section R314 of the one- and two-family
dwelling subcode, as applicable.
ii. Fire separation between dwelling units.
(1) One-hour dwelling unit separation;
or
(2) Two layers of 5/8-inch thick
type X gypsum wallboard. The base layer shall be applied at right angles to the
joists with 1 1/4-inch minimum drywall screws or nails at 24 inches on center.
The face layer shall be applied at right angles to the joists with 1-7/8-inch
minimum drywall screws or nails at 12 inches on center. The face layer joints
shall be offset from the base layer joints by a minimum of one joist bay. The
joints of the face layer shall be taped and provided with a minimum of one
layer of spackle. (Plan review--Building, Fire. Inspection--Building)
(b)
Compliance with Basic Requirements: Compliance with the basic requirements
shall be required as follows:
TABLE B
Relative Group Hazard
1 (highest) |
H-1, H-2, H-3 |
2 |
A-1, A-2 Nightclubs, H-4, H-5, F-1, I-3, M, S-1 |
3 |
A-2 Other than Nightclubs, A-3, A-4, A-5, B, F-2, I-2,
I-4, R-1, S-2 |
4 |
A-3 Places of Worship, E, I-1, R-2, and R-4 buildings
more than two stories in height or more than four dwelling units |
5 (lowest) |
R-2 and R-4 buildings two stories or fewer in height and
four dwelling units or less, R-3, R-5, U |
1. When the use
of a building is changed to a higher relative use group hazard as shown in
Table B above, the building shall comply with the basic requirements of
N.J.A.C.
5:23-6.10 through 6.30 applied throughout the
building for the new group unless otherwise provided. Where another lettered
subsection of this section establishes a requirement that differs from the
basic requirement, the requirement contained in that other lettered subsection
shall govern.
i. Where a portion of a
building is changed to a higher relative group hazard, the building shall
comply with the basic requirements of
N.J.A.C.
5:23-6.10 through 6.30 for an automatic
sprinkler system and fire detection and/or alarms applied throughout the
building for the new group unless the proposed use is separated from the
existing use(s) by a fire barrier or horizontal assembly, or both, having a
fire resistance rating in accordance with Table 707.3.10 of the building
subcode in which case only the portion changed shall comply; mixed occupancies
shall use the highest applicable rating from Table 707.3.10. The portion of the
building changed shall comply with all the other basic requirements of
N.J.A.C.
5:23-6.10 through 6.30 for the new
group.
2. When a change
of use is made to an equal or lesser relative group hazard as shown in Table B
above, the existing building is not required to comply with the basic
requirements except:
i. Where required in
connection with alteration or reconstruction work by the sections of this
subcode applicable to alteration or reconstruction work; or
ii. Where the proposed use is subject to and
not in compliance with the applicable requirements of N.J.A.C.
5:70-4.
(c)
Means of Egress: The following requirements apply to means of egress in a
change of use:
TABLE C
Hazard Categories and Classifications
Means of Egress
Relative Hazard | Use Classifications |
1 (highest) | H-1, H-2, H-3, A-2
Nightclubs |
2 | I-2, I-3, I-4 |
3 | A (other than A-2 nightclubs), E, I-1, M,
R-1, R-2, R-4 |
4 | B, F-1, R-3, R-5, S-1, H-4, H-5 |
5 (lowest) | F-2, S-2, U |
1. For any
change of use, except a change of use to Group A-2 Nightclubs, the occupant
load of the space shall be calculated based on the capacity of the exits as per
N.J.A.C.
5:23-6.11(b). The occupant
load shall not exceed one occupant per five square feet floor area unless the
building complies with chapter 10 of the building subcode in its entirety.
i. For Group A-2 Nightclubs, the occupant
load shall be calculated using section 1029.2 of the building subcode, except
the maximum occupant load shall not exceed one occupant per five square feet of
occupiable floor space.
ii. Where a
portion of a building undergoes a change of use, the determination of the
capacity of the exit(s) serving that portion shall include all spaces served by
those exit(s).
2. When a
change in use is made to a higher hazard category as shown in Table C above,
the entire building or portion thereof shall comply with the following
requirements of the building subcode or of this subcode as specified below.
i. Sections 1006 (Number of Exits and Exit
Access Doorways) and 1007 (Exit and Exit Access Doorway Configuration).
(1) Exception: The occupant load of the space
may be restricted in order to comply with the requirements of these
sections;
(2) Exception: A single
exit shall be permitted in a change of use to a Group R-2 or R-4 where the
conditions of
N.J.A.C.
5:23-6.26(b) for a single
exit are met;
ii. Section
1008 (Means of Egress Illumination);
iii. Section 1010 (Doors, Gates and
Turnstiles) except section 1010.1.1 (Size of doors). Apply the Basic
Requirements (6.10 through 6.30) for door widths;
iv. Sections 1011.7.2 (Outdoor conditions),
1011.7.3 (Enclosures under interior stairways), 1011.12 (Stairway to roof), and
the Basic Requirements (6.10 through 6.30) for stair widths;
vi. Section 1013.1 (Exit signs - where
required) and Section 1013.3 (Illumination);
vii. Section 1016.2 (Egress through
intervening spaces);
viii. Section
1017 (Exit Access Travel Distance);
ix. Section 1018 (Aisles);
x. Sections 1020.2 (Corridor construction),
1020.4 (Corridor obstruction), 1020.6 (Air movement in corridors), 1020.7
(Corridor continuity), and the Basic Requirements (6.10 through 6.30) for
corridor widths.
(1) Existing lath and plaster
in good condition or existing 1/2-inch thick gypsum wallboard on both sides of
the wall shall be accepted where a one-hour fire separation assembly is
required by Table 1020.2 (Corridor Fire-Resistance Rating);
xi. Section 1025 (Luminous Egress
Path Markings);
xii. Section 1026
(Horizontal Exits);
xiii. Section
1028 (Exit Discharge) and Section 1029 (Egress Courts); and
xiv. Section 1030 (Assembly).
