Current through Register Vol. 56, No. 18, September 16, 2024
(a)
For the purposes of this subchapter, alteration of an elevator device means any
change to equipment other than minor work as provided in (b) below and ordinary
maintenance, as defined at
N.J.A.C.
5:23-2.7(c)6. Alteration of
an elevator device shall comply with the applicable requirements of Section 8.7
and Appendix L of the most recent edition of ASME A17.1, referenced in the
building subcode, or with the applicable requirements of the most recent
edition of ASME A18.1, or ASME A90.1 referenced in the building subcode.
1. For purposes of the elevator subcode,
"alteration" shall mean stand-alone projects undertaken on elevator devices
and, with the exception of
N.J.A.C.
5:23-6.6(e)22, shall not be
used to trigger any additional requirements of
N.J.A.C. 5:23-6.6. If
work on an elevator device or devices is part of a larger scope of work, then
the appropriate category of work, as determined under the Rehabilitation
Subcode, and the accompanying requirements shall apply.
(b) For the purposes of this subchapter,
minor work on an elevator device shall mean work as outlined below and meeting
the applicable sections and Appendix L of ASME A17.1, adopted by reference in
the building subcode:
1. Alteration to
hoistway enclosures--Sections 8.7.2.1.1 and 8.7.3.1 only as it pertains to
Section 8.7.2.1.1;
2. Alteration to
construction at top of hoistways--Section 8.7.2.1.3. Exception: Section
5.2.1.4.4 for Limited-Use/Limited-Application elevators (LULA));
3. Alteration at the bottom of
hoistways--Section 8.7.2.1.4. Exception: Section 5.2.1.4.2 for
Limited-Use/Limited-Application elevators (LULA);
4. Alteration to hoistways that affect
control of smoke and hot gases--Section 8.7.2.1.5;
5. Construction and alteration of machine
room and machinery spaces--Sections 8.7.2.7 and 8.7.3.7;
6. Installation and alteration of electrical
equipment, wiring, pipes and ducts in hoistway and machine rooms--Sections
8.7.2.8 and 8.7.3.8;
7. Replacement
of a controller, without any change in the type of operation or
control--5:23-6.8(i)4;
8. Alteration to pits--Sections 8.7.2.2 and
8.7.3.2;
9. Alteration to bottom
and top of car and counterweight clearances and runbys--Sections 8.7.2.4 and
8.7.3.4. Exception: Sections 5.2.1.4.2 and 5.2.1.4.4 for
Limited-Use/Limited-Application elevators (LULA);
10. Alteration to horizontal car and
counterweight clearances--Sections 8.7.2.5 and 8.7.3.5;
11. Additions, alterations or replacements of
hoistway entrances--Sections 8.7.2.10 and 8.7.3.10;
12. Installation or alteration of hoistway
door locking devices, access switches, parking devices and unlocking
devices--Sections 8.7.2.11 and 8.7.3.11;
13. Alteration or addition of power operation
of hoistway doors--Sections 8.7.2.12 and 8.7.3.12;
14. Alteration of spring buffers and
bumpers--Sections 8.7.2.23 and 8.7.3.27;
15. Alteration of counterweights--Sections
8.7.2.22 and 8.7.3.26, with the exception of the addition of counterweights to
previously uncounterweighted elevators;
16. Alteration of car frames and
platforms--Sections 8.7.2.15.1 and 8.7.3.14;
17. Alteration of car enclosures, car doors,
gates, and illumination of cars--Sections 8.7.2.14, with the exception of the
installation of new cars, and 8.7.3.13;
18. Alteration to car emergency signaling
devices--Sections 8.7.2.28 and 8.7.3.31.8(a);
19. Use of freight elevators to carry
passengers, hydraulic elevators only--Section 8.7.2.16.3;
20. Relocation of power unit--Section
8.7.3.23.6;
21. Replacement or
alteration of tanks--Section 8.7.3.29;
22. Addition or alteration of top-of-car
operating devices--Sections 8.7.2.27.1 and 8.7.3.31.1;
23. Addition or alteration or car-leveling or
truck-zoning--Section 8.7.2.27.2 and 8.7.3.31.2;
24. Alteration of anti-creep leveling
devices--Section 8.7.3.31.3;
25.
Change of power supply, hydraulic elevators only--Section 8.7.3.31.4;
26. Addition of rope equalizers--Sections
8.7.2.21.2 and 8.7.3.25.2;
27.
Addition of auxiliary rope-fastening devices--Section 8.7.2.21.3;
28. Alteration of manual operating devices
which are provided to manually operate elevators in case of power failure or an
alteration to auxiliary power lowering operation--Section 8.7.3.31.9;
29. Alteration of handrails on escalators and
moving walks--Sections 8.7.6.1.6 and 8.7.6.2.6;
30. Alteration or addition of lighting and
access to interiors and related electrical work--Sections 8.7.6.1.14 and
8.7.6.2.14;
31. Alteration of
entrances or egresses on escalators--Section 8.7.6.1.15;
32. Protection of Floor Openings--Sections
8.7.6.1.3 and 8.7.6.2.3; and
33.
Protection of Trusses and Machinery Spaces Against Fire--Sections 8.7.6.1.4 and
8.7.6.2.4.