Current through Register Vol. 56, No. 18, September 16, 2024
(b) The following pages, chapters, sections,
or appendices of the plumbing subcode shall be amended as follows:
1. The section entitled "Administration,"
comprising sections ADM 1.1 through ADM 1.13, is deleted in its
entirety.
2. Chapter 1 of the
plumbing subcode, entitled "Definitions," shall be amended as follows:
i. Delete the term and definition of
"Adopting Agency."
ii. Amend the
definition of "approved" as follows: delete "Sec. 3.12" and insert
"5:23-3.7."
iii. Delete the
definition of "Authority Having Jurisdiction" and insert the following: "Unless
otherwise defined herein, or unless the context clearly indicates otherwise,
the term "authority having jurisdiction" for purposes of the plumbing subcode,
shall mean the "plumbing subcode official."
iv. In the definition of "Building
Classification" delete "code" and insert "subcode at 5:23-3.14."
v. In the definition of "hot water" the
following shall be inserted after the first sentence: "Hot Water is potable
water at a temperature of not less than 120 degrees F and not more than 140
degrees F."
vi. The term and
definition of "nuisance" are deleted.
vii. In the definition of tempered water,
"desired" shall be deleted. Additionally, "for its intended use, typically"
shall be deleted and "of" shall be inserted.
3. Chapter 2 of the plumbing subcode,
entitled "General Regulations," shall be amended as follows:
i. Section 2.5, Health and Safety, is deleted
in its entirety.
ii. In Section
2.9.3, From Weakened Structure, delete "building code" and insert "building
subcode."
iii. In Section 2.11,
Materials Exposed Within Plenums, "Codes" shall be deleted and "subcodes" shall
be inserted.
iv. In Section 2.12,
Sleeves for Piping, subparagraph e, "regulations" shall be deleted and
"subcode" shall be inserted.
v. In
Section 2.16, Freezing or Overheating, at Item 1, "42" shall be inserted in the
blank space provided. Additionally, the following shall be inserted:
"Combination domestic/fire water service piping shall be installed such that
the minimum earth cover is 42 inches or the top of the pipe is 12 inches below
the frost depth of the locality, whichever is greater. Limited-area sprinkler
systems installed in accordance with Section 903.3.8 of the building subcode,
shall be installed such that the minimum earth cover is 42 inches." In the same
section, at Item 2, "24" shall be inserted in the blank space provided. In
addition, in the third line of Item 2, "6" shall be inserted in the blank space
provided.
vi. Section 2.19.1,
Availability of Public Water and Sewer, is amended to delete the blank and the
words "feet of any property line of the premises, or other."
vii. Section 2.19.2, Private Systems, is
amended to delete the words "the Health Department or other agency having
jurisdiction" and substitute in lieu thereof "The New Jersey Department of
Environmental Protection."
viii.
New Section 2.19.3, Common Systems, shall be inserted as follows:
a. Common water services shall be permitted
to serve attached single-family dwellings in groups of three or more where the
common water service is located within property subject to an association
easement or on common property and there is a homeowners' association or other
owner entity responsible for maintenance and upkeep.
b. Common building sewers shall be permitted
to serve attached single-family dwellings in groups of three or more where the
common sewer is located within property subject to an association easement or
on common property and there is a homeowners' association or other owner entity
responsible for maintenance and upkeep.
ix. Section 2.24, Toilet Facilities for
Construction Workers, shall be deleted in its entirety.
x. Section 2.26.1, General, shall be amended
as follows:
(1) Subsection b. shall be
deleted.
(2) In subsection d,
"Phase II firefighter override" shall be deleted and "firefighter emergency
operation" shall be inserted.
xi. Section 2.26.2, Where Elevator Pit
Drainage is Provided, shall be amended as follows:
(1) In subsection b, "Where the drainage
discharge is outdoors," shall be deleted and "the" shall be
capitalized.
(2) Subsection c.
shall be deleted.
(3) In subsection
d, "hydraulic" shall be deleted. Additionally, "or there shall be oil
separation for pump operation" shall be deleted.
(4) In subsection g, "Phase II firefighter
override" shall be deleted and "firefighter emergency operation" shall be
inserted. Additionally, the last sentence shall be
deleted.
4.