3. When a change of use is made to
an equal or lesser hazard category as shown in Table C above, the existing
building is not required to comply with the requirements contained in (c)2
above except in areas where reconstruction work being performed in connection
with the change of use triggers these requirements.
4. Vertical opening protection shall be
provided for all stairs in accordance with
5:23-6.10
through 6.30 when a change of use that also constitutes a change of group is
made and the proposed group is a higher hazard category as shown in Table C
above.
i. Where the group of a portion of a
building is changed to a higher hazard category, vertical opening protection
shall be provided for all stairs serving the proposed group from the floor(s)
on which the proposed group is located to the level of exit
discharge.
5.
Notwithstanding the relative hazard as determined by Table C above, where any
change of use occurs to a story with one exit, the story shall meet the
requirements at Section 1006.3.4 (single exits) of the building subcode for the
proposed use.
i. Exception: A single exit
shall be permitted in a change of use to a Group R-2 or R-4 where the
conditions of
N.J.A.C.
5:23-6.26(b) for a single
exit are met.
6. When a
change of use is made to any residential group (R-1, R-2, R-3, R-4 or R-5) or
to Group I-1, every sleeping room below the fourth story shall have at least
one operable window or exterior door. Where windows are provided to comply with
this requirement, the window shall have a sill height of not more than 44
inches, and have a width of at least 20 inches, a height of at least 24 inches
and a minimum total area of 5.7 square feet measured from head to sill and from
side to side.
i. An outside window or
exterior door is not required in buildings where the sleeping room is provided
with a door to a corridor having access to two remote exits.
ii. An outside window or exterior door is not
required in buildings equipped throughout with an automatic sprinkler
system.
iii. In a building that
originally was in Group R-3 or R-5 and is returning to Group R-3 or R-5, the
windows shall be permitted to remain as they were during the time when the
building previously was in use as a residence. (Plan review--Building, Fire.
Inspection--Building)
7.
Notwithstanding the relative hazard as determined by Table B or C above, where
any change in use occurs to a Group A or Group E with an occupant load of 50 or
more, approved panic hardware shall be installed in accordance with Section
1010.2.9 (panic and fire exit hardware) of the building subcode.
8. Notwithstanding the relative hazard as
determined by Table B or C above, a single exit shall not be permitted when a
building is to be used as a child care center. (Plan review--Building, Fire.
Inspection--Building)
(d)
Enclosure of vertical openings:
1. For any
change of use that also constitutes a change in group, vertical openings other
than stairs shall be protected as required by
5:23-6.10
through 6.30 for the proposed use within each space undergoing a change of
use.
2. Stairs shall be enclosed in
accordance with
5:23-6.10
through 6.30 for the proposed use when a change of use that also constitutes a
change of group is made and the proposed group is a higher hazard category as
shown in Table C above.
3. Atriums
in compliance with Section 404 of the building subcode are not required to be
enclosed. (Plan review--Building, Fire. Inspection--Building)
(e) Height and Area Limitations:
The following height and area limitations apply in a change of use.
TABLE E
Hazard Categories and Classifications
Height and Area
Relative Hazard |
Use Classification |
1 (highest) |
A-2 Nightclubs, H-1, H-2, I-2, I-3, I-4 |
2 |
A-1, A-2 Other than Nightclubs, A-3, A-4, E, F-1, H-3,
H-4, H-5, I-1, M, S-1 |
3 |
A-3 Places of Worship, B, R-1, R-2, R-4 |
4 (lowest) |
F-2, R-3, R-5, S-2, U |
1. When a change
of use is made to a higher hazard category as shown in Table E above, the
height and area of the building shall meet the limitations of Chapter 5 of the
building subcode for the proposed group.
i.
For the purpose of determining the construction type, the fire resistance
rating of the following structural elements shall be considered: exterior
loadbearing walls, interior loadbearing walls, columns, girders, trusses and
framing, floor construction, including beams, and roof construction, including
beams, trusses and framing, arches and roof decks.
2. When a change of use is made to an equal
or lesser hazard category as shown in Table E, the existing building may
continue to exceed the maximum allowable height and area permitted for new
buildings.
3. Where a change of use
is made in a mixed use building or a single use building is changed to a mixed
use building, and any of the proposed uses is a higher category as per Table E,
the building shall comply with one or any combination of the following:
i. Nonseparated groups: The maximum allowable
height and area shall be determined by applying the more restrictive of the
height and area limitations of each group, as per Tables 504.3, 504.4, and
506.2 of the building subcode, to the entire building.
(1) Occupancies of Group H shall not be
permitted to be unseparated when located in the same building as Groups A, E,
I, M, R, or non-accessory Group B.
(2) Accessory occupancies in compliance with
Section 508.2 of the building subcode are not required to comply with this
requirement.
(3) When a change of
use is made such that any nonresidential use is located below or attached to a
residential use, a one-hour fire separation shall be provided between the
groups. The exits from the residential floors shall be separately enclosed.
ii. Separated groups:
Each portion of the building containing a group shall be completely separated
from adjacent groups by a fire barrier or horizontal assembly, or both, having
a fire resistance rating in accordance with Table 707.3.10 of the building
subcode; mixed occupancies shall use the highest applicable rating from Table
707.3.10. For buildings equipped throughout with an automatic sprinkler system,
the required fire resistance rating for groups other than H is permitted to be
reduced by one hour but shall not be reduced to less than one hour. Each
portion of the building shall comply with the height limitation of Tables 504.3
and 504.4 of the building subcode for that group. In each story, the area shall
be such that the sum of the ratios of the floor area of each group divided by
the allowable area of Table 506.2 of the building subcode for each group shall
not exceed 1.0.
(1) Exception: Accessory
occupancies in compliance with Section 508.2 of the building subcode are not
required to comply with this requirement.
iii. Separate buildings: If each group is
separated from other groups by fire walls that meet the requirements of Table
601 of the building subcode, then each group shall be considered a separate
building. Each building shall comply with the height and area limitation of
Tables 504.3, 504.4, and 506.2 of the building subcode.
(1) Exception: Accessory occupancies in
compliance with Section 508.2 of the building subcode are not required to
comply with this requirement.
