Current through Register Vol. 56, No. 18, September 16, 2024
(a)
Manual Alarm System: When the work area exceeds 50 percent of the gross
enclosed floor area of the building, a fire alarm system shall be installed
throughout the building.
1. Exception: Manual
alarm systems are not required in buildings which do not have occupied floors
which are two or more stories above the lowest level of exit discharge or
floors two or more stories below the highest level of exit discharge.
(Fire)
(b) Vertical
Opening Protection: When the work area exceeds 50 percent of the gross enclosed
floor area of the building, vertical opening protection shall be provided
throughout the building as follows:
1. A
minimum two hour fire rated assembly with approved opening protectives shall be
required for interior stairways and other vertical openings connecting more
than six floor levels.
2. A minimum
one hour fire rated assembly with approved opening protectives shall be
required for interior stairways and other vertical openings connecting four to
six floor levels.
3. A minimum
30-minute UFC fire barrier shall be required for interior stairways and other
vertical openings not exceeding three stories.
i. Exception: No vertical opening protection
shall be required for buildings up to 3,000 square feet per floor or for
buildings with an automatic sprinkler system throughout. (Plan
review--Building, Fire. Inspection--Building)
(c) Requirements for high-rise buildings: Any
building or structure having one or more floors used for human occupancy
located either more than six stories or more than 75 feet above the lowest
level accessible to a fire department vehicle shall comply with the following:
1. When the work area is one entire floor or
more or when the work area is 20 percent or more of the occupied floor area
served by a recirculating air system, the recirculating air system which serves
the work area shall be equipped with approved smoke and heat detection devices
installed in accordance with the UCC. The devices shall stop the fan(s)
automatically and shall be of the manual reset type. Automatic fan shutdown is
not required when the system is part of an approved smoke removal or smoke
control system. (Building)
2. When
the work area is one entire floor or more or when the work area is 20 percent
or more of the occupied floor area of the building, all elevators in the
building shall be equipped with the following emergency control devices:
i. All automatic (nondesignated attendant)
elevators having a travel distance of 25 feet or more above or below the
designated level shall be equipped with Phase 1 Emergency Recall Operation as
required by ASME A17.1-1987, Rules 211.3a and 211.3b listed in N.J.A.C.
5:70-3;
ii. At least one elevator
shall be equipped with Phase II Emergency In-Car Operation, as required by ASME
A17.1-1987, Rule 211.3c; and
(1) In buildings
with multiple elevators, at least one elevator to each floor served by an
elevator shall be equipped with Phase II Emergency In-Car Operation.
iii. All designated attendant
elevators having a travel distance of 25 feet or more above or below the
designated level shall be equipped with emergency controls, as required by ASME
A17.1-1987, Rule 211.4. (Elevator)
3. When the work area is one entire floor or
more or when the work area is 20 percent or more of the occupied floor area of
the building, standpipes shall be provided up to and including the highest
floor that is part of the work area. The standpipes shall be located and
installed in accordance with the building subcode, except as follows:
i. No pump shall be required provided that
the standpipes are capable of accepting delivery by fire department apparatus
of a minimum of 250 gpm at 65 psi to the topmost floor in buildings equipped
throughout with an automatic sprinkler system or a minimum of 500 gpm at 65 psi
to the topmost floor in all other buildings. (Where the standpipe terminates
below the topmost floor, the standpipe shall be designed to meet these
requirements (gpm/psi) for possible future extension of the
standpipe.)
ii. Hose and hose
cabinets shall not be required. (Fire)
4. When the work area is one entire floor or
more or when the work area is 20 percent or more of the occupied floor area of
the building, central control station and communication systems shall be
provided as follows:
i. An approved public
address communication system consisting of loudspeakers in each corridor and in
each room and tenant space exceeding 1,000 square feet, each elevator and
elevator lobby and in each stair enclosure which shall be capable of being
operated from the central control station;
ii. A two-way fire department communication
system which shall operate between the central control and every elevator,
elevator lobby and entry to enclosed exit stairways;
iii. A central control station for fire
department operations shall be provided in a location approved by the fire
department. It shall contain the public address panel, the fire department
communications panel, fire detection and alarm system annunciator panels,
status indicators and controls for air handling systems, sprinkler valve and
water flow detector display panels, and status indicators and a telephone for
fire department use with controlled access to the public telephone system.
(Fire)
5. Automatic
Sprinkler System: When the work area is an entire floor, an automatic sprinkler
system shall be installed on that floor. When an automatic sprinkler system is
provided, the sprinkler riser shall be sized to serve the entire building, even
if the system currently being installed serves only a portion of the building.
(Fire)
(d) Elevator
Devices: When the work area exceeds 50 percent of the gross enclosed floor area
of the building, all elevator devices serving any part of the work area shall
comply with the requirements of
5:23-6.30(g).
(Elevator)
(e) Airport Traffic
Control Towers: When the work area exceeds 50 percent of the gross enclosed
floor area of an airport traffic control tower, the entire structure shall
comply with the requirements of Section 412.3 of the building
subcode.