Chapter 3 of the plumbing subcode, entitled "Materials," shall be amended as
follows:
i. In Section 3.1.1, Minimum
Standards, delete "Minimum" in the title. In the same section at items (1) and
(2), delete "Section 3.12.2" and insert "5:23-3.7."
ii. In Section 3.1.2, General Requirements,
at Item a, delete "at least." In the same section, delete "Section 3.12" and
insert "N.J.A.C. 5:23-3.7."
iii. In Section 3.1.3, Standards Applicable
to Plumbing Materials, "Section 3.12.2" shall be deleted and "N.J.A.C.
5:23-3.7" shall be inserted.
iv. In Table 3.1.3, Approved Materials, Part
XI, Installation Procedures and Practices, insert: "11. Suction Entrapment
Avoidance in Swimming Pools, Wading Pools, Spas, Hot Tubs, and Catch Basins:
ANSI/APSN/ICC-7-2018."
v. Section
3.3.11 entitled "Septic Tanks" is deleted in its entirety.
vi. Add new section 3.4.2.1 as follows:
3.4.2.1 Combination Domestic/Fire Water Service: Water service piping for
combination domestic/fire water services shall be of materials listed in Table
3.4 and shall be water pressure rated not less than 200 psig at 7373[degrees]F.
Joint restraints shall comply with Section 6.3, entitled "Joint Restraint for
Fire Mains" per NFPA 13.
Exception: Limited area sprinkler systems installed in
accordance with Section 903.3.8 of the building subcode, shall be water
pressure rated not less than 160 psig at 73[degrees]F.
vii. Section 3.12, Alternate Materials and
Methods, shall be deleted in its entirety.
5. Chapter 5 of the plumbing subcode
entitled, "Traps, Cleanouts and Backwater Valves," shall be amended as follows:
i. In Section 5.3.2, Trap seals, in Exception
(2), "in accordance with 5:23-3.3 " shall be inserted after "Authority Having
Jurisdiction."
ii. In Section
5.3.4, Building traps, "in accordance with 5:23-3.3 " shall be inserted after
"Authority Having Jurisdiction."
iii. In Section 5.4.6, Building Drain and
Building Sewer Junctions and the Property Line, in subsection b, "in accordance
with the requirements of the Authority Having Jurisdiction" shall be
deleted.
iv. In Section 5.4.10,
Manholes for Large Pipes, subsection d shall be deleted.
6. Chapter 6 of the plumbing subcode,
entitled "Liquid Waste Treatment Equipment," shall be amended as follows:
i. At the end of Section 6.1.1, Where
Required, the following shall be inserted: "The determination of necessity
shall be made by the plumbing subcode official in accordance with
N.J.A.C.
5:23-3.3."
ii. In Section 6.1.4.1, General, "and the
Authority Having Jurisdiction" shall be deleted.
iii. Section 6.4.4, Alternate Design, is
amended to add the phrase "in accordance with
N.J.A.C.
5:23-3.3" after the word "approval" on line
4.
7. Chapter 7 of the
plumbing subcode, entitled "Plumbing Fixtures, Fixture Fittings and Plumbing
Appliances," shall be amended as follows:
i.
Section 7.2, Fixtures For Accessible Use, subsection a. shall be deleted and
the following shall be inserted: "Plumbing fixtures for accessible use and
their installation shall conform to the requirements of Chapter 11 of the
building subcode (N.J.A.C. 5:23-3.14)."
ii. In Section 7.18.2, Approval, "to the
Authority Having Jurisdiction" shall be deleted.
iii. In Table 7.21.1, in the second column
entitled "Occupancy Group," "R-2: One- and two-family dwellings" shall be
deleted and "R-3/R-5: One- and two-family dwellings" shall be
inserted.
iv. In Note 1 to Table
7.21.1, Minimum Number of Required Plumbing Fixtures, delete the second
sentence.
v. Section 7.5.3,
Surrounding Surfaces, is amended to delete the following after "surface,"
"extending not less than four feet above the floor. One foot to each side of
the urinal, and one foot in front of the lip of the urinal. See Figure 7.5.3.,"
and insert, "Refer to the International Building Code, Section 1209.2.2." This
section is amended to delete Figure 7.5.3, "Protecting Surrounding Surfaces of
Urinals."
vi. In Section 7.11.4,
Service Sinks and Mop Receptors, b. is amended to delete the following after
"surface," "at least one foot in front of the sink or receptor, at least one
foot on each side, and up to a point one foot above the faucet height," and
insert, "refer to the International Building Code, Section 1210.2.2."
vii. In Section 7.21.2, Occupant Load, b.