4. In an unlimited area building, when a
change of use is made to a higher hazard category as shown in Table E above,
the building or portion thereof is required to comply with Section 507 of the
building subcode for the proposed new use. (Plan review--Building, Fire
Inspection--Building)
(f)
Exterior Wall Fire Resistance Ratings and Maximum Area of Exterior Wall
Openings: The following exterior wall fire resistance ratings and maximum area
of exterior wall openings apply in changes of use:
TABLE F
Hazard Categories and Classifications
Exposure of Exterior Walls
Relative Hazard |
Use Classification |
1 (highest) |
H |
2 |
Buildings exceeding 12,000 sq ft of F-1, M or S-1 |
3 |
A, B, E, F-2, I, R-1, S-2 Buildings 12,000 sq ft or less
of F-1, M$=B,$=R or S-1 |
4 (lowest) |
R-2, R-3, R-4, R-5, U |
1. Exterior
Wall Protection: If the group of a building is changed to a higher hazard
classification in accordance with Table F, the requirements for exterior wall
fire resistance rating in the table below shall be met.
Requirements for Exterior Wall Fire
Resistance Rating Building Use Group<b> |
Fire Separation Distance | H-2 | F-1, H-3,
M, S-1 | A, B, E, F-2, S-2, H-4, H-5, I, R-1 |
0-5 feet | 4 | 3 | 2<a> |
Over 5-10 feet | 3 | 2 | 1 |
Over 10-15 feet | 2 | r1 | 0 |
Over 15-30 feet | r1 | -30 | 0 |
Over 30 feet | 30 | 30 | 0 |
Note a: Existing eight-inch hollow or
six-inch solid masonry walls shall be accepted as a two-hour rating in other
than Group H-2 or H-3. |
Note b: When the group of a building is
changed to H-1, the building shall be located in accordance with Section 415.3
of the building subcode. |
i. The
requirements for exterior wall fire resistance rating shall not apply to
exterior walls which face buildings on the same lot where the buildings are
such that, if combined into one structure, the resulting building would comply
with the height and area limitations of Tables 504.3, 504.4, and 506.2 of the
building subcode.
ii. Where a
portion of a building is changed to a higher hazard classification, exterior
walls and openings of the entire building shall comply with the provisions of
this section. If the proposed use is separated from the rest of the building by
a fire barrier having a fire resistance rating in accordance with Table
707.3.10 of the building subcode, then only the portion changed must comply
with the provisions of this section; mixed occupancies shall use the highest
applicable rating from Table 707.3.10.
iii. When a change of use is made to an equal
or lesser hazard classification as shown in Table F, no change in the rating of
existing exterior walls is required.
iv. The fire resistance rating of
non-loadbearing exterior walls may be reduced by one hour in buildings equipped
throughout with an automatic sprinkler system. In a building equipped
throughout with an automatic sprinkler system installed in accordance with NFPA
13, the fire resistance rating of a non-loadbearing exterior wall may be
reduced by one hour with the following exceptions:
(1) Exception: Where the fire separation
distance is five feet or less, the fire resistance rating shall not be reduced
to less than one hour.
(2)
Exception: The rating of non-loadbearing exterior walls shall not be reduced in
buildings of Group H.
2. Exterior Wall Openings: If the group of a
building is changed to a higher hazard classification in accordance with Table
F, the requirements for exterior wall openings in the table below shall be met.
Group |
Exterior Wall Requirements |
H |
No opening permitted with a fire separation distance of
three feet or less. Protected openings required with a fire separation distance
of 20 feet or less. |
A-1, A-2 Nightclubs, A-2 Other than Nightclubs, A-3,
A-4, A-3 Places of Worship, B, E, F-1, I-1, I-2, I-3, I-4, M, S-1, R-1 |
No openings permitted with a fire separation distance of
three feet or less. Walls with a fire separation distance of 10 feet or less,
but more than three feet, are permitted to have unprotected openings with an
aggregate area not exceeding 10 percent of the area of the wall. Openings in
excess of 10 percent of the aggregate wall area shall be protected. |
F-2, S-2 |
No openings permitted with a fire separation distance of
three feet or less. Protected openings required with a fire separation distance
of five feet or less. |
i. If the
building is provided with an automatic sprinkler system throughout, the amount
of unprotected openings shall be permitted to be increased to the limit for
protected openings.
ii. In all
occupancies other than Group H, unlimited unprotected openings are permitted in
the first story of exterior walls facing a street which have a fire separation
distance of greater than 15 feet, or facing unoccupied space. The unoccupied
space shall be on the same lot or dedicated for public use, shall not be less
than 30 feet in width and shall have access from a street by a posted fire lane
not less than 30 feet in width and shall have access from a street by a posted
fire lane not less than 18 feet in width.
iii. When a change of use is made to an equal
or lesser hazard classification as shown in Table F, no change in existing
exterior wall openings is required. (Plan review--Building, Fire.
Inspection--Building)
(g) Automatic Sprinkler Systems: The
following automatic sprinkler system requirements apply in changes of use.
TABLE G
Hazard Categories and Classifications Automatic Sprinkler
Systems
Relative Hazard |
Use Classification |
1 (highest) |
A-2 nightclubs, H, I |
2 |
A-2 (other than nightclubs), R-1, R-2, R-3, R-4 |
3 |
A-1, A-3, A-4 |
4 |
F-1, M, S-1 |
5 |
A-3 Places of Worship, E |
6 (lowest) |
A-5, B, F-2, R-5, S-2, U |
1. When a change
of use is made to a higher hazard category as shown in Table G, the building
shall be provided with an automatic sprinkler system as required by the
following sections of the building subcode: 903.2.1 for Group A occupancies,
903.2.3 for Group E occupancies, 903.2.4 for Group F-1 occupancies, 903.2.5 for
Group H occupancies, 903.2.6 for Group I occupancies, 903.2.7 for Group M
occupancies, 903.2.8 for Group R occupancies, 903.2.9 for Group S-1, 903.2.10
for Group S-2, and 903.2.11.1 for windowless stories (stories without
openings.) When this section requires an automatic sprinkler system, compliance
with 903.3 of the building subcode is also required.
i. When a portion of a building is changed to
a higher hazard category and the proposed use is separated from the existing
use(s) by a fire barrier or horizontal assembly, or both, having a fire
resistance rating in accordance with Table 707.3.10 of the building subcode, an
automatic sprinkler system as required above shall be installed only in the
portion changed; mixed occupancies shall use the highest applicable rating from
Table 707.3.10.
ii. When an
attached single-family townhouse or portion thereof or a portion of a detached
one- or two-family dwelling is changed to any nonresidential use, except Group
H, Group F, or Group S, the remaining attached dwelling(s) or portion of the
dwelling(s) are not required to be provided with an automatic sprinkler system.
2. When a change of use
is made to an equal or lesser hazard category as shown in Table G, there is no
requirement to install an automatic sprinkler system except in areas where work
being performed in connection with the change of use triggers a requirement for
an automatic sprinkler system and in windowless stories in accordance with
5:23-6.30(c)
of this subchapter.
3. Notwithstanding the relative hazard as
determined by Table G, when a change in the character of the use is made to a
higher degree of hazard as defined by NFPA 13 (Light Hazard, Ordinary Hazard
Group 1, Ordinary Hazard Group 2, Extra Hazard Group 1, Extra Hazard Group 2
and Special Occupancy Hazards), the sprinkler system shall be evaluated and,
where required by NFPA 13, altered to conform to the required density and
maximum sprinkler protection area per head for the proposed
occupancy.
4. Notwithstanding the
relative hazard as determined by Table G above, when a change in the group or a
change in the character of the use is made to create a dormitory, the building
or portion thereof is required to be provided with an automatic sprinkler
system. (Fire)
(h) Fire
Alarm and Detection Systems: When a change of use is made to any of the
following groups, a fire alarm system and/or an automatic fire detection system
shall be installed in accordance with Section 907 of the building subcode.
Where a portion of a building is changed to any of the following groups, a fire
alarm system and/or an automatic fire detection system shall be installed
throughout the building in accordance with Section 907 of the building subcode
unless the proposed use is separated from the other use(s) in the building by a
fire barrier having a fire resistance rating in accordance with Table 707.3.10
of the building subcode in which case only the portion changed shall comply;
mixed occupancies shall use the highest applicable rating from Table 707.3.10.
(For purposes of applying this section, horizontal separation shall not be
considered.)
1. Group A: A manual or automatic
fire alarm system shall be installed and maintained as required by Section
907.2.1 of the building subcode.
2.
Group B: A manual fire alarm system shall be installed and maintained as
required by Section 907.2.2 of the building subcode.
3. Group E: A manual fire alarm system shall
be installed and maintained as required by Section 907.2.3 of the building
subcode.
4. Group F: A manual fire
alarm system shall be installed and maintained as required by Section 907.2.4
of the building subcode.
5. Group
H: A manual fire alarm system shall be installed and maintained as required by
Section 907.2.5 of the building subcode.
6. Group I: A manual fire alarm system and an
automatic smoke detection system shall be installed and maintained as required
by Section 907.2.6 of the building subcode.
7. Group M: A manual fire alarm system shall
be installed and maintained as required by Section 907.2.7 of the building
subcode.
8. Group R-1: A manual
fire alarm system and an automatic smoke detection system shall be installed
and maintained as required by Section 907.2.8 of the building
subcode.
9. Group R-2: A fire alarm
system shall be installed and maintained as required by Section 907.2.9 of the
building subcode.
10. Group R-4: An
automatic smoke detection system shall be installed and maintained as required
by Section 907.2.9A of the building subcode.
11. Group S: A manual fire alarm system shall
be installed and maintained as required by Section 907.2.10 of the building
subcode. (Fire)
(i)
Single and Multiple Station Smoke Alarms: When a change of use is made to any
of the following groups, single and multiple station smoke alarms shall be
installed in accordance with Section 907.2.11 of the building subcode.
1. Group R-1: Single or multiple station
smoke alarms shall be installed and maintained as required by Section
907.2.11.1 of the building subcode.
2. Groups R-2, R-3, R-4, R-5, and I-1: Smoke
alarms shall be installed and maintained as required by Section 907.2.11.2 of
the building subcode or Section R314 of the one- and two-family dwelling
subcode, as applicable.
3. Where
the use of a portion of a building is changed such that any nonresidential use
is located below or attached to one or more dwelling units (including single
room occupancies), single or multiple station smoke alarms shall be installed
in the nonresidential portion(s) of the building in accordance with NFPA 72 and
provided with an audible alarm located within each dwelling unit of the
residential portion of the building. The alarms shall be AC powered with
battery back-up. Hard-wired, interconnected smoke alarms installed throughout
the building shall be accepted as meeting this requirement. (Fire)
(j) Carbon monoxide detection
equipment: When the use of a building is changed and the building contains a
fuel-burning appliance or has an attached garage, carbon monoxide detection
equipment shall be installed in accordance with Section 915 of the building
subcode or Section R 315 of the one- and two-family dwelling subcode, as
applicable. (Fire)
1. Exception: In
occupancies other than Group I-1, I-2, I-4 or R or classrooms in Group E
occupancies, battery-powered or plug-in devices shall be accepted for purposes
of meeting the requirements of this section.
(k) Structural Requirements: The following
structural requirements shall apply in changes of use:
TABLE K |
Structural Load Categories |
Load Category | Use or Character of Use |
1 (highest) | F-1, F-2, S-1, S-2, stack areas in
libraries, stages and platforms, areas subject to vehicular loads, queuing
areas |
2 | All loading conditions not listed in category
1 or 3 |
3 (lowest) | B, E, I-1, I-2, I-3, I-4, R-1, R-2,
R-3, R-4, R-5 |
1. When the
use or the character of use of a building is changed to a higher load category
as shown in Table K above, then the structure shall be capable of supporting
the load requirement for the new use or character of use as specified in Table
1607.1 of the building subcode.
i. If the
building subcode official determines that the number of occupants or the
placement and weight of furniture and equipment can be controlled by the
occupants, the areas designed for the reduced live load shall be posted with
the approved live load. Placards stating the allowable live loads shall be
posted. Placards may state loads in forms usable by the occupants, in addition
to posting the allowable load in pounds per square foot. Such information shall
be developed by a licensed design professional and be approved by the subcode
official.