"building code" shall be deleted and "building subcode" shall be
inserted.
viii. In Section 7.21.9,
Family and Assisted-Use Toilet Rooms, "applicable building code" shall be
deleted and "building subcode" shall inserted.
ix. Section 7.23, Safety Features for Spas
and Hot Tubs, shall be deleted and Section 7.23, Safety Features for Spas and
Hot Tubs, shall be inserted as follows:
"7.23
Safety Features for Swimming Pools, Spas, and Hot Tubs.
7.23.1, Suction Entrapment Avoidance. Suction
outlets shall be designed and installed in accordance with
ANSI/PHTA/ICC-7."
8. Chapter 8 of the plumbing subcode,
entitled "Hangers and Supports," shall be amended as follows:
i. In Section 8.9, Seismic Supports for
Piping, "code" shall be deleted and "subcode" shall be
inserted.
9. Chapter 10
of the plumbing subcode, entitled "Water Supply and Distributions," shall be
amended as follows:
i. In Section 10.4.2,
Interconnections, delete "with the approval of the Authority Having
Jurisdiction" and insert "in accordance with the rules of the New Jersey
Department of Environmental Protection at N.J.A.C. 7:10-10."
ii. In Section 10.4.3, Cross Connection
Control, the text shall be deleted and the following shall be inserted "Potable
water supplies shall be protected in accordance with the provisions of this
code and where applicable the Safe Drinking Water Regulations (N.J.A.C. 7:10).
The requirements of this code shall establish requirements for individual
outlet protection. The requirements of the Safe Drinking Water Act shall
establish the requirements for containment."
iii. In Section 10.4.4b, Private Supplies,
"in accordance with
N.J.A.C.
7:10-10.2(e)" shall be
inserted after "Authority Having Jurisdiction."
iv. In Section 10.5.6e, Testing and
Maintenance of Backflow Prevention Assemblies, "and repair" shall be deleted.
Additionally, in the same sentence, "approved by an agency acceptable to the
Authority Having Jurisdiction" shall be deleted.
v. Section 10.5.9a, Protection from Fire
Systems, Exception (4) shall be deleted and the following inserted: "(4) Where
fire protection systems supplied from a potable water system include a fire
department connection which is located less than 1,700 feet from a non-potable
water source, the water supply shall be protected by one of the following:
(i) Reduced pressure backflow preventer
assembly; or
(ii) Reduced pressure
detector assembly."
vi.
In Section 10.8.1, Water Pressure Booster Systems Required, "and in accordance
with good practice" in the fifth and sixth lines shall be deleted.
vii. In Section 10.15.1, Hot Water Supply
System, "Outlet temperature of hot water from lavatory faucets in public use
facility restrooms or public toilet rooms shall be provided with a means to
limit the maximum temperature to 110 degrees F." shall be inserted after the
first sentence.
viii. In Section
10.20, NFPA 13D Multipurpose Residential Fire Sprinkler Systems, shall be
deleted and new section 10.20, Dwelling Unit Fire Sprinkler Systems, shall be
inserted, as follows: Section P2904, Dwelling Unit Fire Sprinkler Systems, of
the one- and two-family dwelling subcode shall be considered part of the
plumbing subcode.
10.
Chapter 12 of the plumbing subcode, entitled "Vents and Venting," shall be
amended as follows:
i. Section 12.5, Frost
Closure, is deleted in its entirety.
ii. Section 12.8.2, Provision for Venting
Future Fixtures, is deleted in its entirety.
iii. Section 12.10, Wet Venting, shall be
deleted and the text of the 2015 National Plumbing Code shall be inserted:
12.10 WET VENTING
12.10.1 Single Bathroom Groups
a. An individually vented lavatory in a
single bathroom group shall be permitted to serve as a wet vent for the water
closet, the bathtub, or shower stall, the water closet and bathtub/shower if
all of the following conditions are met.
1.
The wet vent is 1-1/2" minimum pipe size if the water closet bend is 3" size,
or it shall be 2" minimum pipe size if the water closet bend is 4" pipe
size.
2. A horizontal branch drain
serving both the lavatory and the bathtub or shower stall is 2" minimum pipe
size.
3. The length of the trap arm
for the bathtub or shower stall is within the limits of Table 12.8.1. If not,
the bathtub or shower stall shall be individually vented.
4. The distance from the outlet of the water
closet to the connection of the wet vent is within the limits established by
Section 12.8.4. Otherwise, the water closet shall be individually
vented.