(1) Analysis and test methods for
evaluation of existing structural members shall use methods specified in the
code in effect at the time the building was originally constructed or other
standards as approved by the subcode official.
ii. The corridor and lobby loading
requirements of Table 1607.1 shall be met only if the corridor exceeds six feet
in width or if the lobby or corridor area is used for queuing
purposes.
2. Where the
use or character of use within an existing building is changed to an equal or
lower load category as shown in Table K above, then the existing structure may
be used without modification, provided that the building is structurally sound
and in good structural repair.
3.
When a building is reclassified into one of the following occupancies, the
building shall comply with the seismic design requirements of Section 1613 of
the building subcode: Fire, rescue and police stations; Group I-2 having
surgery or emergency treatment facilities; emergency preparedness centers;
post-earthquake recovery vehicle garages; post-earthquake shelters;
power-generating stations and other utilities required as emergency backup
facilities; primary communication facilities; highly toxic materials as defined
by Section 307 of the building subcode where the quantity of material exceeds
the exempt amount as per Section 307.1 of the building subcode.
(Building)
(l) Plumbing
Requirements: When the character of the use of a building or portion of a
building is changed, the following plumbing provisions shall apply:
1. The fixture requirements for the proposed
new use shall comply with the basic requirements for that use.
2. If the new use is a food handling
establishment, all existing sanitary waste lines above the food or drink
preparation or storage areas shall be panned or otherwise protected to prevent
leaking pipes or condensation on pipes from contaminating food or drink. New
drainage lines shall not be installed above such areas except where it is the
only practical alternative. Where new lines are to be installed, they shall be
protected in accordance with the plumbing subcode.
3. New uses that will produce grease or oil
laden wastes shall be provided with interceptors as required in the plumbing
subcode.
4. If the new use produces
chemical wastes, the following shall apply:
i.
If the existing piping is compatible with the chemical waste, no change to the
existing piping material is required.
ii. If the existing piping is not compatible
with the chemical waste, either the waste must be neutralized prior to entering
the drainage system or the piping must be changed to a compatible
material.
iii. No chemical waste
shall discharge to a public sewer system without the approval of the sewage
authority.
5. Where a
building's use is changed to a health care facility, the requirements of
chapter 14 of the plumbing subcode shall apply. (Plumbing)
(m) Electrical Requirements: The following
electrical requirements shall apply in changes of use:
1. When the character of the use of a
building or portion thereof is changed to one of the following special
occupancies as described at Chapter 5 of the electrical subcode, the electrical
wiring and equipment of the building or portion thereof that contains the
proposed use shall comply with all applicable requirements of the electrical
subcode regardless of whether a change of group is involved:
i. Hazardous (classified)
Locations;
ii. Commercial Garages,
Repair and Storage;
iii. Aircraft
Hangars;
iv. Motor Fuel Dispensing
Facilities;
v. Bulk Storage
Plants;
vi. Spray Application,
Dipping, Coating, and Printing Processes;
vii. Health Care Facilities;
viii. Assembly Occupancies;
ix. Theaters, Motion Picture and Television
Studios, and Similar Locations;
x.
Motion Picture and Television Studios and Similar Locations; and
xi. Agricultural Buildings.
2. When the use of a building is
changed to Group R-2, R-3, R-4 or R-5, the electrical wiring and equipment of
the building shall comply, at a minimum, with the Basic Requirements of this
subcode for that use and shall have the electrical service (conductors and
equipment) sized and rated in accordance with the electrical subcode.
(Electrical)
(n)
Mechanical Requirements: When the character of the use of a building is
changed, the following mechanical provisions shall apply:
1. All spaces intended for human occupancy
shall be provided with natural or mechanical ventilation. A building intended
to be used as a public school shall be mechanically ventilated.
i. Spaces intended to be naturally ventilated
shall be provided with openable doors, windows, louvers or other openings to
the outdoors. The minimum openable area to the outdoors shall be four percent
of the floor area being ventilated. Where rooms without openings to the
outdoors are ventilated through an adjoining room, the unobstructed opening to
the adjoining room shall be at least eight percent of the floor area of the
interior room or space, but not less than 25 square feet. The ventilation
openings to the outdoors shall be based on the total floor area being
ventilated.
ii. Spaces intended to
be mechanically ventilated shall comply with the following:
(1) If the occupancy of a building is changed
and the new occupancy would require the same or a lesser amount of outdoor air
based on the equations below, no change to the mechanical ventilation system is
required.
(2) If the occupancy of a
building is changed and the new occupancy would require a greater amount of
outdoor air based on the equations below, the HVAC system shall be upgraded to
satisfy the requirements of Table 403.3.1.1 in the mechanical subcode for the
new occupancy.
(3) Residential
buildings that are intended to be mechanically ventilated shall be provided
with the ventilation specified in the mechanical subcode.
(4) When the use of a building is changed to
a health care facility, mechanical ventilation shall be provided as required by
the mechanical subcode and
5:23-3.2(b).
(5) When the group of a building is changed
to B or E and the building is a class one or class two building, a test and
balance report shall be submitted prior to the issuance of a certificate of
occupancy. (Building)
2. A commercial hood and an automatic
suppression system that comply with the mechanical subcode shall be required
for commercial cooking operations producing grease-laden vapors. No automatic
suppression system shall be required for completely enclosed ovens, steam
tables or similar equipment.
i. Exception:
Bed and breakfast home stay facilities, which are designed to accommodate five
or fewer guests, shall not be required to comply with this provision.
(Fire)
3. All
newly-introduced devices, equipment or operations that produce airborne
particulates, odors, fumes, sprays, vapors, smoke or gases in such quantities
as to be irritating or injurious to health shall be provided with local exhaust
in accordance with Section 502 of the mechanical subcode. (Building)
TABLE N |
Outdoor Air Rates Based on Occupancy
Type |
|
Occupancy | P/1,000
sq.ft. | CFM/person |
Storage Warehouses | 5 | 10 |
|
Correction Facilities |
|
|
Dining Halls | 100 | 15 |
Guard Stations | 40 | 15 |
Dry Cleaners, laundries |
|
|
Coin oper dry cleaner | 20 | 15 |
Coin oper laundries | 20 | 15 |
|
Education |
|
|
Auditoriums | 150 | 15 |
Classrooms | 50 | 15 |
Libraries | 20 | 15 |
Music Rooms | 50 | 15 |
Food & Bev Service | | |
Dining Rooms | 70 | 15 |
Kitchens (cooking) | 20 | 15 |
|
Hospitals, Nursing & |
| |
Convalescent Homes |
| |
Med Procedure Rooms | 20 | 15 |
Physical Therapy | 20 | 15 |
Recovery and ICU | 20 | 15 |
|
Hotels, Motels, Resorts, |
| |
Dormitories |
| |
Assembly Rooms | 120 | 15 |
Dormitory Sleep Areas | 20 | 15 |
Lobbies | 30 | 15 |
|
Specialty Shops | | |
Barber | 25 | 15 |
Florists | 8 | 15 |
Hardware, drug, fabric | 8 | 15 |
Reducing Salons | 20 | 15 |
Supermarkets | 8 | 15 |
|
Theaters |
| |
Auditoriums | 150 | 15 |
Stages and Studios | 70 | 15 |
|
Transportation |
| |
Platforms | 100 | 15 |
Vehicles | 150 | 15 |
Waiting Rooms | 100 | 15 |
|
Workrooms |
| |
Bank Vaults | 5 | 15 |
Meat Processing | 10 | 15 |
Pharmacy | 20 | 15 |
Photo Studios | 10 | 15 |
|
Sports and Amusement |
| |
Spectator Areas | 150 | 15 |
|
Correctional Facilities |
| |
Cells | 20 | 20 |
|
Education |
| |
Laboratories | 50 | 20 |
Training Shops | 30 | 20 |
Food & Bev Service | | |
Cafeteria, fast food | 100 | 20 |
|
Hotels, Motels, Resorts, | | |
Dormitories |
| |
Conference Rooms | 50 | 20 |
|
Dry Cleaners | | |
Commercial Laundry | 10 | 25 |
|
Hospitals, Nursing and | | |
Convalescent Homes |
| |
Patient Rooms | 10 | 25 |
|
Specialty Shops |
| |
Beauty | 25 | 25 |
|
Dry Cleaners, Laundries | | |
Commercial Dry |
| |
Cleaner | 30 | 30 |
|
Food & Bev Service | | |
Bars & Cocktail |
| |
Lounges | 100 | 30 |
|
Dry Cleaners, Laundries |
| |
Storage, Pick-up | 30 | 35 |
|
Smoking Lounges | 70 | 60 |
|
Offices |
| |
Conference Rooms | 50 | 20 |
Office Spaces | 7 | 20 |
Reception Areas | 60 | 20 |
Telecommunication |
| |
Ctrs & Data Entry | 60 | 20 |
|
Theaters |
| |
Lobbies | 150 | 20 |
Ticket Booths | 60 | 20 |
|
Sports and Amusement |
| |
Playing floors (gym) | 30 | 20 |
|
Sports and Amusement |
| |
Ballrooms and Discos | 100 | 25 |
Bowling Alleys | | |
(Seating areas) | 70 | 25 |
Game Rooms | 70 | 25 |
|
Hospitals, Nursing & |
| |
Convalescent Homes |
| |
Operating Rooms | 20 | 30 |
Hotels, Motels, Resorts, | | |
Dormitories |
| |
Gambling Casinos | 120 | 30 |
Occupancy | CFM/sq. ft. |
Education |
|
Corridors | 0.1 |
Locker Rooms | 0.5 |
Hospitals, Nursing and |
|
Convalescent Homes |
|
Autopsy Rooms | 0.5 |
Public Spaces |
|
Corridors and Utilities | 0.05 |
Elevators | 1.0 |
Locker & Dressing
Rooms | 0.5 |
Public Restrooms | 75 cfm per water
closet |
or urinal |
|
Retail Stores, Sales Floors |
|
and Showroom Floors |
|
Basement and Street | 0.3 |
Dressing Rooms | 0.2 |
Malls and Arcades | 0.2 |
Shipping and Receiving | 0.15 |
Storage Rooms | 0.15 |
Upper Floors | 0.2 |
Warehouses | 0.05 |
Specialty Shops |
|
Automotive Service | 1.5 |
Clothes and Furniture | 0.3 |
Pet Shops | 1.0 |
Sports & Amusement |
|
Ice Arenas | 0.5 |
Swimming Pools |
|
(Pool & Deck Area) | 0.5 |
Storage |
|
Repair Garages/Public |
|
Garages | 1.5 |
Workrooms |
|
Darkrooms | 0.5 |
Duplicating | 0.5 |
Note: P/1,000 sq. ft. = persons per 1,000
square feet of building area. |
Note a. Spaces unheated or maintained below
50 degrees F are not covered |
by these requirements unless the occupancy
is continuous. |
Where the ventilation rates in Table N are
based on CFM/person |
(1) OL[n] x V[n] is less than or equal to
OL[e] x V[e] | + no upgrade |
(2) OL[n] x V[n] is greater than OL[e] x
V[e] | + upgrade |
Where the ventilation rates in Table N are
based on CFM/square footage |
(3) SF[n]xV[n] is less than or equal to
SF[e]xV[e] | + no upgrade |
(4) SF[n]xV[n] is greater than
SF[e]xV[e] | + upgrade |
Where the ventilation rates in Table N are
based on CFM/square footage |
and CFM/person |
(5) OL[n]xV[n] is less than or equal to
SF[e]xV[e] | + no upgrade |
(6) OL[n]xV[n] is greater than
SF[e]xV[e] | + upgrade |
(7) SF[n]xV[n] is less than or equal to
OL[e]xV[e] | + no upgrade |
(8) SF[n]xV[n] is greater than
OL[e]xV[e] | + upgrade |
Where: |
OL[n] = | the occupant
load of the proposed occupancy based on |
Table N. When accepted by the
administrative authority this occupant load can be reduced. |
OL[e] = | the occupant
load of the existing occupancy |
based on Table N. |
SF[n] = | the square footage of the
proposed occupancy. |
SF[e] = | the square footage of the
existing occupancy. |
V[n] = | the ventilation
rate for the proposed |
occupancy based on Table N. |
V[e] = | the ventilation
rate for the existing |
occupancy based on Table N. |
(o) Accessibility requirements: The following
accessibility requirements shall apply in changes of use:
1. Nonresidential buildings and buildings of
Use Group R-1.