5. A horizontal branch
serving the lavatory and the bathtub or shower stall shall connect to the stack
at the same level as the water closet, or it may connect to the water closet
bend, or the lavatory and bathtub or shower stall may individually connect to
the water closet bend.
6. When the
bathroom group is the topmost load on a stack, a horizontal branch serving the
lavatory and the bathtub or shower stall may connect to the stack below the
water closet bend, or the lavatory and the bathtub, or shower stall may
individually connect to the stack below the water closet
bend.
12.10.2
Double Bathtubs and Lavatories
Two lavatories and two bathtubs or showers back-to-back may
be installed on the same horizontal branch with a common vent for the
lavatories and with no back vent for the bathtubs or shower stalls provided the
wet vent is 2" in size and the lengths of the tub/shower drains conform to
Table 12.8.1.
12.10.3
Multi-Story Bathroom Groups
a. On the lower
floors of a stack, the waste pipe from one or two lavatories may be used as a
wet vent for one or two bathtubs or showers as provided in Section
12.10.2.
b. Each water closet below
the top floor shall be individually back vented.
EXCEPTION: The water closets in bathroom groups shall not be
required to be back vented if the following conditions are met:
(1) The 2" waste serving the tubs/showers and
lavatories connect directly into the water closet bend with a 45#[degrees]# wye
tap in the direction of flow; or
(2) A special stack fitting is used that
consists of a 3" or 4" closet opening and two side inlets each 2" in size and
the inverts of which are above the center, and below the top of the water
closet opening; and one of the 2" inlets is connected to the tub/shower drains,
and the other is connected to the waste pipe from a maximum of two lavatories
that are vented to a vent stack or stack vent; or
(3) In lieu of the special stack fitting of
Section 12.10.3b(2) above, 4" closet bends with two 2" wye taps may be
used.
12.10.4
Bathtubs and Water Closets
a. An individually
vented bathtub in a single bathroom group shall be permitted to serve as a wet
vent for the water closet if all of the following conditions are met:
1. The wet vent is 2" minimum size.
2. The distance from the outlet of the water
closet to the connection of the wet vent is within the limits established by
Section 12.8.4. Otherwise, the water closet shall be individually
vented.
12.10.5
Reserved
12.10.6 Floor Drains and
Floor Sinks
a. A lavatory or sink shall be
permitted to serve as a wet vent for a floor drain or floor sink if all of the
following conditions are met:
1. The wet vent
shall be not less than 1-1/2" size for a 1 DFU lavatory or 2" for 2 DFU
sink.
2. The wet vent shall be
larger than 1/2 the size of the drain for the floor drain or floor
sink.
3. The distance from the
outlet of the floor drain or floor sink to the connection of the wet vent shall
be within the limits established by Table
12.8.1.
11. Chapter 13 of the plumbing subcode,
entitled "Storm Water Drainage," shall be amended as follows:
i. In Section 13.1.5, Foundation Drains,
Notes a. through d. shall be deleted and the following shall be inserted: "a.
Foundation drains shall be provided in accordance with the building
subcode."
ii. Section 13.1.10.1,
Primary Roof Drainage, shall be amended to delete the last sentence and to
substitute in lieu thereof "Rainfall rates shall be applied so that the
applicable rainfall rate for Burlington and Ocean counties and all counties
south shall be six inches per hour and for Mercer and Monmouth counties and all
counties north, the applicable rainfall rate shall be five inches per
hour."
iii. Section 13.1.10.2,
"Secondary Roof Drainage," shall be deleted and the following shall be
inserted:
Section 13.1.10.2 Overflow Roof Drainage
Where parapet walls extend or other construction extends
above the roof, creating areas where storm water would become trapped if the
primary roof drainage system failed to provide sufficient drainage, an overflow
roof drainage system consisting of *scuppers*, standpipes, or roof drains shall
be provided. The capacity of the primary system shall not be considered in the
sizing of the overflow system.
(1)
Subsection b. shall be deleted and the following shall be inserted: "Where
overflow drainage is provided by means of roof drains or standpipe, the
overflow system shall be permitted to connect to the primary roof drainage
system."
(2) Subsection c.
"secondary" shall be deleted and "overflow" shall be inserted.