i. The change of use of a
building of 10,000 square feet or more total gross enclosed floor area shall
comply with all applicable provisions of Chapter 11 of the building
subcode.
ii. The change of use of a
building of less than 10,000 square feet total gross enclosed floor area shall
be exempt from the provisions of Chapter 11 of the building subcode, except as
follows:
(1) An alteration project undertaken
in connection with the change of use of a small building shall provide
accessibility as required by
5:23-6.6.
(2) A reconstruction project undertaken in
connection with the change of use of a small building shall provide
accessibility as required by
5:23-6.7.
iii. In a building of any size,
where there is a change of use of an area of 10,000 square feet or more, the
proposed new use shall comply with the requirements of Chapter 11 of the
building subcode.
iv. In a building
of any size, where there is a change of use of an area of less than 10,000
square feet, the proposed new use shall be exempt from the provisions of
Chapter 11 of the building subcode, except as follows:
(1) A renovation project undertaken in
connection with the change of use of a small building shall provide
accessibility as required by
5:23-6.5.
(2) An alteration project undertaken in
connection with the change of use of a small building shall provide
accessibility as required by
N.J.A.C.
5:23-6.6.
(3) A reconstruction project undertaken in
connection with the change of use of a small building shall provide
accessibility as required by
N.J.A.C. 5:23-6.7.
(Building)
2.
When an assisted living facility that was constructed with dwelling units or
rooms pursuant to Chapter 11 of the building subcode because it provided
accommodations for stays of 30 or more consecutive days makes any of those
dwelling units or rooms available for less than 30 consecutive days, 50 percent
of the accommodations or rooms made thus available shall be made fully
accessible. The work needed to make those units accessible shall be completed
and approved before any occupancy of less than 30 days.
3. Residential buildings, other than
buildings of Group R-1, with four or more dwelling units.
i. A renovation project undertaken in
connection with the change of use shall provide accessibility as required by
N.J.A.C.
5:23-6.5.
ii. An alteration project undertaken in
connection with the change of use shall provide accessibility as required by
N.J.A.C.
5:23-6.6.
iii. A reconstruction project undertaken in
connection with the change of use shall provide accessibility as required by
N.J.A.C. 5:23-6.7.
(Building)
(p)
Change of use to a bed and breakfast shall be done in compliance with this
subchapter except as modified below. (Plan review--Building, Fire.
Inspection--Building)
1. Single-family
dwellings of Group R-3, R-4, or R-5 that are being converted to bed and
breakfast guest houses shall meet the requirements of this section.
i. "Bed and breakfast guest house" shall mean
a facility providing sleeping or dwelling accommodations to transient guests
which:
(1) Consists of a structure originally
constructed for the purposes of a private residence;
(2) Includes individual sleeping
accommodations for six to 12 guests;
(3) Has at least one dwelling unit occupied
by the owner of the facility or the owner's agent as his or her place of
residence during any time this facility is being used for the lodging of guests
or has an owner or agent of the owner within 15 minutes travel distance of the
facility while guests are lodging there;
(A)
If the owner or agent is not on site, there shall be a clearly legible sign,
conspicuously displayed in the area where guests register, containing the
owner's or agent's name, address (including unit number or apartment number),
and a 24-hour emergency telephone number;
(4) Has not less than 300 square feet of
common area for the exclusive use of the guests, including, but not limited to,
parlors, dining rooms, libraries, porches, verandas, and solariums for
occupancies with more than 10 guests or not less than 150 square feet of common
area for occupancies with 10 or fewer guests;
(5) Prohibits cooking and smoking in guest
rooms;
(6) Provides a meal to the
guests in the forenoon of each day but does not operate as a restaurant open to
the general public;
(7) Is not a
"rooming house" or "boarding house" as defined in
55:13B-3;
(8) Does not allow more than 15 percent of
the guests to remain more than 30 successive days or more than 30 days of any
period of 60 successive days; and
(9) Does not allow any guest to remain more
than 60 successive days or more than 60 days of any period of 90 successive
days.
2.
Single-family dwellings of Group R-3, R-4, or R-5 that have been converted to
bed and breakfast guest houses shall be deemed to have met the intent of the
rules, as provided in
N.J.A.C.
5:23-2.6(b) l, if the
following requirements have been met:
i.
AC-powered interconnected smoke alarms with battery back-ups shall be installed
in accordance with the building subcode in the locations listed below. Fixed
temperature or rate-of-rise and fixed temperature heat detectors may be
substituted for smoke alarms in those locations where frequent nuisance alarms
would be likely to occur. At least one portable visual alarm-type smoke alarm
for the deaf or hearing impaired shall be available. Notification of the
availability of such devices shall be provided to each occupant. Installation
shall be required at the following locations:
(1) In all guestrooms;
(2) On each story in common areas;
(3) In storage rooms;
(4) In basements; and
(5) In utility and mechanical
rooms.
ii. Except as
otherwise provided in (p)2ii(1) and (2) below, every story utilized for human
occupancy shall be provided with a minimum of two exits.
(1) An existing fire escape shall be accepted
as providing one of the required means of egress if it can safely be used under
emergency exiting conditions. All occupants shall have unobstructed access to
the fire escape without having to pass through a room subject to locking.