(3) Subsection d. shall be amended as
follows: Add Table A.5 after Appendix A. and delete the second and third
sentences.
iv. In Section
13.8, Sizing for Continuous or Intermittent Flows, "Section A-3 and Table A-1
in Appendix A" shall be deleted and the following shall be inserted: "5 IN/HR =
0.052 GPM/SF and 6 IN/HR = 0.062 GPM/SF."
12. Chapter 15 of the plumbing subcode,
entitled "Tests and Maintenance" is amended as follows:
i. Add new Section 15.6.1 as follows: 15.6.1
Combination Domestic/Fire Water Service Systems: Piping for combination
domestic/fire water services systems shall be pressure tested to not less than
200 psig and shall maintain that pressure without loss for 2 hours.
ii. Add new Section 15.6.1.1 as follows:
15.6.1.1 Leakage: The following provisions shall apply to buried pipe in all
combination domestic/fire water service systems, except for limited sprinkler
systems:
(1) The amount of leakage at the
joints shall be no greater than 2 qt/hr (1.89 L/hr) per 100 joints or gaskets,
regardless of pipe diameter.
(2)
The amount of leakage in accordance with (1) above shall be permitted to be
increased in increments of 1 fluid ounce (30 ml) per inch valve diameter per
hour for each metal seated valve that isolates the test section.
(3) The amount of leakage in buried piping
shall be measured at the test pressure specified by pumping from a calibrated
container.
iii. Add new
Section 15.9 as follows: 15.9 Flushing of Piping: Lead-in connections to system
risers and fire service mains from the water supply to the system riser
(excluding limited systems) shall be flushed completely before connection is
made to sprinkler piping. The flushing operation shall be continued for a
sufficient amount of time to ensure that the system is thoroughly cleaned. The
minimum rate of flow shall be not less than one of the following:
(1) The hydraulically calculated water demand
rate of the system, including any hose requirements.
(2) The flow that is necessary to provide a
velocity of 10 ft/sec (3.1 m/sec).
(3) The maximum flow rate available to the
system under fire conditions.
13. Chapter 16 of the plumbing subcode,
entitled "Regulations Governing Individual Sewage Disposal Systems for Homes
and Other Establishments Where Public Sewer Systems Are Not Available," shall
be deleted and the following shall be inserted:
i. "16.1 General. On-site sewage disposal
systems are under the jurisdiction of the Department of Environmental
Protection and the county or local boards of health, as applicable."
ii. "16.1.7 Abandoned Disposal Systems. When
an existing building is being demolished and the existing sewage disposal
system is abandoned or an existing sewage disposal system is being abandoned
and a connection is being made to the public sewer systems, the plumbing
subcode official shall ensure that the existing abandoned tank is disconnected
from the building, pumped out, and filled with gravel, stones, or soil
material. Sewage disposal systems that are abandoned without an associated
hookup to a public sewer system are to be inspected by the health department
having jurisdiction."
14.
Chapter 17 of the plumbing subcode entitled, "Potable Water Supply Systems,"
shall be deleted and the following shall be inserted:
i. "17.1 General. On-site water supply
systems are under the jurisdiction of the Department of Environmental
Protection and county or local boards of health, as
applicable."
15. Chapter
18 of the plumbing subcode, entitled Referenced Standards, shall be amended as
follows:
i. In Section 18.2, Standards
Organizations, insert the following: " Pool & Hot Tub Alliance (Formally
APSP--The Association of Pool and Spa Professionals), 2111 Eisenhower Avenue,
Ste. 500, Alexandria, VA 22314, tel: 703-838-0083, fax: 703-549-0493," and
"International Code Council, Inc., 500 New Jersey Avenue, NW, 6th Floor,
Washington D.C. 20001, tel: 888-422-7233."
16. Appendix A of the plumbing subcode,
entitled "Sizing Storm Drainage Systems," shall be deleted in its
entirety.
17. Appendix E of the
plumbing subcode, entitled "Special Design Plumbing Systems," shall be amended
as follows:
i. Section E.9.3, Rainfall Rates,
shall be deleted and the following shall be inserted: "Rainfall rates shall be
applied so that the applicable rainfall rates for Burlington and Ocean counties
and all counties south, shall be six (6) inches per hour; for Mercer and
Monmouth counties and all counties north, the applicable rainfall rate shall be
five (5) inches per hour."
ii.
Section E.9.4, Secondary Roof Drainage, shall be deleted.
18. Appendix G, entitled "We-Stand Excerpts,"
shall not be adopted as part of the plumbing subcode. Appendix G may be used as
a reference standard for special design plumbing systems in accordance with
Appendix E.
19. Appendix L,
entitled "Tiny Houses," shall be adopted as part of this
subcode.