Access to a fire escape shall be through a door, except that window access
shall be permitted from guest rooms;
(A)
Window access shall be permitted to serve more than one guestroom provided that
the window serves a floor with a maximum occupant load of 10 and that the
window has a clear opening of at least 5.7 square feet, a minimum net clear
opening of 24 inches in height, a minimum net clear opening of 20 inches in
width, and a sill height of not more than 44 inches above the finished
floor.
(B) Where a door is required
because the occupant load served exceeds 10, the door shall have a clear
opening of at least 10 square feet, a minimum net clear opening of 54 inches in
height, and a minimum net clear opening of 24 inches in width.
(2) In buildings having a single
exit, no additional exit shall be required if all of the following conditions
are met:
(A) At all locations in the story at
the level of discharge, the exit access travel distance shall not exceed 75
feet;
(B) In buildings not more
than two stories in height, from floors that are not more than 16 feet above
grade, where there are not more than four guestrooms per floor and the exit
access travel distance does not exceed 50 feet, the exit shall be enclosed with
construction and opening protection providing a one hour fire-resistance
rating; and
(C) No part of the
building open to guests shall be on a floor that is more than 16 feet above
exterior grade.
iii. Every sleeping room shall be provided
with an operable window having a sill height of not more than 44 inches, having
a width of at least 20 inches, a height of at least 24 inches and a minimum
total area of 5.7 square feet measured from head to sill and from side to
side.
iv. Dead-end corridors shall
not exceed 35 feet.
v. Emergency
egress lighting shall be provided and shall be connected to an emergency
electrical system conforming to NFPA 70 to assure continued illumination for a
duration of not less than one hour, in case of primary power loss in all
building rooms or spaces required to have more than one exit or exit access.
vi. In all buildings, rooms or
spaces required to have more than one exit or exit access, all required means
of egress shall be indicated with approved, internally illuminated or
self-luminous exit signs that comply with the building subcode. Exit signs
shall not be required if the second means of egress is a fire escape that is
accessed directly from an individual sleeping room(s) or on main exterior doors
that are clearly identified as exits. Exit signs shall be connected to an
emergency electrical system to assure continued illumination for not less than
one hour in case of primary power loss.
vii. Means of egress doors shall comply with
the following:
(1) All doors opening into a
passageway at grade or exit stair shall be self closing or automatic closing by
listed closing devices; and
(2) All
guest room doors shall be at least 1 3/8 inch solid core wood or approved equal
with approved door closers and shall be reasonably tight fitting. Replacement
doors shall be 1 3/4 inch solid cord wood or approved equal unless existing
frame will accommodate only a 1 3/8 inch door.
viii. Existing handrails and guardrails
provided for stairways and open sided floor areas shall be permitted to remain
in place, provided they are structurally sound. When handrails or guardrails do
not exist in locations where the building subcode requires them, or where
handrails or guardrails are in danger of collapse when used under emergency
conditions, handrails and guardrails complying with the building subcode shall
be provided.
ix. Transoms shall be
either glazed with 1/4 inch wire glass set in metal frames and permanently
secured in the closed position or sealed with materials consistent with the
corridor construction.
x. Interior
finish shall comply with the following:
(1)
Interior finish of exit enclosures shall have a flame spread of 0-25 and a
smoke developed rating of 450 or less (Class I finish as determined by
ASTM-E84);
(2) Interior finish of
exit access enclosures shall have a flame spread of 26-75 and a smoke developed
rating of 450 or less (Class II finish as determined by ASTM-E84);
(3) Interior finish of all other spaces shall
have a flame spread rating of under 200 and a smoke developed rating of 450 or
less (Class III finish as determined by ASTM-E84).
xi. Interior stairways and other vertical
openings connecting more than six floor levels shall be enclosed with approved
assemblies having a two-hour fire-resistance rating. Those connecting four to
six floor levels shall be enclosed with approved assemblies having a one-hour
fire-resistance rating. Interior stairways connecting three or fewer levels
shall be enclosed as follows:
(1) A minimum
one-hour fire barrier shall be provided to protect all interior stairways and
other vertical openings not exceeding three stories. Such fire barrier may be
omitted provided that:
(A) The building is
provided throughout with an approved automatic fire suppression system
complying with the building subcode; or
(B) All of the following conditions exist:
I. Every sleeping room has an operable window
with a sill height of not more than 44 inches, a width of at least 20 inches, a
height of at least 24 inches and a minimum total area of 5.7 square feet
measured from head to sill and from side to side;
II. The building is protected throughout by
an automatic fire alarm system complying with the building subcode and is
supervised in accordance with NFPA 72; and
III. Every sleeping room above the second
floor or more than 16 feet above grade is provided with direct access to a fire
escape or other approved secondary exit or any exit-access corridor exceeding
20 feet in length which serves two means of egress, at least one of which is an
unprotected vertical opening, shall be separated from the vertical opening by a
one-hour fire barrier.
(q) A change in the character of
use of a single-family home to a cooperative sober living residence shall
comply with this subchapter except as modified below. (Plan review--Building,
Fire. Inspection--Building, Fire.)
1.
Single-family dwellings of Group R-3 or R-5 that are being converted to a
cooperative sober living residence shall meet the requirements of this section.
i. There shall be not more than 10 occupants,
excluding staff; each occupant, including staff, shall be capable of prompt
self-evacuation;
ii. Each home
shall have smoke alarms that comply with the Uniform Fire Code
(N.J.A.C.
5:70-4.19). Fire alarm systems
installed in accordance with the One- and Two-Family Dwelling Subcode shall
also be deemed to comply. Smoke alarms shall be located in each sleeping room,
in the area outside separate sleeping rooms, and on each additional story of
the dwelling, including basements and habitable attics;
iii. In the vicinity of each sleeping area,
each home with a fuel burning appliance or with an attached garage shall have
carbon-monoxide alarms that comply with the Uniform Fire Code
(N.J.A.C.
5:70-4.19) or with
N.J.A.C.
5:27-14.1; and
iv. Each bedroom shall have an operable
egress window that complies with the Uniform Construction Code
(N.J.A.C. 5:23).